SCT-0750 Energy Management
1Pages

{{requestButtons}}

Catalog excerpts

SCT-0750 Energy Management - 1

Split-Core AC Current Sensor SCT-0750 0.75" Opening With Ratings Up To 200 Amps Description: Magnelab's SCT-0750 Series split-core current sensors "sense" AC current up to 200 Amps passing through the center conductor. Split-core transformers are ideal for installation on existing electrical wiring by snapping around the conductor. The SCT series have a self-locking mechanism. Custom outputs and other parameters are available at customer request. Features: • Inputs: Rated up to 200 Amp • Outputs: 0.333 Volt at rated current • Linearity accuracy ± 1% • Accuracy at 10% to 130% of rated current • Phase angle < 2 degrees (valid for 70A or higher) Operates from 30 Hz to 1,000 Hz 8 ft. twisted-pair lead, 22 AWG Maximum Voltage: 600 V (on bare conductor) UL Standard 61010-1, EN 60044-1 Operating temperature: -20°C to +110°C PART NUMBER AND RATING Magnelab reserves the right to modify products to make improvements without advance notice.