ND45-1

• Measurement and recording of over 500 electric energy quality parameters acc. to en 50160, en 61000-4-30, en 61000-4-7 standards. • Measuring class a - for 3 second aggregation. 10 minute and 2 hour aggregation - class S. • operation in 3 or 4-wire, 3-phase, balanced or unbalanced power networks. • analysis of current and voltage harmonics and interharmonics up to the 51 st for class i (acc. to en 61000-4-7). • Flicker. • 4-quadrant energy measurement in 4 tariffs. • Monitoring up to 6 additional energy meters with pulse output. • recording of measurements before and after events (dips & swells). • configurable archives of actual values and events recording. • data archiving on an Sd card - memory up to 32 GB. • e-mail messages in case of alarm occurs, • web server (http protocol), Ftp server, dhcp client. • interfaces: rs-485 Modbus slave, ethernet 100 Base-t (Modbus tcp/ip), USB device & host. • colour touch screen: lcd tFt 5.6”, 640 x 480 pixels. • ip65 protection grade from the frontal side. • Synchronization of rtc clock with the ntp time server. - power network analyzer / recorder * for selected parameters details in the technical data Ethernet www/ ftp / smtp Ethernet TCP IP energy counter

 Open the catalog to page 1
ND45-2

ND45 - power network analyzer / recorder Measurement and visualization of power network parameters Aggregated values for 3 seconds, 10 minutes and two hours: • phase voltages U1, U2, U3, U123avg • phase current I1, I2, I3, I123avg • active phase powers P1, P2, P3, ΣP123, P123avg • reactive phase powers Q1, Q2, Q3, ΣQ123, Q123avg • apparent phase powers S1, S2, S3, ΣS123, S123avg • active power factors PF1, PF2, PF3, PF123avg • power factor distortion dPF1, dPF2, dPF3, dPF123avg • reactive/active power factors tgj1, tgj2, tgj3, tgj123avg • phase-to-phase voltages U12, U31, U23, U123avg • current...

 Open the catalog to page 2
ND45-3

LUMEL EVERYTHING COUNTS ND45 - POWER NETWORK ANALYZER / RECORDER RATED OPERATING CONDITIONS where: Ku - voltage transformer ratio Ur% lrd9 - measurement values Ki - current transformer ratio Ul1, ln, Pn, Qn - nominal values Udin - declared input voltage

 Open the catalog to page 3
ND45-4

ND45 - POWER NETWORK ANALYZER / RECORDER LUMEL EVERYTHING COUNTS EXAMPLES OF MEASURING DATA PRESENTATION • digital display • analog view, • bargraphs, • vector diagrams • trends • energy meter • harmonics analysis • energy meter. Screen system log files. control panel.

 Open the catalog to page 4
ND45-5

ND45 - POWER NETWORK ANALYZER / RECORDER LUMEL EVERYTHING COUNTS EXAMPLES OF MEASURING DATA PRESENTATION ETHERNET: WWW SERVER, FTP www.lumel.com.pl

 Open the catalog to page 5
ND45-6

nD45 - power network analyzer / recorder diMenSionS and aSSeMBly in stanDarD: • two temperature inputs pt100 or pt1000, • rS-485 Modbus Slave, • ethernet. 1 orDer eXaMple: the code: nD45 1 2 1 0 e 00 1 means: nD45 - power network analyzer nd45 type 1 - input votlage 3 x 57,7/ 100 V 2 - 6 logic inputs, 4 relay outputs 1 - supply 85…253 V a.c., 90…300 V d.c. 0 - S mearusing class E - english version 00 - standard version 1 -with an extra quality inspection certificate. * only after agreeing with the manufacturer For more information about lumel products please visit our website: www.lumel.com.pl...

 Open the catalog to page 6

All LUMEL catalogs and technical brochures

  1. NR30IoT

    6  Pages

  2. ND30IoT

    8  Pages

  3. n20plus

    3  Pages

  4. n20Hplus

    2  Pages

  5. RE22

    2  Pages

  6. SR11

    4  Pages

  7. N27D

    2  Pages

  8. N30O

    2  Pages

  9. N30U

    2  Pages

  10. N30H

    2  Pages

  11. Catalog

    88  Pages

  12. catalogue Lumel

    84  Pages

  13. product guide

    12  Pages

Archived catalogs

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.