1. Catalogs
  2. MAGNELAB
  3. HT300M Series

HT300M Series

HT300M Series

Product catalog summary
Description: The HT300M is a closed loop Hall Effect Current Transformer by Magnelab, designed for measuring currents up to 300 Amps. It provides an output current of 120 mA, isolated from the primary conductor.
Features: The transformer boasts high accuracy, a 7 kV proof stress, and fast response times.
Technical Specifications:
  • Nominal primary current: 300 Amp
  • Turns ratio: 2500:1
  • Power supply: ±12 V to ±15 V
  • Power supply current: 25 mA per rail + output current
  • Minimum burden resistance: 11 OHMs
  • Operating temperature: -10 to +85°C
  • Linearity: 0.1% of nominal primary current
  • Limit of linearity: ±800 Amp peak
  • Overall accuracy: 0.65% of nominal primary current
  • Output offset current: < ±150 uA at 0A primary current
  • Zero offset/Temperature: < 2 uA/°C
  • Zero offset/supply variation: < 5 uA/V
  • Coil resistance: 30 OHMs
  • Bandwidth: DC to 70 KHz at -1 dB, DC to 115 KHz at -3 dB
  • di/dt following: < 100 A/uS
  • Delay time: < 0.5 uS
  • Proof stress voltage: 7 KVac, rms, 50 Hz for 1 minute
General Data:
  • Weight: 110 grams nominal
  • Housing: Modified Polyphenylene Oxide UL94 V0
  • Terminations: Molex 5046-04/AG
  • Conductor temperature: Should not exceed 100°C
Notes: Overload currents should not exceed 2 minutes in any 15-minute period at maximum ambient temperature and supply voltage.
Dimensions: Provided in both inches and millimeters for various parts of the transformer.
Certifications: RoHS2 and ISO 9001:2008 compliant.
See more

Catalog excerpts

HT300M Series-1

Hall Effect Current Transformer HT300M Panel Mouting Description: Magnelab's HT300 is a closed loop Hall Effect Current Transformer suitable for measuring current up to 300 Amp. The product provides an output current of 120 mA at rated primary current, galvanically isolated from the primary conductor into an external load resistance. Features: • High accuracy • 7 kV proof stress • Fast response Technical and Specification: • Nominal primary current • Turns ratio • Nominal power supply • Power supply current • Min. burden resistance • Operating temperature • Linearity • Limit of linearity • Overall accuracy • Output offset current • Zero offset / Temperature • Zero offset /supply variation 300 Amp 2500:1 ± 12 V -5% to ±15 V +5% 25 mA per rail + output current 11 OHMs -10 to +85°C 0.1% of nominal primary current ± 800 Amp peak value (See Note 1) 0.65% of nominal primary current < ± 150 uA at primary current = 0A < 2 uA / °C <5uA/V • Coil resistance • Bandwidth • di/dt following • Delay time 30 OHMs DC to 70 KHz at -1 dB, DC to 115 KHz at -3 dB <100 A/uS < 0.5 uS • Proof stress voltage 7 KVac, rms, 50 Hz for 1 minute, bore to output terminals • Weight 110 grams nominal • Housing Modified Polyphenylene Oxide UL94 V0 • Conductor temperature The temperature or the primary conductor should not exceed 100°C Note 1: At maximum ambient temperature and supply voltage, the duaration of over load currents should not exceed 2 minutes in any 15 minute period.

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.