MPT60 M1

MPT60 M1
1 / 45 PagesView full catalog

MPT60 M1

Product catalog summary
General Overview
The MPT60 series are compact, single-loop microprocessor temperature regulators with dimensions of 48x48 mm and a depth of 96 mm. They support various input types such as thermoresistance PT100, thermocouples, voltage, and current inputs. The device features a display for process values, programmable keys, and options for relay contacts and analogue outputs.
Technical Characteristics
The MPT60 supports sensors like PT100 and various thermocouples, offering precision data reading and supporting both ON-OFF and PID control types. It includes alarm handling capabilities and specific power supply requirements.
Display Messages
The instrument displays messages indicating operational status or errors, such as temperature out of range or sensor malfunctions. Users should consult the manual for troubleshooting.
Instrument Connection Overview
The front panel includes a display and LEDs indicating alarm status, load control, and temperature relative to the set-point. The terminal board supports sensor inputs, power supply connections, and relay contacts.
Installation Notes
Installation involves connecting appropriate sensors and configuring the instrument for specific control types (heating, cooling, servomotor, or valve control). Users should follow provided diagrams and instructions for optimal setup.
Control Functions
The device can regulate heating or cooling using the main relay, supports alarm outputs, and analogue outputs that vary with temperature. Users can program the instrument using the menu and set control parameters as needed.
Specifications
  • Alarm Settings: Allows setting maximum and minimum alarm values independent of the set point, configurable as minimum or maximum based on set-point comparison.
  • Control Types: Includes reverse (heating) and direct (cooling) functions, selectable using the SP5 key.
  • Analog Outputs: Options include 0-10V, 0-20mA, and 4-20mA, selectable based on process requirements.
Procedures
  • Alarm Configuration: Use the SP5 key to enable or disable alarms and set alarm values, confirming changes with the enter key.
  • Temperature Scale and Sensor Selection: Choose between Celsius and Fahrenheit scales and select the appropriate sensor type using the SP5 key.
  • Servomotor Control: Configure the servomotor's cycle time and dead band percentage to prevent actuation within a specified range.
Norms and Recommendations
  • Ensure all settings are within specified ranges to avoid errors. If out-of-range values are entered, the system defaults to the nearest valid value.
  • Reset to factory default parameters if necessary, as described in the 'Default Parameters' section.
Key Features
  • Heating and Cooling Control: The main relay manages heating, while the alarm relay handles cooling, including a cooling dead-band feature.
  • Servomotor and Valve Control: Detailed setup instructions for controlling servomotors and valves, including time settings and dead band configurations.
Conclusion
This technical document serves as a comprehensive guide for configuring and operating the instrument across various control scenarios. It emphasizes the importance of correct parameter settings and provides step-by-step instructions for each configuration task.
Specifications and Procedures
The document outlines procedures for configuring and operating the MPT60 thermoregulator, including instructions for entering passwords, setting up alarms, and configuring analogue inputs and outputs. Users can change settings using specific keys to increment or shift digits and confirm inputs.
Password and Setup
Access to the menu requires a password, which can be set between 0 and 9999, with the default being 0. The setup procedure involves using keys to adjust numbers and confirm selections.
Temperature Scale and Sensor Selection
The temperature scale can be set to Celsius or Fahrenheit, with various sensor types selectable using specific keys and confirmed with the enter key.
Analogue Inputs and Outputs
The MPT60 supports current and voltage inputs with configurable ranges. Analogue outputs can be used for motorized valves or readout, with options for 0-20 mA, 4-20 mA, and 0-10 V outputs.
Alarm Configuration
The thermoregulator offers programmable alarms with various settings, including absolute, percentage, and offset-based alarms. The alarm contact can be configured as normally open or closed, with programmable hysteresis.
PID Regulation
Allows programming of cycle time, proportional band, integrative and derivative action times, and a cutback function to reduce temperature overshoot. The self-tuning function can automatically calculate these parameters.
Cutback Function
This function helps reduce temperature overshoot by programming a cutback value in degrees, set automatically via self-tuning or manually based on observed overshoot.
Tables and Data
Includes tables detailing analogue output ranges and configurations for different sensor types and input scales, with step-by-step instructions for setting up various parameters.
Self-Tuning Function
Calculates PID parameters through a heating cycle, recommended to start at room temperature, away from the set point. Errors such as temperature exceeding the set point or sensor issues can abort the process, requiring user intervention.
On-Off Regulation
Allows hysteresis programming, with the main relay operating within a specified temperature range. A cooling dead band can be defined to manage heating-cooling regulation.
Soft-Start Function
Limits initial power to 30% to ensure a "cold" start, applicable in both PID and On-Off modes, but not available in direct control mode. The function can be canceled by user intervention.
Password Protection
Uses a password system to protect settings, allowing full access with a correct password, while an incorrect one restricts changes.
Default Parameters and Safety Notes
The "dEF" function resets the instrument to factory settings, erasing previous configurations. Safety precautions include using external switches and fuses, and avoiding environmental hazards. Mect srl disclaims responsibility for improper use of the instrument.
See more

Catalog excerpts

MPT60 M1-4

MPT60 M1 1.0 GENERAL POINTS The instruments of the family "MPT60" represent a series of " Single Loop" microprocessor temperature regulators in the standard 48x48 dimensions (96 mm. depth.) The complete version of the MPT60 instrument has the following technical characteristics: 1- Input from Thermoresistance PT100 ( scale -40.0 ÷ 200.0°C or -40 ÷ 800°C), or from thermocoupling Fe/CO (0÷600°C) and Cr/Al (0÷1200°C) and Pt-Pt/Rh (0 ÷ 1710°C), or from voltage ( 0÷ 10 V ) and current (0/4 ÷ 20 mA) selectable from the keyboard. 2- One display to see Process Value and 4 keys for an easy programmability....

 Open the catalog to page 4
MPT60 M1-5

MPT60 M1 Alarms Main Output Alarm output Power supply Analogue outputs Max load for current output Min load for voltage output Max voltage given Max current given Resolution of min. or max in the range: 0 ÷ F.S. °C/°F relay contact 220V /5A relay contact 220V /5A 25Vac or 115Vac or 230Vac or 12÷30 Vdc 0 ÷ 10 V – 0 ÷ 20 mA – 4 ÷ 20 mA 300 Ω 1 KΩ 10 V 20 mA 12 bits 1.2 DISPLAY MESSAGES The following table shows a summary of all the messages that the instrument can show on the display. Some are operating signals, others are indications of anomalies or non performance. In these cases we ask you to...

 Open the catalog to page 5
MPT60 M1-6

MPT60 M1 1.3 MPT INSTRUMENT CONNECTION OVERVIEW DESCRIPTION OF THE FRONT COMMANDS Display: temperature as read by sensor Led AL: alarm status indication or cooling action or servomotor control drive (if requested ) Led ON: load control indication Led = : the displayed temperature is coincident with set-point (± 2 degrees) Led 3: the displayed temperature is lower than set-point for more than 2 degrees Led 4: the displayed temperature is higher than set-point for more than 2 degrees Key : access to the programming functions : shows set-point. In program menu it increases the blinking digit. :...

 Open the catalog to page 6
MPT60 M1-7

MPT60 M1 DESCRIPTION OF THE TERMINAL BOARD inputs for sensor transducer power supply ( see configurations ) analogue outputs (OAP option) enable remote second set-point (if RSP option is requested) instrument power supply. If Vcc the terminal 7 = + contact NO of main relay ( A option ) or static output (C option) contact NO of alarm relay (if requested: 03 option) CONNECTIONS PT100 gnd PT100 Thermocouplings must be isolated. For thermocoupling connection use only compensated wire for the type of thermocouple in use. If shielded cable is used, connect the shield to ground at one end only. For...

 Open the catalog to page 7
MPT60 M1-8

VOLTAGE OR CURRENT INPUT CONNECTIONS CURRENT/VOLTAGE INPUT CONNECTIONS WITH TRANSDUCER POWER SUPPLY This connection can be used if the transducer power supply is configured ( see TERMINAL 3 CONFIGURATION). STATIC OUTPUTS CONNECTIONS V+ Be careful: this output is not isolated and should be used for an external solid state relay with double isolation between instrument and power line. RELAY CONNECTIONS NC 11 10 I=5Amax 9 NO load OPTION “F” or “G” CONTACT ALARM (not available with “F” or “G” option) ME4021_04 01/11

 Open the catalog to page 8
MPT60 M1-9

SERVOMOTOR CONNECTIONS valve supply valve opening 1.4 TERMINAL 3 CONFIGURATION ( TRANSDUCER POWER SUPPL Y) Open the instrument and set the jumper JP2 for a PT100 input (standard) or for a transducer power supply connection. ANALOGUE OUTPUTS CONNECTIONS

 Open the catalog to page 9
MPT60 M1-10

2.0 INSTALLATION NOTES 1. Copy the connection schemes on pages 7, 8 and 9 taking into account the following points: a- the instrument can operate with analogue inputs or temperature sensors of both thermoresistance and thermocoupling types. Only one of this sensors can be connected (attach the connection only for the chosen sensor, leaving the other connections free.). b- the connector diagram shows all the possible options that the instrument may have; if certain options are not required then the relative connections are not necessary. 2. Follow the instructions of the paragraph: 2.1: for heating...

 Open the catalog to page 10
MPT60 M1-11

2.1.1 DIAGRAM MENU' WITH HEATING OR COOLING CONTROL see "password J ^ 3 = number re|evQn+ +Q uSed +ab|e If yuo want to reach an item, use the To skip into the item press If you want to change a number, use the a to increment the blinking digit, and the ° key to shift the blinking digit. To exit the menu, press parameters will be stored.

 Open the catalog to page 11
MPT60 M1-12

if requested analogue outputs tCOn = In for heating control tCOn = dlr for cooling control

 Open the catalog to page 12
MPT60 M1-13

MPT60 M1 Table 3 ref. touch appears on NOTE key display 1 enter PASS PASSWORD 2 enter 0 000 In this phase the instrument asks for the Password in order to allow the changing in menù. The number memorized by the factory is 0, but any number between 0 and 9999 can be memorized by writing where “CPAS” appears (next displayed item). 3 0 0 00 Set Up Procedure. AL4 To digit the desired number touch the key " AL4" to move the flashing number to the right. 4 0 1 00 Touch the key " SP5" to increase the flashing SP 5 number. Confirm by “enter” 5 CPAS CHANGE PASSWORD 6 enter 0000 Number of the access key...

 Open the catalog to page 13
MPT60 M1-15

touch appears on NOTE key display SPr OFFS CORRECTION OF READING SP 5 TEMPERATURE enter 0010 Using the number "OFFS" it is possible to correct the displayed temperature by adding or subtracting a constant. To digit the number follow the procedure described in points 3 and 4. OFFS S.AL1 ALARM 1 SELECTION SP 5 enter tEnP Selection the kind of working Alarm1 tEnP = min or max absolute alarm value PEr = percentage alarm dELt = relative alarm at the set point SOGL = max absolute alarm value indipendent from Set Point To change this item use the “SP5“ key and confirm by “enter” AbA1 MINIMUM ALARM 1...

 Open the catalog to page 15
MPT60 M1-16

touch appears on NOTE key display ISA1 C A1 POSSIBILITY OF INVERTING THE RELAY SP 5 FUNCTION enter nA Possibility of inverting the relay function nA = normally open nC = normally closed Set the requested regulation by “SP5” and confirm with “enter“. C A1 AbtA KEY ALARM 1 ENABLE. SP 5 enter OFF On: key alarm 1 enabled OFF: key alarm1 disabled To change this item use the “SP5“ key and confirm by “enter” AbtA OUAn ANALOG OUTPUT SELECTION (if required) SP 5 enter 0 10 If analogue outputs are requested touch the key "SP5" until the output required appears on the display and then confirm with "enter"....

 Open the catalog to page 16

All MECT SRL catalogs and technical brochures

  1. TPAC1008

    22  Pages

  2. TPAC1007

    14  Pages

  3. TPAC1006

    22  Pages

  4. MPA-MPV M6

    42  Pages

  5. MPA386 M6

    39  Pages

  6. MPP P6

    19  Pages

  7. MPA-MPV P6

    18  Pages

  8. MPX28

    8  Pages

  9. MPSN20

    2  Pages

  10. MPCV015

    20  Pages

  11. MPT390 M6

    61  Pages

  12. MPT91 M1

    66  Pages

  13. MPT90 M1

    46  Pages

  14. MPT100 M1

    35  Pages

  15. MPCIB396 P6

    41  Pages

  16. MPCIB20 M1

    25  Pages

  17. MPCT301 P6

    53  Pages

  18. MPCT300 P6

    37  Pages

  19. MPCT30 P6

    36  Pages

  20. MPCT20 M1

    35  Pages

  21. MP2200 M6

    44  Pages

  22. MP1200 P6

    36  Pages

  23. MPPV340 M6

    40  Pages

  24. MPO347 M6

    40  Pages

  25. MPP323 M6

    42  Pages

  26. MPPV010 P6

    40  Pages

  27. MP45 P6

    18  Pages

  28. MPM P6

    34  Pages

  29. MP30 P2

    15  Pages

  30. MP20 M1

    35  Pages

  31. MPNC030

    12  Pages

  32. TPLC005

    28  Pages

  33. MPNC020

    13  Pages

  34. MPNC010

    25  Pages

  35. TP1070

    15  Pages

  36. TP1057

    15  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.