1. Catalogs
  2. MAGNELAB
  3. RCS-5A Series Three Phase Rogowski Coil Set

RCS-5A Series Three Phase Rogowski Coil Set

RCS-5A Series Three Phase Rogowski Coil Set

Product catalog summary
Overview: The document describes the Magnelab RCS-5A Series, a three-phase RopeCT integrator that converts input voltage to a 5 A AC RMS output. It is designed for use with power meters or equipment with a 5 A current transformer input and includes three RopeCTs and a 24 V DC power supply.
Applications: The integrator is suitable for submetering, smart home energy management, power generation monitoring, industrial pump monitoring, solar consumption monitoring, EV charging stations, and lifecycle management of equipment.
Specifications:
  • Output Load: 50 mΩ Maximum (or 1.8 VA max.)
  • Inputs: Selectable up to 5,000 A with RopeCT
  • Outputs: 5 A @ 50 mΩ (6A max.)
  • Accuracy: ±1.0% Full Scale Error
  • Phase Displacement: Less than 0.5°
  • Temperature Range: -20% to 55°C
  • Leads: 8ft, 600 V insulated leads; suggest 18 AWG wire or larger for connecting 5 A AC output
  • Power Supply: 24 V DC 40 Watt Din Rail, 0.9 A DC min.
  • UL Max Voltage: 600 V on bare conductor
  • RMS Voltage: 10,000 V withstand
  • Rated Frequency: 50 to 60 Hz
  • Certifications: UL Listed, conforms to IEC 61010-1, RopeCT meets IEEE C57.13, IEC 60044-1
  • Weight: 3.57 lb (1.62 kg) in RCT-1800 Configuration
  • Mounting: DIN TS-35/7.5 or 15 (integrator + power supply), 12” DIN Rail + two stops provided
Model Variants: The document lists several model numbers (RCS-1205-VAR, RCS-1805-VAR, RCS-2405-VAR, RCS-3605-VAR) with selectable input ranges of 500, 1000, 2500, 5000 Amp and coil lengths of 12”, 18”, 24”, and 36”.
Important Note: The integrator should be installed as close to the meter as possible to maintain load impedance under 50 mΩ due to increased impedance from lead resistance. Output leads are not supplied.
See more

Catalog excerpts

RCS-5A Series Three Phase Rogowski Coil Set-1

5 A Output Three-Phase RopeCT RCS-5A Series Rogowski Coils with 5 A RMS Current Output Integrator The RCS-5A Series integrator converts Magnelab RopeCT input voltage to 5 A AC RMS output. It was designed for use with any power meter or equipment with a 5 A current transformer input. The integrator ships with three RopeCTs and a 24 V DC power supply. An ideal replacement for bulky 5 A current transformers. SPECIFICATIONS Output Load 50 mQ Maximum (or 1.8 VA max.)* Inputs Selectable to 5,000 A with RopeCT Accuracy ±1.0% Full Scale Error Temperatures UL Rated Ambient: -20% to 55°C Leads 8ft, 600 V insulated leads (RopeCT to integrator). Suggest 18 AWG wire or larger (not included) for connecting 5 A AC output. Power Supply 24 V DC 40 Watt Din Rail , 0.9 A DC min. Lead wire included UL Max Voltage 600 V on bare conductor (RopeCT rating) RMS Voltage 10,000 V withstand (RopeCT rating) Certifications UL Listed, coforms to IEC 61010-1, (RopeCT meets IEEE C57.13, IEC 60044-1) Weight 3.57 lb (1.62 kg) in RCT-1800 Configuration Mounting DIN TS-35/7.5 or 15 (integrator + power supply) 12” DIN Rail + two stops provided * Important Note: RCS-5A Series integrator should be installed as close to the meter as possible to keep the load impedance under 50 mQ, because the lead resistance increases the impedance. APPLICATIONS • Submetering • Smart Home Energy Management System • Power Generation Monitoring • Industrial Pump Monitoring • Solar Consumption Monitoring • EV Charging Stations • Lifecycle Management of Equipment MODEL NUMBER cTOus C€ v6>HS2 IS09001 **Magnelab reserves the right to implement modifications without prior notice

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.