  • Electrical: Operates at 240 Volts AC, 50/60Hz. Test currents include Full Trip settings of 6mA to 500mA and Half Trip settings of 3mA to 250mA. Fast Trip setting is 150mA for specific Full Trip settings. Accuracy is ±3% at 240V AC, increasing linearly to ±9% at ±6% of 240V. Timing range is 0 to 1999 mSec with accuracy of ±2% of reading ±1 digit. Test current duration varies by setting.
  • Mechanical: Dimensions are 54mm height, 190mm length, and 90mm width. Made of ABS and polycarbonate materials. Weighs 0.35 Kg without carry case. Features a liquid crystal display and CEE 22 (IEC 320) sockets.
  • Environmental: Operates between 0°C to +40°C with 95% RH at 40°C. Storage temperature ranges from –20°C to +70°C.
Procedures and Features
  • The Digital RCD Tester is designed for testing Residual Current Protection Devices in compliance with the 16th Edition of the IEE Wiring Regulations.
  • It tests common RCDs using a selector switch for Fast, I, and ½ Trip current settings. The Fast setting is for RCDs not exceeding 30mA, the I setting provides full rated trip current, and the ½ setting provides half the rated trip current.
  • Includes a polarity switch with 0° and 180° settings for testing with positive or negative waveforms. Neon lamps and voltage monitoring ensure correct system wiring.
See more

Catalog excerpts

Martindale RC2000-1

RC2000 RCD Testers SPECIFICATIONS ELECTRICAL Supply Voltage: 240 Volts AC, 50/60Hz Test Currents I, Full Trip Settings: I/2, Half Trip Settings: FAST Trip Setting: 150mA (Applicable to Full Trip Settings of 6, 10 and 30mA only) Accuracy: ± 3% at 240V AC Supply Voltage Rising Linearly To ±9% at ± 6% of 240V Supply Voltage the16th Edition of the IEE Wiring Regulations. Timing Range: 0 to 1999 mSec in steps of 1mSec Timing Accuracy: ±2% of reading ± 1 digit Test Current Duration: ½ 2 seconds I 0.5 or 2 seconds selectable FAST 0.05 seconds Fuse: 1amp, HBC, ceramic, 5 x 20mm Transient Protection: VDR at input Safety: EMC: Meets BS EN 50081-1, BS EN 50082-1 LVD: Meets BS EN 61010-1 The tester is designed to test the most common RCDs in use,with a selector switch providing Fast, I and ½ Trip current Height: 54mm (Excluding knob) Length: 190mm Width: 90mm Case Material: Top – ABS Base – ABS Window – Polycarbonate Weight (less carry case): 0.35 Kg Display: Liquid Crystal Sockets: CEE 22 (IEC 320) Mains Lead: 1.5 metres long The Digital RCD Tester is ideally suited for the testing of Residual Current Protection Devices, in compliance with settings. The Fast setting provides 150mA trip current for RCDs not exceeding 30mA. The I setting provides full rated trip current, which should cause the RCD under test to trip.The ½ setting provides half the rated trip current whereby the RCD should not trip. This tester has a 6mA setting, widening the range of RCDs it can test. Other features include a polarity switch with 0° and 180°settings which permits a test cycle to commence with a positive or negative going wave form from the zero crossover point. The facility to establish whether the system under test is correctly wired is provided by means of neon lamps Operating Temperature Range: 0°C to +40°C Humidity: 95°RH at 40°C Storage Temperature Range: –20°C to +70°C and monitoring of the voltage present on the earth terminal. Due to policy of continuous development, Martindale Electric reserves the right to alter equipment specification and description outlined in this document without prior notice. No part of this document shall be deemed to be part of any contract for the equipment unless specifically referred to as an inclusion within such contract. © Martindale Electric Co. Ltd. 2005 Martindale Electric Company Ltd. Metrohm House, Penfiold Trading Estate, Imperial Way, Watford, WD24 4YY. Tel: 01923 441717 Fax: 01923 446900 E-mail: [email protected] Web site: http://www.martindale-electric.co.uk

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.