1. Catalogs
  2. LSP
  3. FLP12.5-xxx/1(S)

FLP12.5-xxx/1(S)

FLP12.5-xxx/1(S)
1 / 12 PagesView full catalog

FLP12.5-xxx/1(S)

Product catalog summary
Overview: The document details the technical specifications and features of the AC Surge Protective Device (SPD) model FLP12.5-xxx/1(S) and its variants, designed for main distribution boards compatible with TN-S, TN-C, and TT network systems.
Specifications:
  • Surge Ratings: Iimp up to 12.5 kA (10/350 µs), In up to 20 kA (8/20 µs).
  • Protective Elements: High Energy Metal Oxide Varistor (MOV).
  • Housing: Pluggable design for easy installation and maintenance.
  • Compliance: Meets IEC 61643-11:2011 and EN 61643-11:2012 standards.
Technical Data:
  • Nominal AC Voltage: 230 V / 400 V.
  • Maximum Continuous Operating Voltage (Uc): 320 V, 385 V, 440 V.
  • Nominal Discharge Current (In): 20 kA.
  • Maximum Discharge Current (Imax): 50 kA.
  • Impulse Discharge Current (Iimp): 12.5 kA.
  • Voltage Protection Level (Up): Ranges from 1000 V to 2000 V depending on the model.
  • Response Time: Less than 25 ns.
  • Short-Circuit Current Rating (ISCCR): 25 kA.
Mechanical & Environmental:
  • Operating Temperature Range: -40 ºF to +158 ºF (-40 ºC to +70 ºC).
  • Humidity: 5% to 95% RH.
  • Mounting: 35 mm DIN Rail, EN 60715.
  • Degree of Protection: IP 20 (built-in).
  • Housing Material: Thermoplastic with UL 94V-0 extinguishing degree.
Additional Features:
  • Thermal Protection: Indication of operating state (Green for OK, Red for defect).
  • Remote Contacts (RC): Optional, with specific switching capacities for AC and DC.
Order Information: The document lists various ordering codes for different models and configurations, including options with remote contacts and spare modules.
Connection and Installation: The SPD is designed for easy installation with a single port and features a terminal screw torque of 39.9 Ibf·in [4.5 Nm]. It supports conductor cross-sections up to 2 AWG for solid and stranded wires.
See more

Catalog excerpts

FLP12.5-xxx/1(S)-1

AC Surge Protective Device FLP12.5-xxx/1(S)Class I • Class II • Type 1 • Type 2 Location of Use: Network Systems: Mode of Protection: Surge Ratings: IEC/EN Category: Protective Elements: Main Distribution Boards TN-S, TN-C, TT (only L-N) L-PE, N-PE (only TN-S), L-PEN, L-N Iimp = up to 12.5 kA (10/350 ps) Class I+II / Type 1+2 High Energy MOV Pluggable Design IEC 61643-11:2011 EN 61643-11:2012 Technical Data Maximum Continuous Operating Voltage (AC) Uc 75 V 150 V 275 V 320 V 385 V 440 V Nominal Discharge Current (8/20 ps) In 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA Maximum Discharge Current (8/20 ps) Imax 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA Impulse Discharge Current (10/350 ps) Iimp 12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA 12.5 kA Voltage Protection Level Up 700 V 1000 V 1500 V 1600 V 1800 V 2000 V Short-Circuit Current Rating (AC) ISCCR 25 kA mode Withstand Safe Fail Safe Fail Safe Fail Safe Fail Safe Fail Mechanical & Environmental Operating Temperature Range Ta Permissible Operating Humidity RH Atmospheric pressure and altitude Terminal Screw Torque Mmax Conductor Cross Section (max) Degree of Protection Housing Material Thermal Protection Operating State / Fault Indication Remote Contacts (RC) RC Switching Capacity RC Conductor Cross Section (max) Order Information FLP12.5-xxx/1S (with remote contacts) FLP12.5-xxx/0 (spare modules) 2 AWG (Solid, Stranded) / 4 AWG (Flexible) Thermoplastic: Extinguishing Degree UL 94V-0 Yes Green ok / Red defect Optional 13 Low Voltage Power Systems Series

 Open the catalog to page 1
FLP12.5-xxx/1(S)-2

Internal Configuration Legend L Line Conductor Terminal N Neutral Conductor Terminal © PE/G Conductor Terminal S Signalling Contacts Optional Dimensions & Packaging Spare Plug [mm] Standard Order Quantity 64 Units Standard Order Quantity 120 Units Pluggable Single & Multi-pole SPDs J 14

 Open the catalog to page 2
FLP12.5-xxx/1(S)-3

Class I • Class II • Type 1 • Type 2 Location of Use: Network Systems: Mode of Protection: Surge Ratings: IEC/EN Category: Protective Elements: Main Distribution Boards TN-S Iimp = up to 12.5 kA (10/350 ps) In= up to 20 kA (8/20 ps) Class I+II / Type 1+2 High Energy MOV Pluggable Design IEC 61643-11:2011 EN 61643-11:2012 Technical Data Maximum Continuous Operating Voltage (AC) Uc 75 V 150 V 275 V 320 V 385 V 440 V Nominal Discharge Current (8/20 ps) In 20 kA 20 kA 20 kA 20 kA 20 kA 20 kA Maximum Discharge Current (8/20 ps) Imax 50 kA 50 kA 50 kA 50 kA 50 kA 50 kA Impulse Discharge Current (10/350...

 Open the catalog to page 3
FLP12.5-xxx/1(S)-4

L Line Conductor Terminal N Neutral Conductor Terminal © PE/G Conductor Terminal S Signalling Contacts Optional Dimensions & Packaging Spare Plug [mm] Complete Unit Standard Order Quantity 32 Units Single Unit Standard Order Quantity 120 Units Pluggable Single & Multi-pole SPDs J 16

 Open the catalog to page 4
FLP12.5-xxx/1(S)-5

AC Surge Protective Device Main Distribution Boards Iimp = up to 12.5 kA (10/350 ps) In= up to 20 kA (8/20 ps) Class I+II / Type 1+2 High Energy MOV Pluggable Design IEC 61643-11:2011 EN 61643-11:2012 Maximum Continuous Operating Voltage (AC) Uc 150 V Nominal Discharge Current (8/20 ps) In 20 kA Maximum Discharge Current (8/20 ps) Imax 50 kA Impulse Discharge Current (10/350 ps) Iimp 12.5 kA Voltage Protection Level Up 1000 V Short-Circuit Current Rating (AC) IsCCr mode Safe Fail Safe Fail Safe Fail Safe Fail Mechanical & Environmental Operating Temperature Range Ta Permissible Operating Humidity...

 Open the catalog to page 5
FLP12.5-xxx/1(S)-6

Internal Configuration Legend L Line Conductor Terminal N Neutral Conductor Terminal © PE/G Conductor Terminal S Signalling Contacts Optional Dimensions & Packaging Complete Unit Standard Order Quantity 20 Units Single Unit Standard Order Quantity 120 Units Pluggable Single & Multi-pole SPDs J 18

 Open the catalog to page 6
FLP12.5-xxx/1(S)-7

AC Surge Protective Device FLP12.5-xxx/4(S) Class I • Class II • Type 1 • Type 2 Location of Use: Network Systems: Mode of Protection: Surge Ratings: IEC/EN Category: Protective Elements: Main Distribution Boards TN-S Iimp = up to 12.5 kA (10/350 ps) In= up to 20 kA (8/20 ps) Class I+II / Type 1+2 High Energy MOV Pluggable Design IEC 61643-11:2011 EN 61643-11:2012 Technical Data Maximum Continuous Operating Voltage (AC) Uc 150 V Nominal Discharge Current (8/20 ps) In 20 kA Maximum Discharge Current (8/20 ps) Imax 50 kA Impulse Discharge Current (10/350 ps) Iimp 12.5 kA Voltage Protection Level...

 Open the catalog to page 7
FLP12.5-xxx/1(S)-8

Internal Configuration Legend L Line Conductor Terminal N Neutral Conductor Terminal © PE/G Conductor Terminal S Signalling Contacts Optional Complete Unit Standard Order Quantity 16 Units Single Unit Standard Order Quantity 120 Units Pluggable Single & Multi-pole SPDs J 20

 Open the catalog to page 8
FLP12.5-xxx/1(S)-9

AC Surge Protective Device Location of Use: Network Systems: Mode of Protection: Surge Ratings: IEC/EN Category: Protective Elements: Main Distribution Boards TT, TN-S L-N, N-PE Class I+II / Type 1+2 High Energy MOV and GDT Pluggable Design IEC 61643-11:2011 EN 61643-11:2012 Technical Data Maximum Continuous Operating Voltage Nominal Discharge Current (8/20 ps) Maximum Discharge Current (8/20 ps) Impulse Discharge Current (10/350 ps) Specific Energy Charge Voltage Protection Level Follow Current Interrupt Rating Residual Current at Uc Response Time Short-Circuit Current Rating (AC) (L - N) ISCCR...

 Open the catalog to page 9
FLP12.5-xxx/1(S)-10

Internal Configuration Legend L Line Conductor Terminal N Neutral Conductor Terminal © PE/G Conductor Terminal S Signalling Contacts Optional Complete Unit Standard Order Quantity 28 Units Single Unit Standard Order Quantity Connection Diagram TN-S, TT (Single-phase, 1+1) Pluggable Single & Multi-pole SPDs J 22

 Open the catalog to page 10
FLP12.5-xxx/1(S)-11

AC Surge Protective Device Location of Use: Network Systems: Mode of Protection: Surge Ratings: IEC/EN Category: Protective Elements: Main Distribution Boards TT, TN-S L-N, N-PE Class I+II / Type 1+2 High Energy MOV and GDT Pluggable Design IEC 61643-11:2011 EN 61643-11:2012 Technical Data Maximum Continuous Operating Voltage Nominal Discharge Current (8/20 ps) (L - N) / (N - PE) In Maximum Discharge Current (8/20 ps) (L - N) / (N - PE) Im Impulse Discharge Current (10/350 ps) (L - N) / (N - PE) Iimp 12.5 kA / 50 kA 12.5 kA / 50 kA 12.5 kA / 50 kA 12.5 kA / 50 kA 12.5 kA / 50 kA Specific Energy...

 Open the catalog to page 11
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.