BC9 Series
1 /3Pages

BC9 Series

BC9 Series
1 /3Pages

Catalog excerpts

BC9 Series-1

BC9 SeriesElectrodeless Conductivity Controllers Features • IP66 surface mounting enclosure • Low cost maintenance free system • Cooling tower bleed and proportional feed • Solution concentration with optional 0-5% NaOH range • Rinse water control The BC9 series of electrodeless conductivity controllers are designed for use in applications where sensor fouling occurs. The electrodeless or inductive method of measuring conductivity provides a maintenance free measurement system at a competitive price when using the BC9 series controllers with the LTH Electronics ECS/20 series of electrodeless conductivity sensors. The controllers are housed in an IP66 surface mounting enclosure with a 3.5 digit LCD display. Four measurement ranges can be selected: - 1.999 mS/cm, 19.99 mS/cm, 199.9 mS/cm & 1999 mS/cm. Note that 1.999 mS/cm = 1999 pS/cm. An optional version is available with the output scaled 0-5% NaOH (Sodium Hydroxide). The BC9 series comprises of four models as follows: The BC9 has a single changeover relay, with a fully adjustable high or low control set point that can be used for a variety of dosing and bleeding applications. The BC92 has a second relay that gives a time proportioning output that is particularly useful for corrosion inhibitor dosing. A 10% to 100% linear proportional dose can be set using a graduated potentiometer.

 Open the catalog to page 1
BC9 Series-2

The BC93 has a second relay, with a fully adjustable high or low control set point that can be used for a variety of dosing and bleeding applications. It can also be configured as an alarm device to operate a safety valve or klaxon. The BC94 has a second relay, configured as a dose alarm device, perhaps used to operate a safety valve or klaxon. The timer can be set from 1-60 minutes. If any single dose exceeds the set time, the dose relay and LED is de-energised, the alarm relay is energised and the alarm LED flashes. A low-tank switch input can also activate the alarm condition. The BC92, BC93...

 Open the catalog to page 2
BC9 Series-3

LTH Electronics Ltd, Chaul End Lane, Luton, Bedfordshire. LU4 8EZ England Telephone: +44 (0)1582 593693 Fax: +44 (0)1582 598036 email: [email protected] web: www.lth.co.uk Electronics www.lth.co.uk Type No Part No Description BC9 1173 IP66 surface mounting electrodeless conductivity indicator/controller with single relay output. BC9 1198 IP66 surface mounting electrodeless conductivity indicator/controller, with single relay output. Scaled for 0-5% NaOH BC92 1174 IP66 surface mounting electrodeless conductivity indicator/controller...

 Open the catalog to page 3
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.