ESR_Fuse_Datasheet - 1

ESR Series High-Speed Square Body Battery Protection Fuses • 1500 V Dc • Class aBat • 125 A Description The Littelfuse Energy Storage Rack (ESR) series of fuses is designed specifically to protect battery racks in energy storage systems, inverters, and many other dc applications. The 1500 V dc high-speed square body fuse is extremely fast-acting to respond quickly to a range of fault currents to safeguard the battery module or other devices. This Class aBat partial range fuse has superior short circuit protection and a low minimum breaking capacity (MBC)—from 300 % or 3 times the fuse’s rated current to 175 kA (250 kA self-certified)—to cover a range of over currents that traditional high-speed partial range fuses do not protect against. The ESR fuse safely interrupts most faults in a battery storage system to avoid catastrophic failures and costly shutdowns. Features & Benefits FEATURES High dc interrupting rating Provides superior short-circuit protection and the ability to scale-up systems without the need to redesign the existing circuit protection, saving time and costs Low minimum breaking current Offers easy coordination with battery modules and reduces size and rating of dc contactors to save space and costs Extremely fast acting Delivers high-speed performance Maximizes efficiency by preventing energy loss and minimizing the wasted power of components Conforms to the IEC60269-7 battery standard Specifically design to safeguard evolving battery technologies with fuse circuit protection Saves space and offers design flexibility Battery energy storage systems (BESSs) – Battery Protection Unit (BPU) and battery racks Power conversion systems Dc common bus systems Hybrid PV-BESS inverters Littelfuse.com/ESR ©2022 Littelfuse, Inc. Specifications are subject to change without notice

Open the catalog to page 1
ESR_Fuse_Datasheet - 2

ESR Series High-Speed Square Body Specifications Voltage Rating Amperage Rating Interrupting Rating Time Constant Bolted-blade style, DIN-blade style Body: ceramic Contacts: plated copper (bladed) Applicable Standards RoHS Compliant, REACH, Halogen Free Operating Temperature Storage Temperature Up to +35 °C with relative humidity <65 % Certification & Compliance cURus cURus Recognized (File: E71611) RoHS 2 Directive 2011/65/EU Directive (EU) 2015/863 Ordering Information CATALOG NUMBER ESR1XLDB0125 ESR1XLUB0125 Electrical Specifications CASE SIZE CATALOG NUMBER TOTAL VOLTAGE CLEARING...

Open the catalog to page 2
ESR_Fuse_Datasheet - 3

ESR Series High-Speed Square Body REVISION REV DESCRIPTION REVISION 525xxxGCP - RELEASE MRY DESCRIPTION MOUNTING SPECS: MOUNTING SPECS: RECOMMENDED FASTENER: M10 OR 3/8" RECOMMENDED FASTENER: M12 OR 1/2" TIGHTENING TORQUE (REFERENCE ONLY): 26Nm TIGHTENING TORQUE (REFERENCE ONLY): 64Nm MOUNTING SPECS: RECOMMENDED FASTENER: M10 OR 3/8" TIGHTENING TORQUE (REFERENCE ONLY): 26Nm RECOMMENDED FASTENER: M10 OR 3/8" TIGHTENING TORQUE (REFERENCE ONLY): 26Nm MOUNTING SPECS: DENOTES CRITICAL CHARACTERISTICS. CRITICAL CHARACTERISTIC FOR PART SAFETY/COMPLIANCE DENOTES CPK DIMENSIONS, -MINIMUM CPK VALUE...

Open the catalog to page 3
ESR_Fuse_Datasheet - 4

ESR Series High-Speed Square Body Time Current Curve (1XL Case Size 125 A) 100000 90000 80000 70000 VIRTUAL MELTING (PRE‐ARCING) TIME IN SECONDS PROSPECTIVE R.M.S CURRENT IN AMPERE TEST VOLTAGE: TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER: TIME CURRENT CHARACTERISTIC CURVES 4 of 6 - THIS DATA IS GENERATED IN EXCEL - DRAWN BY: LLL DATE: 06/16/2022 REVISION: A DRAWING NO.: Specifications are subject to change without notice. FCC01-ESR Revi

Open the catalog to page 4
ESR_Fuse_Datasheet - 5

ESR Series High-Speed Square Body Total Clearing l2T Correction Factor Curve (1XL) 1500 TOTAL CLEARING I2t CORRECTION FACTOR OPERATING VOLTAGE IN VOLTS TEST VOLTAGE: 500V - 1500V TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER: LITTELFUSE, INC. Temperature Derating Curve CHICAGO, IL. USA DRAWN BY: LLL 03/31/2020 DATE: REVISION: A I2T VARIATION temperature of air immediately surrounding fuse FCC07-PSX Ambient temperature: CURVES DRAWING NO.: - THIS DATA IS GENERATED IN EXCEL - AMBIENT TEMPERATURE TEST VOLTAGE: TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER: TEMPERATURE RE-RATING CURVE -...

Open the catalog to page 5
ESR_Fuse_Datasheet - 6

ESR Series High-Speed Square Body Watts Loss Correction Factor Curve 100 WATTS LOSS CORRECTION FACTOR PERCENT OF RATED CURRENT(%) TEST VOLTAGE: TIME CONSTANT/POWER FACTOR: FUSE CATALOG NUMBER: DRAWN BY: LLL 03/20/2017 01/26/2015 DATE: A REVISION: DERATINGI2T CORRECTION LOSS CORRECTION CURVE - WATTS FACTOR - THIS DATA IS GENERATED IN EXCEL - Disclaimer Notice – Information furnished is believed to be accurate and reliable. However, users should independently evaluate the suitability of and test each product selected for their own applications. Littelfuse products are not designed for, and...

Open the catalog to page 6

All Littelfuse catalogs and technical brochures

  1. ECSW SERIES

    3 Pages

  2. LSR-0

    1 Pages

  3. LSRU SERIES

    2 Pages

  4. 50R-400-ALT

    1 Pages

  5. ALT SERIES

    2 Pages

  6. AK1-Y Series

    4 Pages

  7. TS Series

    11 Pages

  8. MP8000

    2 Pages

  9. 606 Series

    3 Pages

  10. ST Series

    3 Pages

  11. TPSMB Series

    6 Pages

  12. TPSMD Series

    6 Pages

  13. POLYFUSE®

    6 Pages

Archived catalogs