MPT390 M6
61Pages

{{requestButtons}}

Catalog excerpts

MPT390 M6 - 5

MPT390 M6 1.0 GENERAL POINTS The instruments of the family " MPT/390/M6" represent a series of " Single Loop" microprocessor temperature regulators in the standard 48x96 dimensions (120 mm. depth.) The complete version of the MPT/390/M6 instrument has the following technical characteristics: 1- Input from Thermoresistance PT100 ( scale -40.0 ÷ 200.0°C or -40 ÷ 800°C), or from thermocoupling Fe/CO (0÷600°C) and Cr/Al (0÷1200°C) and Pt-Pt/Rh (0 ÷ 1710°C), or from voltage ( 0÷ 10 V ) and current (0/4 ÷ 20 mA) selectable from the keyboard. 2- Two display to see Set-Point and Process Value and 6...

Open the catalog to page 5
MPT390 M6 - 6

MPT390 M6 on-off / pid HY in the range 0 ÷ F.S. °C/°F cycle time in the range:1 ÷ 200 sec proportional band: 0 ÷ F.S. °C/°F integrative time: 0 ÷ 6000 sec. derivative time: 0 ÷ 600 sec cutback const.: 0 ÷ F.S. °C/°F of min. or max in the range: 0 ÷ F.S. °C/°F Alarms Exchange relay 220V /5A Main Output relay contact 220V /5A Alarm output Power supply 90 ÷ 260 Vac/Vdc 20÷30Vac/Vdc Analogue outputs 0 ÷ 10 V – 0 ÷ 20 mA – 4 ÷ 20 mA Max load for current output 300 Ω Min load for voltage output 1 KΩ 10 V Max voltage given 20 mA Max current given 12 bits Resolution by TA/1 A Heater breaker control...

Open the catalog to page 6
MPT390 M6 - 7

MPT390 M6 1.3 MPT INSTRUMENT CONNECTION OVERVIEW DESCRIPTION OF THE FRONT COMMANDS input readout key for ramp programming. It is possible to set up 3 programs of 8 steps each and execute one of them. set point readout keys to change the set point (not working if ramp in progress) key to enter main menu programming functions PV-Upper Display: temperature as read by sensor SP-Lower Display: set-point (power percentage on manual control) Led AL1: alarm status indication or cooling action or servomotor control drive (if requested ) Led AL2: alarm 2 status indication (if requested) Led Rp: ramp...

Open the catalog to page 7
MPT390 M6 - 8

DESCRIPTION OF THE TERMINAL BOARD Thermocoupling sensor principal exchange relay ( NO contact). principal exchange relay ( COM contact). principal exchange relay ( NC contact). contact NO of alarm relay 1 (if requested) contact NO of alarm relay 2 (if requested) static output for main operations (terminal 8: power supply, for exsternal static relay, of around 16 Vdc). load control break HB (if requested) instrument power supply. Between terminals 13 and 15 power at 90/260 Vac/Vdc, or 12/30Vac/Vdc if requested. analogue outputs (if requested). serial output connections (if requested)....

Open the catalog to page 8
MPT390 M6 - 9

For thermoresistance connection pay attention to the line resistance: if too high there may be some errors in readout. Use the same kind of wire for the three connections. If shielded cable is used, connect the shield to ground at one end only. THERMOCOUPLING CONNECTIONS Thermocouplings must be isolated. only compensated wire for the type If shielded cable is used, connect CURRENT INPUT CONNECTIONS

Open the catalog to page 9
MPT390 M6 - 10

STATIC OUTPUTS CONNECTIONS V+ Be careful: this output is not isolated and may be used for an external solid state relay with double isolation between instrument and power line. SERVOMOTOR CONNECTIONS Valve closing Valve supply Servomotor Valve opening SERIAL OUTPUTS AND ANALOGUE OUTPUTS CONNECTIONS See dedicated paragraphs. ME4014_15 10/11

Open the catalog to page 10
MPT390 M6 - 11

MPT390 M6 2.0 INSTALLATION NOTES 1. Copy the connection schemes on pages 6, 7 and 8 taking into account the following points: a- the instrument can operate with analogue inputs or temperature sensors of both thermoresistance and thermocoupling types. Only one of this sensors can be connected (attach the connection only for the chosen sensor, leaving free the other connections.). b- the connector diagram shows all the possible options that the instrument may have; if certain options are not required then the relative connections are not necessary. 2. Follow the instructions of the paragraph:...

Open the catalog to page 11
MPT390 M6 - 12

2.1.1 DIAGRAM MENU WITH HEATING OR COOLING CONTROL I ^ 3 = number relevant to used table FE-CO Cr-AL Search for the item to change, shown in the upper display using key The value to change is shown on the lower display. If you must change a number, use the key to increment the blinking digit, key to shift the blinking digit, an you must select an item, use the To exit the menu, press I_I : the modified parameters will be stored.

Open the catalog to page 12
MPT390 M6 - 13

if requested analogue outputs tCOn = In for heating control tCOn = dlr for cooling control bAud bAud if requested serial output

Open the catalog to page 13
MPT390 M6 - 14

MPT390 M6 Table 3 ref. touch appears on appears on NOTES key PV display SP display PASS 0 000 In this phase the instrument asks for the 1 enter Password in order to save the data already programmed. The number memorized by the factory is 0, but any number between 0 and 9999 can be memorized by writing where CPAS appears (next displayed item). PASS 0 0 00 Set Up Procedure. 2 SP-4 To digit the desired number touch the key " SP-4" to move the flashing number to the right. SP+ PASS 0 1 00 3 Touch the key " SP+5" to increase the 5 flashing number CPAS 0 000 Number of the access key to the 4...

Open the catalog to page 14
MPT390 M6 - 15

MPT390 M6 ref. touch appears on appears on NOTES key PV display SP display IS t 0000 Set the requested reading with the 8 enter beginning of the analogue input. To digit the number see 2 and 3 paragraphs. FS t 1000 Set the requested reading with the full 9 enter scale of the analogue input. To digit the number see 2 and 3 paragraphs. Out rISC Choose rISC for heating regulation with 10 enter the main relay. Set the requested regulation by “SP+5” and confirm with “enter“. LISP 0 000 Lower limit set-point. To digit the 11 enter number follow the procedure described in points 2 and 3 LSSP 0 000...

Open the catalog to page 15
MPT390 M6 - 16

MPT390 M6 ref. touch appears on appears on NOTES key PV display SP display AbA1 On Minimum alarm enable. 16 enter On: Minimum alarm relay is always enabled OFF: Minimum alarm relay is enabled after the first time the temperature reaches the alarm value To change this item use the “SP+5“ key and confirm by “enter” AL1 0 000 Alarm value set up (if requested). To 17 enter digit the value see steps 2 and 3. An alarm can work as minimum alarm (if < set-point) or maximum alarm (if > setpoint). ISA1 001 Alarm 1 hysteresis set up 18 enter 19 Possibility of inverting the relay 1 function nA =...

Open the catalog to page 16

All MECT SRL catalogs and technical brochures

  1. TPAC1008

    22 Pages

  2. TPAC1007

    14 Pages

  3. TPAC1006

    22 Pages

  4. MPA-MPV M6

    42 Pages

  5. MPA386 M6

    39 Pages

  6. MPP P6

    19 Pages

  7. MPA-MPV P6

    18 Pages

  8. MPX28

    8 Pages

  9. MPSN20

    2 Pages

  10. MPCV015

    20 Pages

  11. MPT91 M1

    66 Pages

  12. MPT90 M1

    46 Pages

  13. MPT60 M1

    45 Pages

  14. MPT100 M1

    35 Pages

  15. MPCIB396 P6

    41 Pages

  16. MPCIB20 M1

    25 Pages

  17. MPCT301 P6

    53 Pages

  18. MPCT300 P6

    37 Pages

  19. MPCT30 P6

    36 Pages

  20. MPCT20 M1

    35 Pages

  21. MP2200 M6

    44 Pages

  22. MP1200 P6

    36 Pages

  23. MPPV340 M6

    40 Pages

  24. MPO347 M6

    40 Pages

  25. MPP323 M6

    42 Pages

  26. MPPV010 P6

    40 Pages

  27. MP45 P6

    18 Pages

  28. MPM P6

    34 Pages

  29. MP30 P2

    15 Pages

  30. MP20 M1

    35 Pages

  31. MPNC030

    12 Pages

  32. TPLC005

    28 Pages

  33. MPNC020

    13 Pages

  34. MPNC010

    25 Pages

  35. TP1070

    15 Pages

  36. TP1057

    15 Pages