Power generation Selection guide - Low voltage

Product catalog summary
Generator Applications
This section provides guidance on selecting low voltage generators, focusing on types such as ODP, TEAAC, and TEWAC. It covers applications for both 50 Hz and 60 Hz with various winding configurations and voltage ratings.

Rating Definition
Generators are rated for prime and stand-by power. Prime rating supports variable load operation for unlimited hours with temperature rise classes B, F, and H. Stand-by rating is for emergency power during outages with specific temperature rise ratings.

Operating Conditions
Includes altitude and ambient temperature adjustments, with derating factors for installations above 1,000 meters and temperatures deviating from 40°C. The nominal power factor is 0.8 lagging.

Connections
Details various connection configurations such as star, delta, and zig-zag, with derating factors. Guidance on single-phase operation and air filter impact is provided.

Overloads
Generators can handle 10% overload for one hour every six hours during continuous duty. Stand-by duty does not permit overloads.

Technical Specifications
Includes tables of specifications for continuous and stand-by duty ratings, efficiency, moment of inertia, and weight for various models.

Specifications
Details specifications for TEWAC Generators MJR - LV 6 poles, including power ratings, efficiency, and temperature rise classes for models like MJR 400 LA6, MJR 450 MB6, and MJR 500 MB6 at 60 Hz and 480 V.

AVR Selection Table
Includes an AVR selection table listing types like MARK VX, MARK V, MGC I, MGC II, MEC-20, and MEC-100, their compatibility with generator frame sizes, supply options, and voltage sensing configurations.

Functional Features
Outlines features such as parallel operation capabilities, standard protections, limiters for under-frequency, auxiliary inputs, PC interface, and soft start functions.

Contact Information
Provides contact details for Marelli Motori's offices worldwide, including addresses, phone, fax, and email contacts for locations in Italy, Asia Pacific, UK, South Africa, Central Europe, USA, Middle East, China, Vietnam, and Spain.
See more

Catalog excerpts

Power generation Selection guide - Low voltage-1

Selection guide - Low Voltage

 Open the catalog to page 1
Power generation Selection guide - Low voltage-2

Content Generator applications Rating definition Operating conditions Connections ODP generators: MXB - MJB | 50 Hz 2. Standard winding 6 poles (rating: 380 - 400 - 415 V) 3. Standard winding 8 poles (rating: 380 - 400 - 415 V) 4. Single phase - parallel star - std. winding 4 poles (rating: 190 - 200 - 208 V) 5. Single phase - zig-zag - std. winding 4 poles (rating: 220 -230 V) TEAAC generators: MJV | 50 Hz TEWAC generators: MJR | 50 Hz 1. 4 poles (rating: 380 - 400 - 415 - 440 V) ODP generators: MXB - MJB | 60 Hz 1. Standard winding 4 poles (rating: 380 - 416 - 440 - 460 - 480 V) 2. Standard...

 Open the catalog to page 2
Power generation Selection guide - Low voltage-3

Key TEWAC Totally Enclosed Water to Air Cooled ODP Open Drip Proof TEAAC Totally Enclosed Air to Air Cooled

 Open the catalog to page 3
Power generation Selection guide - Low voltage-4

Operating conditions Rating definition Prime rating Prime rating is the maximum power available at a variable load for an unlimited number of hours. Marelli Motori low voltage generators are class H insulated as a standard feature. Under these conditions three different classes of temperature rise are allowed and are here below represented as over-temperature above the reference ambient temperature (ref. amb. Temp. is 40°C as defined in IEC 60034): Class B temperature rise: generator can reach a temperature rise of 80° above 40° ambient temperature. Class F temperature rise: generator can reach...

 Open the catalog to page 4
Power generation Selection guide - Low voltage-5

Overloads The nominal power factor is 0,8 lagging. For different power factor values the following derating factors must be applied. This overloads must be occasional and followed by one hour of running at normal load or less. Stand-by ratings are based on conti-nuos supply of loads for any utility power failure. No overloads are allowed in stand-by duty. 10% for 1 hour Overload during S1 15% for 10 minutes continuous duty 30% for 4 minutes Single phase operation MXB The rated outputs of MXB three-phase (12-wire) wound generators, when reconnected for single phase operation, can be obtained by...

 Open the catalog to page 5
Power generation Selection guide - Low voltage-6

12 Leads / Winding code M0 Voltages L-L Voltages Frequency Series Delta (High Delta) Voltages Frequency Series Star (High Wye) Key * Voltage not available on MJB 400 frame - neutral not available

 Open the catalog to page 6
Power generation Selection guide - Low voltage-7

Key * voltage not available on MJB355MB4, MJB400MB4 - neutral not available (l) Voltage not availabe on MXB generators

 Open the catalog to page 7
Power generation Selection guide - Low voltage-8

6 Leads / Winding code 17 - 80 Voltages

 Open the catalog to page 8
Power generation Selection guide - Low voltage-10

ODP Generators MXB - MJB - Standard winding 4 poles (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 10
Power generation Selection guide - Low voltage-11

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 11
Power generation Selection guide - Low voltage-12

ODP Generators MXB - MJB - Standard winding 4 poles (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 12
Power generation Selection guide - Low voltage-13

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 13
Power generation Selection guide - Low voltage-14

ODP Generators MXB - MJB - Standard winding 6 poles

 Open the catalog to page 14
Power generation Selection guide - Low voltage-16

ODP Generators MXB - MJB - 4 poles - Single phase - parallel star - std. winding (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 16
Power generation Selection guide - Low voltage-17

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 17
Power generation Selection guide - Low voltage-18

ODP Generators MXB - MJB - 4 poles - Single phase - parallel star - std. winding (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 18
Power generation Selection guide - Low voltage-19

(1' Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 19
Power generation Selection guide - Low voltage-20

ODP Generators MXB - MJB - 4 poles - Single phase - zig-zag - std. winding MXB - MJB - 4 POLES - single phase 50 Hz (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 20
Power generation Selection guide - Low voltage-22

TEAAC Generators MJV - LV 4 poles

 Open the catalog to page 22
Power generation Selection guide - Low voltage-24

TEAAC Generators MJV - LV 6 poles

 Open the catalog to page 24
Power generation Selection guide - Low voltage-25

Continuous duty rating kVA @ Temp. rise over 40 °C ambient temp. 125 AT 105 AT

 Open the catalog to page 25
Power generation Selection guide - Low voltage-26

TEWAC Generators MJR - LV 4 poles Continuous duty rating kVA @ Temp. rise over 40 °C ambient temp. 125 AT 105 AT

 Open the catalog to page 26
Power generation Selection guide - Low voltage-27

Continuous duty rating kVA @ Temp. rise over 40 °C ambient temp. 105 AT Cl. F

 Open the catalog to page 27
Power generation Selection guide - Low voltage-28

TEWAC Generators MJR - LV 6 poles

 Open the catalog to page 28
Power generation Selection guide - Low voltage-30

ODP Generators MXB - MJB - Standard winding 4 poles standard winding Moment of Inertia Weight Continuous duty rating Efficiency (1) Stand-by duty rating kVA @ Temp. rise over 40 °C ambient temp. 125 AT 105 AT 80 AT (1' Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 30
Power generation Selection guide - Low voltage-31

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 31
Power generation Selection guide - Low voltage-32

ODP Generators MXB - MJB - Standard winding 4 poles (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 32
Power generation Selection guide - Low voltage-33

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 33
Power generation Selection guide - Low voltage-34

ODP Generators MXB - MJB - Standard winding 4 poles (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 34
Power generation Selection guide - Low voltage-36

ODP Generators MJB - Standard winding 6 poles MJB - 6 POLES 460 V standard winding Continuous duty rating kVA @ Temp. rise over 40 °C ambient temp. Stand-by duty rating Moment of Inertia Weight J

 Open the catalog to page 36
Power generation Selection guide - Low voltage-38

ODP Generators MJB - Standard winding 8 poles

 Open the catalog to page 38
Power generation Selection guide - Low voltage-39

MJB - 4 POLES380 V dedicated winding R3 Leads Continuous duty rating kVA @ Temp. rise over 40 °C ambient temp.

 Open the catalog to page 39
Power generation Selection guide - Low voltage-40

ODP Generators MXB - MJB - 60 Hz dedicated winding

 Open the catalog to page 40
Power generation Selection guide - Low voltage-42

ODP Generators MXB - MJB - 4 poles - Single phase - parallel star - std. winding (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 42
Power generation Selection guide - Low voltage-43

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 43
Power generation Selection guide - Low voltage-44

ODP Generators MXB - MJB - 4 poles - Single phase - parallel star - std. winding (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 44
Power generation Selection guide - Low voltage-45

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 45
Power generation Selection guide - Low voltage-46

ODP Generators MXB - MJB - 4 poles - Single phase - parallel star - dedicated winding

 Open the catalog to page 46
Power generation Selection guide - Low voltage-47

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 47
Power generation Selection guide - Low voltage-48

ODP Generators MXB - MJB - 4 poles - Single phase - zig-zag - std. winding (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 48
Power generation Selection guide - Low voltage-49

(1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 49
Power generation Selection guide - Low voltage-50

ODP Generators MXB - MJB - 4 poles - Single phase - zig-zag - std. winding (1) Value referred to continuous duty rating / 125 AT / Temperature rise class H

 Open the catalog to page 50
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.