MPP P6
19Pages

{{requestButtons}}

Catalog excerpts

MPP P6 - 3

INDEX INDEX ------------------------------------------------------------------------------------------- 3 1.0 GENERAL POINTS--------------------------------------------------------------- 4 1.1 TECHNICAL CHARACTERISTICS ------------------------------------------------- 4 1.2 DISPLAY SIGNALS-------------------------------------------------------------------- 4 1.3 CONNECTION DESCRIPTIONS ---------------------------------------------------- 5 WIRING DIAGRAM FOR POTENTIOMETER INPUT ---------------------------- 7 2.0 INSTALLATION NOTES-------------------------------------------------------- 7...

Open the catalog to page 3
MPP P6 - 4

1.0 GENERAL POINTS The instruments of the MPP series in the P6 type container (75mm depth) use the potentiometer tranducer. The main characteristics are as follows: • two alarms with exchange relay output • alarm programming and 6 key calibration on instrument front panel for ease of use • 9999 point display • the 'hold' function operates directly from the terminal board ( with memory of value displayed ) and ' tara recovery ' (automatic zeroing). • possibility of programming delay time and hysteresis alarms using hidden menu which is password protected. • possibility of fixed zero setup •...

Open the catalog to page 4
MPP P6 - 5

1.3 CONNECTION DESCRIPTIONS KEYBOARD DESCRIPTION : alarm setup 1 : alarm setup 2 : increments blinking digit in menu or decimal point set-up : shifts blinking digit in menu : setup of reading scale start point : set up of reading scale end point + : menu access point

Open the catalog to page 5
MPP P6 - 6

Terminals 4,5,6 Terminals 7,8,9 Terminals 13 and 15 agnd out mA out V rec. tara hold dgnd 2.5Vref InIn+ TERMINAL BOARD DESCRIPTION - alarm output 2 - alarm output 1 - instrument power supply (25Vac, 90÷260Vac/Vdc) in dc power supply, terminals 13 is positive and 15 negative Terminals 29 and 30 - input measure Terminal 28 - potentiometer power supply (MPP) Terminals 22, 23 and 24: - analog outputs (if requested) Terminal 26 - Hold: shortcircuiting terminals 26 and 27 will memorize the reading Terminal 25 - Recovery tara: 1) Terminals 25-27 open: the reading is the same as the programmed...

Open the catalog to page 6
MPP P6 - 7

rec. tara hold dgnd 2.5Vref InIn+ WIRING DIAGRAM FOR POTENTIOMETER INPUT 2.0 INSTALLATION NOTES 2.1 INSTALLATION PROCEDURE 1- Undertake the linkups on page 5, 6, 7 2- Switch on the instrument 3- Use the “zero” key to set up the value that must coincide with the minimum input value (minimum potentiometer) 4- Use the “FS↵“ key to set up the value that must coincide with the maximum input value (maximum potentiometer) 5- Use the “5d.p.” key to set up the decimal point as required 6- Use the SET1 key to set up alarm value 1 7- Use the SET2 key to set up alarm value 2. 8- The instrument is now...

Open the catalog to page 7
MPP P6 - 8

See the paragraph "Instrument Setup". There now follow examples of zero calibration which are also true for end scale and alarms using the personalized keys F.S., SET1 and SET2. Touch the zero key. The display will visualize the value which it keeps in memory with the first left hand digit Touch the " ^ " key to move the flashing flashing value. Confirm the programmed number by To program the decimal point observe the following indications. Touch the ^ key with the instrument in measuring mode. A decimal point will light up. In order to move this point touch the indicated key until the...

Open the catalog to page 8
MPP P6 - 9

MPP P6 mect s.r.l. 2.3 RECOVERY TARA FUNCTION For “Recovery Tara” we mean a function that when in use zeroes the instrument readings. The Recovery Tara function with terminals 25 and 27 open is not in use and in these circumstances the instrument reading is linked to the programming parameters ISL, FSL and OFFS. At the moment when the terminals 25 and 27 are short circuited zero is displayed and the reading zeroed. This operation is indicated when the led 'Reset' lights up on the instrument front. Let us assume that the instrument, linked to a transducer, indicates a 100mm number. Shutting...

Open the catalog to page 9
MPP P6 - 10

Table 2 NOTE n seq. Touch Written key on display 1 PASS FS ↵ + Touch FS ↵ + SET1 keys for some seconds SET1 2 0 000 Digit the personal password ** (confirm with " FS FS ↵ ↵" ) 3 CPAS CHANGE PASSWORD ( if required see paragraph ) 5 4 AbSP SET POINT IN USE 5 5 on on = Set1 and Set2 keys in use FS ↵ oFF = Set1 and Set2 keys out of use To change use "5" key and confirm with " FS ↵" 6 AbSP 7 AbOF ZERO AND END SCALE IN USE 5 8 on on = zero and FS keys in use; OFF = zero and FS FS ↵ keys out of use. To change use "5" key and confirm with " FS ↵" 9 AbOF 10 AbPd DECIMAL POINT IN USE 5 11 on on =...

Open the catalog to page 10
MPP P6 - 11

NOTE Written on display 0000 Use this item to effect a zeroing that will be retained in memory. The number written can vary between -1999 and 1999. ** confirm with " FS ↵" OFFS LSPL LOWER LIMIT SETPOINT 0000 Setup the lower limit for the alarm value **(confirm with " FS ↵") LSPL LSPH UPPER LIMIT SETPOINT 0000 Setup the uppers limit for the alarm value **(confirm with " FS ↵") LSPH rL1 EXCHANGE RELAY 1 SET UP nA nA = normal open relay; nC = normal closed relay To change this use the "5" key and confirm with " FS ↵" rL1 HY1 HYSTERESIS ALARM 1 200 Set up required hysteresis (see Fig.2) with a...

Open the catalog to page 11
MPP P6 - 12

NOTE Written on display Sd2 DELAY SELECTION RELAY 2 no no = no delay time; EC = switch on delay; di = switch off delay; ECdi = delay switch on + off . To change use the "5" key and confirm with " FS ↵" Sd2 dL2 DELAY TIME ALARM 2 20.0 Delay set up for period between 0 and 20.0 secs. ** (confirm with " FS ↵") dL2 ZEFI FIXED ZERO SELECTION on OFF=standard display; ON=fixed zero display . To change use the "5" key and confirm with " FS ↵" ZEFI SEL.A ANALOGUE OUTPUT SCALE 4 20 4 20= analogue ouput 4÷20mA; 0 20= analogue output 0÷20mA; 0 10= analogue output 0÷10V. To change use the "5" key and...

Open the catalog to page 12

All MECT SRL catalogs and technical brochures

  1. TPAC1008

    22 Pages

  2. TPAC1007

    14 Pages

  3. TPAC1006

    22 Pages

  4. MPA-MPV M6

    42 Pages

  5. MPA386 M6

    39 Pages

  6. MPA-MPV P6

    18 Pages

  7. MPX28

    8 Pages

  8. MPSN20

    2 Pages

  9. MPCV015

    20 Pages

  10. MPT390 M6

    61 Pages

  11. MPT91 M1

    66 Pages

  12. MPT90 M1

    46 Pages

  13. MPT60 M1

    45 Pages

  14. MPT100 M1

    35 Pages

  15. MPCIB396 P6

    41 Pages

  16. MPCIB20 M1

    25 Pages

  17. MPCT301 P6

    53 Pages

  18. MPCT300 P6

    37 Pages

  19. MPCT30 P6

    36 Pages

  20. MPCT20 M1

    35 Pages

  21. MP2200 M6

    44 Pages

  22. MP1200 P6

    36 Pages

  23. MPPV340 M6

    40 Pages

  24. MPO347 M6

    40 Pages

  25. MPP323 M6

    42 Pages

  26. MPPV010 P6

    40 Pages

  27. MP45 P6

    18 Pages

  28. MPM P6

    34 Pages

  29. MP30 P2

    15 Pages

  30. MP20 M1

    35 Pages

  31. MPNC030

    12 Pages

  32. TPLC005

    28 Pages

  33. MPNC020

    13 Pages

  34. MPNC010

    25 Pages

  35. TP1070

    15 Pages

  36. TP1057

    15 Pages