MPNC020
1 /13Pages

MPNC020

MPNC020
1 /13Pages

Catalog excerpts

MPNC020-1

USER'S MANUAL digital input/output

 Open the catalog to page 1
MPNC020-4

1.0 Introduction To ensure fast installation and commissioning of described devices, we recommend that you carefully read the information in this manual. 1.1 Personnel Qualification The products described in this manual are for use only by personnel with experience in PLC programming, or technical specialist in the use of an electricaldriven automation. MECT Srl is not liable for failures caused by improper usage and damage to MECT devices or other devices, due to the non-compliance to the instructions contained in this manual. MECT Srl offers technical assistance through its technical office....

 Open the catalog to page 4
MPNC020-5

1.4 Security Attention Power down devices before any operation Attention MPNC020 must be installed in closets or cabinets accessible only by qualified personnel through a key or a tool. ESD (Electrostatic Discharge) The modules contain electronic components that can be destroyed by electrostatic discharge. Every time you handle the modules, be sure that you and the system are connected to ground. The device does not have an ON-OFF switch and an internal fuse. Power up occurs immediately after applying the correct voltage (please check the power source voltage indicated on the nameplate of the...

 Open the catalog to page 5
MPNC020-6

2.2 Technical Data Technical Characteristics Material Power supply Input (PNP) Polycarbonate, Polyamide 6.6 24Vdc +/-15% 3W 16 for model MPNC020 01 8 for model MPNC020 03 16 for model MPNC020 02 Output (PNP) 8 for model MPNC020 03 Max current for every output 500mAdc 2Adc Max current for all output Dimension W x H x L - Terminal - 22.5 mm x 108 mm x 115 mm Installation DIN 35 Climatic Environmental Condition Operative Temperature 0 °C ... 50 °C Storage Temperature -20 °C ... +85 °C Relative Humidity 5 % to 95 % without condensation Safe Electrical Isolation Air and creepage distance acc. to IEC...

 Open the catalog to page 6
MPNC020-7

Immunity to Interference for industrial areas acc. to EN 61000-6-4 (2001) Test Specification Limit Frequency Distance EN 55011 (AC supply, 79 dB (µV) 150 kHz ... 500 conducted) kHz kHz ... 30 73 dB (µV) 500 EN 55011 (radiated) 40 dB (µV/m) 30 MHz ... 230 10 m 47 dB (µV/m) 230 MHz ... 1 10 m Interference Emission for Industrial areas acc. to EN 61000-6-3 (2001) Test Specification Limit Frequency Distance EN 55022 (AC supply, 66 ... 56 dB 150 kHz ... 500 conducted) 56 dB (µV) 500 kHz ... 5 60 dB (µV) 5 MHz ... 30 EN 55022 (DC 40 ... 30 dB 150 kHz ... 500 supply/data, conducted) 30 dB (µA) 500 kHz...

 Open the catalog to page 7
MPNC020-8

2.3 Installation 2.3.1 Distances The system must be installed allowing enough space for heat transfer, installation and wiring. Avoiding wires overlapping also prevents electromagnetic compatibility problems. Fig 2: Spaces 2.3.2 Component Adding and Removal Attention Be sure that devices are not powered when performing component adding or removal. 2.3.3 Assembly sequence The insertion and removal of a single terminal is made by using the hook at the base of the terminal as shown. The assembly must begin with the insertion of the coupler (MPNC010 or TPLC005). After that, the required terminal...

 Open the catalog to page 8
MPNC020-9

adding terminals removing terminals Fig 3: Terminal adding and removal The instruments must be assembled on TBUS as shown below. MPNC010 or TPLC005 must be positioned to the right and the nodes to the left.

 Open the catalog to page 9
MPNC020-10

MPNC020 mect srl 2.3.4 DIN Rail and TBUS All modules must be attached directly onto a DIN rail type EN 50022 (DIN 35) on which their TBUS connection modules were properly inserted. TBUS connection modules perform internal communication between the bus coupler and terminals. modular connector DIN rail modular connector TBUS connection 2.3.5 Wiring Description MPNC10 and nodes daisy chain connection 1 2 3 4

 Open the catalog to page 10
MPNC020-11

TPLC005 and nodes daisy chain connection 1 2 3 4 nero black grigio gray giallo yellow verde green

 Open the catalog to page 11
MPNC020-13

mect srl MPNC020 03 8 ingressi + 8 uscite digitali PNP PNP digital 8 inputs + 8 outputs verde green grigio gray nero black giallo yellow Digital lines, if configured as inputs, are PNP type. ingresso / input Digital lines, if configured as outputs, are PNP type. Uscita / output 24Vpot 3 nero black 1 grigio gray gnd ME7015_03

 Open the catalog to page 13

All MECT SRL catalogs and technical brochures

  1. TPAC1008

    22  Pages

  2. TPAC1007

    14  Pages

  3. TPAC1006

    22  Pages

  4. MPA-MPV M6

    42  Pages

  5. MPA386 M6

    39  Pages

  6. MPP P6

    19  Pages

  7. MPA-MPV P6

    18  Pages

  8. MPX28

    8  Pages

  9. MPSN20

    2  Pages

  10. MPCV015

    20  Pages

  11. MPT390 M6

    61  Pages

  12. MPT91 M1

    66  Pages

  13. MPT90 M1

    46  Pages

  14. MPT60 M1

    45  Pages

  15. MPT100 M1

    35  Pages

  16. MPCIB396 P6

    41  Pages

  17. MPCIB20 M1

    25  Pages

  18. MPCT301 P6

    53  Pages

  19. MPCT300 P6

    37  Pages

  20. MPCT30 P6

    36  Pages

  21. MPCT20 M1

    35  Pages

  22. MP2200 M6

    44  Pages

  23. MP1200 P6

    36  Pages

  24. MPPV340 M6

    40  Pages

  25. MPO347 M6

    40  Pages

  26. MPP323 M6

    42  Pages

  27. MPPV010 P6

    40  Pages

  28. MP45 P6

    18  Pages

  29. MPM P6

    34  Pages

  30. MP30 P2

    15  Pages

  31. MP20 M1

    35  Pages

  32. MPNC030

    12  Pages

  33. TPLC005

    28  Pages

  34. MPNC010

    25  Pages

  35. TP1070

    15  Pages

  36. TP1057

    15  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.