Overview
The BMI-CAP | C Mk II is a device designed for monitoring and troubleshooting MS/TP bus communications. It acts as a passive listener, recording log files without affecting the bus, which can be analyzed using software like Wireshark. The device is available as a tabletop unit or for a control cabinet.

Specifications
- Power Supply: +12 to +24V DC or 12 to 24V AC
- Power Consumption: 1.7 watts
- Dimensions: 100 mm (height) x 30 mm (width) x 70 mm (depth)
- Weight: 250 grams
- Operating Temperature: 0 to 45°C (23 to 113°F)
- Humidity: 20 to 80% relative humidity, non-condensing
- Assembly: DIN top-hat rail TS35

Features
- ARM9 processor with 200MB storage
- Integrated web server for configuration and analysis
- No moving parts, enhancing durability
- Automatic restart after power failure
- Supports international language packages
- Integrated and switchable network and bias resistors
- BACnet routing options including BACnet/IP, BACnet/Ethernet, and BACnet/MS/TP

Connectivity
- LAN: RJ45 with 10/100 Mbit Ethernet
- MS/TP (RS485) connections with bias and termination options

Additional Information
- CE certified
- Specifications are subject to change
- For assistance, contact MBS GmbH at +49 21 51 72 94-0 or [email protected]

Conclusion
The BMI-CAP | C Mk II offers a robust solution for monitoring MS/TP networks, providing essential features for effective communication analysis and troubleshooting.
See more

Catalog excerpts

BMI-CAP | C Mk II - Special router for the control cabinet-1

BMI-CAP I C Mk II Recording logging information and finding errors If problems are suspected on an MS/TP bus, the BMI-CAP can be used to virtually listen in on the communication between the field devices. The interface does not register as a master or slave on the fieldbus, but merely forms a branch that has no effect on the MS/TP bus. Inserted into the fieldbus communication, the BMI-CAP records log files that are stored on a Windows computer via the IP interface. These can be opened and viewed using analysis software such as Wireshark. In this way, decentralised MS/TP networks can also be conveniently monitored. In addition, troubleshooting is considerably accelerated. The BMI-CAP is available in two versions: as a tabletop unit or for a control cabinet. For more information: www.mbs-solutions.de

 Open the catalog to page 1
BMI-CAP | C Mk II - Special router for the control cabinet-2

OEM Based on our modularity, we develop and manufacture cost-effective and time-efficient solutions for you which are highly innovative and guarantee a secure investment. Take advantage of the expertise we have accumulated over more than 30 years and our experience of customer projects in various industries. TECHNICAL DATA SHEET BMI-CAP | C Mk II LAN RJ45: 10/100 MBit Ethernet Link: indicates a LAN connection 10/100: Indicates the connection speed Features Slave-Proxy Mode Auto-Slave-Detection ARM9 processor 200MB integrated Web server for configuration and analysis No Moving parts such as fans...

 Open the catalog to page 2

All MBS GmbH catalogs and technical brochures

  1. maxi | Mk II

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.