1. Catalogs
  2. LTG Aktiengesellschaft
  3. Facade fancoil unit FVM
video corpo

Facade fancoil unit FVM

Facade fancoil unit FVM
1 / 16 PagesView full catalog

Facade fancoil unit FVM

Product catalog summary
Overview: The document outlines the technical specifications and installation guidelines for the Facade Fan Coil Unit Type A/C System FVM, designed for decentralized ventilation, heating, and cooling through facade installation. It is a modular system integrating all functions into a single unit.
Specifications: The FVM system is designed for decentralized ventilation using outside air, with integrated heating and cooling capabilities. It includes components such as supply and return air fans, heat exchangers, and sound absorbers. The system supports both outside air and recirculating air modes, with heat and humidity recovery.
Functional Principle: The system draws in outside air through a facade opening, filters it, and passes it through a heat and humidity recovery unit. The air is then mixed with room air and conditioned via a heat exchanger before being distributed into the room. In case of power failure, dampers close automatically to maintain room conditions.
Installation and Integration: The unit is designed for flush installation in single-shell facades, requiring minimal space. It allows for flexible interior design as it does not require additional space for A/C components within the room. The system is preassembled and tested for easy installation.
Advantages: Key benefits include space efficiency, modular construction, high user acceptance due to individual operability, and energy efficiency. The system offers good indoor air quality and thermal comfort with low energy consumption.
Technical Specifications: Detailed performance data includes air flow rates, sound levels, cooling and heating capacities, and power consumption. Tolerances and surface finish requirements are outlined according to relevant DIN standards.
Diagrams and Examples: Diagrams illustrate the unit's integration with the facade and examples of air flow rates and cooling capacities under different conditions.
Control and Operation: The system integrates into a closed-loop control circuit, requiring modifications due to variable outside air temperatures. Room temperature control is cascade controlled, and emergency functions include automatic damper closure in case of power failure.
Wind Pressure and Air Flow Control: The unit maintains required air flow rates through an integrated controller, with three selectable flow rates. In the absence of a selected flow rate, the system shuts down the air dampers and fan.
Frost Protection: A digital anti-freeze sensor monitors air temperature to prevent heat exchanger damage, shutting off the fan if temperatures drop below 10°C.
Comfort Control Type DKR 5000: This controller offers multiple functions, including PI room temperature control, local fan speed switching, and integration with bus systems (LON/KNX). It supports five operating modes: building protection, nocturnal cooling, economy, pre-comfort, and comfort.
Sound and Energy Efficiency: The unit features low-noise centrifugal fans and energy-saving EC motors. Sound power levels vary based on operation mode, with specific dB(A) ratings provided for different air flow rates.
Filters: The system includes F7 class filters for outside air and F5 for exhaust air, designed for fine dust filtration and marked for easy maintenance.
Diffusers: The unit features an on-site front door with lateral ventilation slots for mixed displacement air flow. It complies with thermal comfort standards DIN EN ISO 7730 for classes A and B.
Dampers: Outside and exit air dampers automatically close during power failures, meeting DIN EN 1751 tightness requirements for class 3.
Control: Options include additional temperature sensors and antifreeze circuits. The unit can be equipped with a digital controller for temperature regulation and error messaging.
Sanitation: Designed to minimize condensate formation, the unit includes a condensate tray and is lined with sound-muffling materials. Components are accessible for maintenance.
Materials and Finishes: The housing is made of galvanized sheet steel with a powder-coated finish. It includes a heat exchanger with copper tubing and aluminum fins.
Installation: Suitable for plug-in installation in facades, the unit is modular and pre-wired. Dimensions are specified, and it meets legal heat insulation requirements.
Control Unit: The digital single-room controller (Type DKR 5000) offers various functions, including temperature control, fan speed regulation, and fault alarms. It supports LON bus connections for centralized control.
Accessories: Optional extras include a full-way valve with an actuator for continuous operation.
See more

Catalog excerpts

Facade fancoil unit FVM-1

Facade Fan Coil Unit Type A/C System FVM For Facade Installation LTG Aktiengesellschaft D - 70435 Stuttgart, Grenzstraße 7 +49 (0711) 82 01-0, Fax +49 (0711) 82 01-720 Internet: http://www.LTG-AG.de E-Mail: info@LTG- AG.de - LTG Incorporated 105 Corporate Drive, Suite E Spartanburg S.C., 29303 USA +1 (864) 599- 6340, Fax +1 (864) 599- 6344 Internet: http://www.LTG-INC.net E-Mail: info@LTG- INC.net -

 Open the catalog to page 1
Facade fancoil unit FVM-2

Components for Room Air Technology Germany Central Office (Frankfurt) Sales area: PLZ 54, 55, 60, 63, 64, 66-69, 97 Sontraer Str. 27 D-60386 Frankfurt am Main (069) 94 20 19-14, Fax -10 E-mail: [email protected] Central office (Herborn) Sales area: PLZ 30, 31, 34-38, 56, 57, 61, 65 Sperberweg 16 D-35745 Herborn Herr Hartmann (02772) 570-725, Fax -727 E-mail: [email protected] Eastern office (Berlin) Sales area: PLZ 10-25, 29, 39 Eisenhutweg 51a D-12487 Berlin Herr Linke (030) 63 22 87-74, Fax -75 E-mail: [email protected] Eastern office (Chemnitz) Sales area: PLZ 01-09, 98, 99 Johannes-Ebert-Straße...

 Open the catalog to page 2
Facade fancoil unit FVM-3

Facade Fan Coil Unit Type A/C System FVM for Decentralized Ventilation with Outside Air via the Facade and for Heating and Cooling Application Decentralized modular A/C system, flush mounted in a single- shell facade, for decentralized ventilation of occupied rooms via the facade using outside air, as well as for heating and cooling. All functions integrated in one ready- to- install unit. - - Functions - Ventilation (air diffusion + return) - Outside air filtering F7 - Heating and cooling in the outside air and recirculating air mode - Heat and humidity recovery WFRG (heat and humidity recuperation)...

 Open the catalog to page 3
Facade fancoil unit FVM-4

Facade Fan Coil Unit Type A/C System FVM Advantages Minimum space requirement even when installed in single- shell facades: width: 450 mm, depth: 160 mm, height: 2680 mm. Maximum space efficiency due to savings in floor height, shaft surfaces, and technician rooms. Modular construction, extendable in steps from static heating to air conditioning, therefore - no unnecessary preparation costs - easy retrofitting - unlimited tenant/user flexibility High user acceptance due to individual operability. Complete, discrete integration in the facade - due to low unit depth and with - due to flush facade...

 Open the catalog to page 4
Facade fancoil unit FVM-5

Facade Fan Coil Unit Type A/C System FVM Connection to the facade (example) High-vacuum panel (facade) Glazing (facade) Vapor barrier on site Insulation (facade) Facade air opening with protection against wind-driven rain and drainage to the outside Insulating strips, installation on site Outside air damper Exhaust air damper Cellular rubber strip (seal) EPDM seal Seal (VDI approved) on site Facade vacuum panel Internal face covering / appearance (examples) Aerodynamic slot 5 mm front panel Flush installation between posts 24 Visible slot Heat exchanger 5 mm front panel Flush installation between...

 Open the catalog to page 5
Facade fancoil unit FVM-6

Facade Fan Coil Unit Type A/C System FVM 450 +3 without screw heads Protection against accidental contact secondary air fan *Dimensions may vary depending on the project Cable feed- through - EPDM- plate - ca. 170 including measuring sensor Insulating strips towards the facade 450 +3 66 250 li 450 +3 Cellular rubber strips Insulating strips towards the facade E LTG Aktiengesellschaft ⋅ Grenzstraße 7 ⋅ D-70435 Stuttgart ⋅ +49 (0711) 8201-0 Fax -720 Internet: http://www.LTG-AG.de ⋅ E-Mail: [email protected] ⋅ Printed in Germany Former editions are invalid ⋅ Subject to technical modifications.

 Open the catalog to page 6
Facade fancoil unit FVM-7

Facade Fan Coil Unit Type A/C System FVM Technical Specifications Functions: Outside air/return air mode, Recirculating air mode, Cooling and Heating, Heat and Humidity Recovery (WFRG) Recirculating air only nA1 wok/pw [kg/h]/[kPa] = 120/10 woh/pw [kg/h]/[kPa] = 100/3 Supply voltage 230 V AC Power consumption ca. 100 VA Weight abt. 75 kg Depending on the type of unit casing the performance loss may be e.g. 10% 1 Fresh air 2 Secondary air 3 Outside air flow rate 4 Secondary air flow rate by induction + secondary air flow rate from recirculating air fan (- 10%) 5 Water supply temperature: 17 C,...

 Open the catalog to page 7
Facade fancoil unit FVM-8

Facade Fan Coil Unit Type A/C System FVM Due to the many parameters decisive for a decentralized unit’s output we will state one example only. Further dimensioning on request using a specific program. Example for: Type Outside air flow rate Room temperature Water intake temperature Nominal water volume Speed outside air and exhaust air fan Speed secondary air fan Heat and humidity recovery Overall cooling capacity with different water flow rates 550 525 Flow rate in % of the nominal flow rate Wasserseitiger Druckverlust pw [kPa] Cooling capacity Qk [W] Room-effective cooling capacity with different...

 Open the catalog to page 8
Facade fancoil unit FVM-9

Facade Fan Coil Unit Type A/C System FVM Control Frost Protection When integrating the A/C system type FVM into a closed- loop control circuit the following particuliarities will have to be considered: In the decentralized A/C system type FVM, both outside air and room air are routed through the heat exchanger. As outside air temperature variations can be significantly higher than intake temperatures in standard recirculating air units, standard fan coil unit control strategies cannot be used without making certain modifications. Since the heat exchanger in decentralized A/C units can handle...

 Open the catalog to page 9
Facade fancoil unit FVM-10

Facade Fan Coil Unit Type A/C System FVM Comfort Control Type DKR 5000 Comfort controller in connecting box for installation in window sills or false floors as stand- alone system or integrated in a bus system (LON/KNX) Type DKR 5000 in a protection class IP 45 casing to be connected to the FVM unit s cable harness, voltage supply (24 V), grounding, connection to the operating unit, connection to LON bus or to the neighboring unit in the same room. Digital controller with the following functions: - PI room temperature controller for heating/cooling with separate setting of P and I shares to activate...

 Open the catalog to page 10
Facade fancoil unit FVM-11

Facade Fan Coil Unit Type A/C System FVM Comfort Control Type DKR 5000 Technical data operating unit: Power supply Operating Unit The operating unit QAA 88.3 with LCD display is connected to the individual room controller via PPS2 interface. It offers the following functions: - Digital operating unit with temperature sensor, operating keys and display, connected to the controller via PPS2 bus (no LON/KNX) - 3K room temperature set point adjuster - Presence key to switch from pre- comfort to comfort set point Alternatively, any LON- compatible operating unit may be used. Functions and key assignments...