Overview: The document provides technical specifications and operational details for the DC Surge Protective Device (SPD) model FLP7-DCxxx/2(S), designed for use in string boxes and inverters.
Specifications:
  • Rated Operational DC Voltage: 65 V
  • Mode of Protection: IEC Electrical
  • Protective Elements: High Energy MOV
  • Housing: Pluggable Design
  • Compliance: IEC/EN 61643-41
Mechanical & Environmental:
  • Operating Temperature Range: -40 ºF to +158 ºF (-40 ºC to +70 ºC)
  • Permissible Operating Humidity: 5% to 95%
  • Terminal Screw Torque: 39.9 Ibf·in (4.5 Nm)
  • Conductor Cross Section: Max 2 AWG (Solid, Stranded) / 4 AWG (Flexible)
  • Mounting: 35 mm DIN Rail, EN 60715
  • Degree Of Protection: IP 20 (built-in)
  • Housing Material: Thermoplastic, UL 94V-0
Electrical Characteristics:
  • Surge Ratings: Iimp = 7 kA (10/350 µs), In = 30 kA (8/20 µs)
  • IEC/EN Category: Class I+II / Type 1+2
  • Nominal Discharge Current: 15 x 8/20 μs impulses
  • Maximum Discharge Current: 30 kA
  • Voltage Protection Level: 0.3 kV
  • Response Time: < 25 ns
  • Residual Current: Leakage current at Uc < 0.5 mA
Additional Features:
  • Thermal Protection: Yes
  • Operating State / Fault Indication: Green (ok) / Red (defect)
  • Remote Contacts (RC): Optional
  • RC Switching Capacity: AC: 250 V / 0.5 A; DC: 250 V / 0.1 A; 125 V / 0.2 A; 75 V / 0.5 A
Order Information:
  • Ordering Codes: FLP7-DCxxx/2, FLP7-DCxxx/2S (with remote contacts), FLP7-DCxxx/0 (spare modules)
  • Standard Order Quantity: 48 Units for FLP7-DCxxx/2(S), 120 Units for FLP7-DCxxx/0
Dimensions & Packaging:
  • DIN 43880 Dimension: 1 CTN
  • Packaging Dimensions (H x W x L): [260 × 220 × 330 mm]
See more

Catalog excerpts

FLP7-DC65/2(S)-1

Technical Data DC Surge Protective Ddevice Location of Use: Mode of Protection: Surge Ratings: IEC/EN Category: Protective Elements: String box, Inverter (DC+/-) - PE, (DC-/+) - PE Iimp= 7 kA (10/350 ps) In= 30 kA (8/20 ps) Class I+II / Type 1+2 High Energy MOV Pluggable Design IEC/EN 61643-41 Rated Operational DC Voltage Maximum Continuous Operating DC Voltage (DC+) - PE, (DC-) - PE Residual current - Leakage current at Uc Nominal Discharge Current - 15 x 8/20 ps impulses Maximum Discharge Current Max. withstand 8/20 ps Impulse Discharge Current Max. withstand 10/350 ps Total lightning current Voltage Protection Level Up Mechanical & Environmental Operating Temperature Range Ta Permissible Operating Humidity RH Atmospheric pressure and altitude Terminal Screw Torque Mmax Conductor Cross Section (max) Degree Of Protection Housing Material Thermal Protection Operating State / Fault Indication Remote Contacts (RC) RC Switching Capacity RC Conductor Cross Section (max) Order Information FLP7 -DCxxx/2S (with remote contacts) FLP7 -DCxxx/0 (spare modules) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) Thermoplastic: Extinguishing Degree UL 94V-0 Yes Green ok / Red defect Optional 81 Low Voltage Power Systems Series

 Open the catalog to page 1
FLP7-DC65/2(S)-2

Internal Configuration Legend @/PE PE/G Conductor Terminal S Signalling Contacts Optional Complete Unit Standard Order Quantity 48 Units Single Unit FLP7-DCxxx/0 DIN 43880 Dimension Packaging Dimensions (H x W x L) Standard Order Quantity Pluggable Single & Multi-pole SPDs J 82

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.