SCT-0950-200 UL-Listed Current Transformer - 1

UL-Listed Split-Core CT SCT-0950-200 0.95 inch Opening with Rating of 200 Amps Magnelab's new UL-Listed SCT-0950-200 split-core sensor measures AC current up to 200 Amps. The SCT-0950-200 meets IEC 61869-2 Class 0.5 and is UL-Listed according to UL 2808. The SCT-0950-200 is compact, performs well and is easy to install around existing conductors. Rated Primary Current 200A APPLICATIONS Rated Output 333mV Phase Displacement < 0.5°at full-scale Temperature Rating Operating: -40 to 185°F (-40° to 85°C) Energy and sub-metering Electrical load monitoring Network equipment Instruments and sensors Control systems Solar and renewable energy Leads 8 ft. 18 AWG black/white cable Rating: 600V (UL 2808) Insulation Voltage 3510 VAC Insulation Test (1 min) PRODUCT DIMENSIONS Rated Frequency 50 - 400 Hz Pollution Degree Degree 2, up to 2000 meters UL-LISTED SCT SERIES PRODUCT # WINDOW SIZE INPUT RATING C€ v&HSz 150*001 Magnelab reserves the right to implement modifications without prior notice