Catalog excerpts
USER'S MANUAL
Open the catalog to page 1MPT390 M6 1.0 GENERAL POINTS The instruments of the family " MPT/390/M6" represent a series of " Single Loop" microprocessor temperature regulators in the standard 48x96 dimensions (120 mm. depth.) The complete version of the MPT/390/M6 instrument has the following technical characteristics: 1- Input from Thermoresistance PT100 ( scale -40.0 ÷ 200.0°C or -40 ÷ 800°C), or from thermocoupling Fe/CO (0÷600°C) and Cr/Al (0÷1200°C) and Pt-Pt/Rh (0 ÷ 1710°C), or from voltage ( 0÷ 10 V ) and current (0/4 ÷ 20 mA) selectable from the keyboard. 2- Two display to see Set-Point and Process Value and 6...
Open the catalog to page 5MPT390 M6 on-off / pid HY in the range 0 ÷ F.S. °C/°F cycle time in the range:1 ÷ 200 sec proportional band: 0 ÷ F.S. °C/°F integrative time: 0 ÷ 6000 sec. derivative time: 0 ÷ 600 sec cutback const.: 0 ÷ F.S. °C/°F of min. or max in the range: 0 ÷ F.S. °C/°F Alarms Exchange relay 220V /5A Main Output relay contact 220V /5A Alarm output Power supply 90 ÷ 260 Vac/Vdc 20÷30Vac/Vdc Analogue outputs 0 ÷ 10 V – 0 ÷ 20 mA – 4 ÷ 20 mA Max load for current output 300 Ω Min load for voltage output 1 KΩ 10 V Max voltage given 20 mA Max current given 12 bits Resolution by TA/1 A Heater breaker control...
Open the catalog to page 6MPT390 M6 1.3 MPT INSTRUMENT CONNECTION OVERVIEW DESCRIPTION OF THE FRONT COMMANDS input readout key for ramp programming. It is possible to set up 3 programs of 8 steps each and execute one of them. set point readout keys to change the set point (not working if ramp in progress) key to enter main menu programming functions PV-Upper Display: temperature as read by sensor SP-Lower Display: set-point (power percentage on manual control) Led AL1: alarm status indication or cooling action or servomotor control drive (if requested ) Led AL2: alarm 2 status indication (if requested) Led Rp: ramp...
Open the catalog to page 7DESCRIPTION OF THE TERMINAL BOARD Thermocoupling sensor principal exchange relay ( NO contact). principal exchange relay ( COM contact). principal exchange relay ( NC contact). contact NO of alarm relay 1 (if requested) contact NO of alarm relay 2 (if requested) static output for main operations (terminal 8: power supply, for exsternal static relay, of around 16 Vdc). load control break HB (if requested) instrument power supply. Between terminals 13 and 15 power at 90/260 Vac/Vdc, or 12/30Vac/Vdc if requested. analogue outputs (if requested). serial output connections (if requested)....
Open the catalog to page 8For thermoresistance connection pay attention to the line resistance: if too high there may be some errors in readout. Use the same kind of wire for the three connections. If shielded cable is used, connect the shield to ground at one end only. THERMOCOUPLING CONNECTIONS Thermocouplings must be isolated. only compensated wire for the type If shielded cable is used, connect CURRENT INPUT CONNECTIONS
Open the catalog to page 9STATIC OUTPUTS CONNECTIONS V+ Be careful: this output is not isolated and may be used for an external solid state relay with double isolation between instrument and power line. SERVOMOTOR CONNECTIONS Valve closing Valve supply Servomotor Valve opening SERIAL OUTPUTS AND ANALOGUE OUTPUTS CONNECTIONS See dedicated paragraphs. ME4014_15 10/11
Open the catalog to page 10MPT390 M6 2.0 INSTALLATION NOTES 1. Copy the connection schemes on pages 6, 7 and 8 taking into account the following points: a- the instrument can operate with analogue inputs or temperature sensors of both thermoresistance and thermocoupling types. Only one of this sensors can be connected (attach the connection only for the chosen sensor, leaving free the other connections.). b- the connector diagram shows all the possible options that the instrument may have; if certain options are not required then the relative connections are not necessary. 2. Follow the instructions of the paragraph:...
Open the catalog to page 112.1.1 DIAGRAM MENU WITH HEATING OR COOLING CONTROL I ^ 3 = number relevant to used table FE-CO Cr-AL Search for the item to change, shown in the upper display using key The value to change is shown on the lower display. If you must change a number, use the key to increment the blinking digit, key to shift the blinking digit, an you must select an item, use the To exit the menu, press I_I : the modified parameters will be stored.
Open the catalog to page 12if requested analogue outputs tCOn = In for heating control tCOn = dlr for cooling control bAud bAud if requested serial output
Open the catalog to page 13MPT390 M6 Table 3 ref. touch appears on appears on NOTES key PV display SP display PASS 0 000 In this phase the instrument asks for the 1 enter Password in order to save the data already programmed. The number memorized by the factory is 0, but any number between 0 and 9999 can be memorized by writing where CPAS appears (next displayed item). PASS 0 0 00 Set Up Procedure. 2 SP-4 To digit the desired number touch the key " SP-4" to move the flashing number to the right. SP+ PASS 0 1 00 3 Touch the key " SP+5" to increase the 5 flashing number CPAS 0 000 Number of the access key to the 4...
Open the catalog to page 14MPT390 M6 ref. touch appears on appears on NOTES key PV display SP display IS t 0000 Set the requested reading with the 8 enter beginning of the analogue input. To digit the number see 2 and 3 paragraphs. FS t 1000 Set the requested reading with the full 9 enter scale of the analogue input. To digit the number see 2 and 3 paragraphs. Out rISC Choose rISC for heating regulation with 10 enter the main relay. Set the requested regulation by “SP+5” and confirm with “enter“. LISP 0 000 Lower limit set-point. To digit the 11 enter number follow the procedure described in points 2 and 3 LSSP 0 000...
Open the catalog to page 15MPT390 M6 ref. touch appears on appears on NOTES key PV display SP display AbA1 On Minimum alarm enable. 16 enter On: Minimum alarm relay is always enabled OFF: Minimum alarm relay is enabled after the first time the temperature reaches the alarm value To change this item use the “SP+5“ key and confirm by “enter” AL1 0 000 Alarm value set up (if requested). To 17 enter digit the value see steps 2 and 3. An alarm can work as minimum alarm (if < set-point) or maximum alarm (if > setpoint). ISA1 001 Alarm 1 hysteresis set up 18 enter 19 Possibility of inverting the relay 1 function nA =...
Open the catalog to page 16All MECT SRL catalogs and technical brochures
-
TPAC1008
22 Pages
-
TPAC1007
14 Pages
-
TPAC1006
22 Pages
-
MPA-MPV M6
42 Pages
-
MPA386 M6
39 Pages
-
MPP P6
19 Pages
-
MPA-MPV P6
18 Pages
-
MP40 P6 Simple imput
16 Pages
-
MP40 P6 Multi input
17 Pages
-
MPX28
8 Pages
-
MPSN20
2 Pages
-
MPCV015
20 Pages
-
MPT91 M1
66 Pages
-
MPT90 M1
46 Pages
-
MPT60 M1
45 Pages
-
MPT100 M1
35 Pages
-
MPCIB396 P6
41 Pages
-
MPCIB20 M1
25 Pages
-
MPCT301 P6
53 Pages
-
MPCT300 P6
37 Pages
-
MPCT30 P6
36 Pages
-
MPCT20 M1
35 Pages
-
MP2200 M6
44 Pages
-
MP1200 P6
36 Pages
-
MPPV340 M6
40 Pages
-
MPO347 M6
40 Pages
-
MPP323 M6
42 Pages
-
MPPV010 P6
40 Pages
-
MP45 P6
18 Pages
-
MPM P6
34 Pages
-
MP30 P2
15 Pages
-
MP20 M1
35 Pages
-
MPNC030
12 Pages
-
TPLC005
28 Pages
-
MPNC020
13 Pages
-
MPNC010
25 Pages
-
TP1070
15 Pages
-
TP1057
15 Pages