1. Catalogs
  2. MAGNELAB
  3. RMS-333 AC to DC Voltage Transducer

RMS-333 AC to DC Voltage Transducer

RMS-333 AC to DC Voltage Transducer

Product catalog summary
Description:
The MAG-RMS-333 series is an AC to DC transducer designed to convert 0.333 Vac to Vdc. It is compatible with standard current transformers, potential transformers, sensors, and various panel meters. The module is compact, requires ultra-low power, and supports a wide range of voltage inputs, making it versatile for different project designs. It is preprogrammed to output values of 0.5, 1, 2, 3, or 5 Vdc.
Features:
  • Input: 0.333 or 1 Volt RMS
  • Output: 0.2, 0.5, 1, 2, 3, or 5 Vdc
  • Linearity Accuracy: 0.5% full scale (40 to 400 Hz)
  • Response Time: 1 second
  • Compatible with standard 333 mV Current Transformers
  • Low Ripple Output: 0.01%
  • Wide Power Input Voltage Range: 3.1 - 35 Vdc
  • Ultra Low Operating Power: 1.35 mW
  • Operating Conditions: -20°C to +70°C
  • Other Outputs Available
Part Numbers and Ratings:
  • MAG-RMS-333-DC02: 0.333Vac In, 0.2Vdc Out
  • MAG-RMS-333-DC05: 0.333Vac In, 0.5Vdc Out
  • MAG-RMS-333-DC10: 0.333Vac In, 1.0Vdc Out
  • MAG-RMS-333-DC20: 0.333Vac In, 2.0Vdc Out
  • MAG-RMS-333-DC30: 0.333Vac In, 3.0Vdc Out
  • MAG-RMS-333-DC50: 0.333Vac In, 5.0Vdc Out
  • MAG-RMS-1000-DC10: 1.0Vac In, 1.0Vdc Out
  • MAG-RMS-1000-DC20: 1.0Vac In, 2.0Vdc Out
  • MAG-RMS-1000-DC30: 1.0Vac In, 3.0Vdc Out
  • MAG-RMS-1000-DC50: 1.0Vac In, 5.0Vdc Out
Certifications:
RoHS2, ISO 9001:2008
See more

Catalog excerpts

RMS-333 AC to DC Voltage Transducer-1

MAG-RMS-333 AC to DC Transducer Converts 0.333 Vac to Vdc Description: The MAG-RMS-333 series is an AC to DC transducer. The module is designed to work with standard 0-333mVrms current transformers, potential transformers, sensors and several types of panel meters. With its compact size, ultra low power requirements, and wide range of voltage inputs, it can be configured into many project designs with ease. The module comes preprogrammed for output values of 0.5, 1,2, 3, or 5 Vdc • Input 0.333 or 1 Volt RMS • Output 0.2, 0.5, 1,2, 3 or 5 Vdc • Linearity Accuracy 0.5% full scale (40 to 400 Hz) • Response time 1 sec • Works with standard 333 mV Current Transformers Low Ripple output 0.01% Wide Power Input Voltage Range 3.1 - 35 Vdc Ultra Low Operating Power 1.35 mW Operating condition -20°C, to +70°C Other Outputs available PART NUMBER AND RATING Magnelab Transducer Wiring Diagram