DC4500

DC4500

DC4500

Product catalog summary
Overview: The Liquitron™ DC4500 Series Conductivity Controller is a microprocessor-based system designed for various water treatment applications. It offers conductivity control with a set point and relay, along with multiple timer functions for chemical addition, including dual biocides. The controller is user-friendly, requiring only three keys for programming, and features a backlit LCD display for operational status.
Key Features:
  • Control range of 0-20,000 µS with display units in µS or PPM/TDS.
  • Temperature display options in °C or °F.
  • High and low alarms with output relay.
  • Water meter totalizer in gallons.
  • Standard 4-20 mA recorder output.
  • Compatible with flow switches (N.O. or N.C.).
  • Backlit LCD alpha/numeric display.
  • Timer or conductivity-based prebleed and bleed output relay.
  • Outputs for inhibitor chemical pump and dual biocide pump (ON/OFF or external trigger).
  • UL, CUL, CE certified.
Specifications:
  • Dimensions & Enclosure: NEMA 12X type for prewired version; suitable for NEMA 4X applications with hardwiring.
  • Material: Flame retardant, molded TPE housing with a clear, lockable polycarbonate cover.
  • Environment: Operates between 32°F to 122°F (0°C to 50°C) with 0% to 95% non-condensing relative humidity.
  • Hardware: 115 VAC and 230 VAC units with power cords and output cables for pump connections.
  • Input & Output: 115 VAC or 230 VAC, 50/60 Hz input; 4-20 mA spannable output for conductivity.
  • Signal Input: Four PG-9 connectors for flow meter, flow switch, and other instrumentation; microphone jack for conductivity probe.
  • Bleed/Control Output: Four relays, 10 amps @ 115 VAC, 5A @ 230 VAC; unit fused for 10 amp total load.
  • Display & Indicators: 16-character backlit LCD with LED indicators for power, bleed, alarm, flow, feed, and timers.
  • Biocide Timers: 1-28 day cycle timers with selectable bleed set points and feed timers.
Operational Details: The controller supports various operational modes, including pulse and percentage-based feed timers, with limits on feed and bleed times.
See more

Catalog excerpts

DC4500-1

Data Sheet Liquitron™ DC4500 Series Conductivity Controller Cooling Tower Controller Bleed & Feed with Dual Biocide Additions The Liquitron DC4500 Series Conductivity Controller is a microprocessor based control system that will operate in a variety of water treatment applications. The DC4500 provides a set point and relay for conductivity control, and a variety of timer functions to control chemical addition, including dual biocides. Pumps may be controlled in either ON/OFF or External Trigger mode. Programming this controller is simple and is accomplished using only three keys. The backlit LCD display and LEDs provide a visual indication of operating conditions and equipment status. Features • • • • • • • 0-20,000 µS Control Range Display units in µS or in PPM/TDS Temperature Display in °C or °F High and Low Alarm with Output Relay Water Meter Totalizer (Gallons) 4-20 mA Recorder Output (Standard) Flow Switch Compatible (N.O. or N.C.) • Backlit LCD Alpha / Numeric Display • Timer or Conductivity Based Prebleed • Bleed Output Relay • Inhibitor Chemical Pump Output (ON / OFF or External Trigger) • Dual Biocide Pump Output (ON / OFF or External Trigger) • UL, CUL, CE - Certified 8 Post Office Square Acton, MA 01720 USA TEL: (978) 263-9800 FAX: (978) 264-9172 http://www.Imipumps.com Replaces same of Rev. E 4/98 1788. F 9/99

 Open the catalog to page 1
DC4500-2

Liquitron DC4500 Series Specifications Enclosure Electrical NEMA 12X Type (prewired version) Hardwiring makes the unit suitable for NEMA 4X applications Material Housing - Flame retardant, molded TPE Cover - Clear molded polycarbonate, lockable Environment 32° F to 122° F (0° C to 50° C) 0% to 95% (non-condensing) Relative Humidity Hardware 115 VAC ON/OFF units provided with a 6 ft (2 m) power cord and plug, plus three 1 ft (30 cm) output power cords for pumps 230 VAC ON/OFF units provided with a 6 ft (2 m) power cord and plug and throughput connectors for hardwire connections of controlled devices...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.