LT Energy

LT Energy

LT Energy

Product catalog summary
Overview
LT Energy is designed for the control and command of electrical management in railway substations. It is programmable using the IEC61131-3 Straton Workbench, which is the IDE of Copalp company. The system supports DNP3.0 slave level 2 over Ethernet and serial links, Modbus RTU & Modbus/TCP, and T5 Straton protocol for distributed applications. It features embedded personal web pages, local storage events, and redundancy between two LT Energy units.
Inputs/Outputs for Safety Applications
Redundant inputs use two acquisition channels to transmit the input state and its logical complement to the CPU. They support three input voltages: 24V, 48V, and 120V. Redundant relay outputs consist of 4 I/O groups connected to electrical devices, with three voltage power options: 24V, 48V, and 120V. Each relay is driven by two serial commands with priority at relay opening.
General Specifications
  • Mechanical: Dimensions are customizable, with fixation options including bolted on plate or grid, or on an asymmetrical DIN rack.
  • Robustness: Operating temperature ranges from -40°C to +70°C, with humidity tolerance from 5% to 95% without condensation. Protection level is IP 30, with high electromagnetic interference immunity and mechanical resistance.
  • Power Supply: Voltage ranges from 20 to 56 Vcc with 20W power, and 120V with 20W power. Input/Earth insulation is 1,500 Veff.
  • Central Unit: Features an Intel PXA 270 - 300 MHz microprocessor, 32 MB SDRAM, and 16 MB FLASH memory.
  • Communication: Includes one Ethernet channel and multiple asynchronous links, with diagnostic LEDs for monitoring.
Inputs/Outputs Specifications
  • Logic Inputs: Available in blocks of 16, 32, 48, or 64 inputs, with protection against polarity inversions.
  • Logic Outputs: Static 24 Vcc or relay 250 Vca, with protection against overloads.
  • Relay Outputs: Neutral/Working contact with modularity per block.
  • Analog Inputs/Outputs: Various ranges with specified resolution and insulation levels.
  • Redundant Relay Outputs: Configurable with tri-tension voltage options.
Additional Features
Includes thresholds for logic inputs with anti-intrusion wiring control, and redundant inputs providing status and complement to the CPU. The document notes that specifications are subject to change without notice.
See more

Catalog excerpts

LT Energy-1

LT Energy Straton Workbench Programming DNP3.0 Communication Protocol Inputs/outputs for circuit breakers management LT Energy is suitable for the control command of the electrical management in railway substations

 Open the catalog to page 1
LT Energy-2

► Straton is the IDE of the Copalp company ► DNP3.0 slave level 2 over Ethernet and serial links (Triangle MicroWorks Stack). ► Modbus RTU & Modbus/TCP : master & slave functions ► T5 Straton protocol between several LT: binding variables in order to build a distributed application ► Embedded personal Web pages ► Local storage events : SOE function block ► Complete redundancy features between 2 LT Inputs / Outputs for safety applications ■ The redundant inputs ► Two acquisition channels transmit the input state and its logical complement to the CPU ► Three input voltage : 24,48,120Vcc (choice...

 Open the catalog to page 2
LT Energy-3

General specifications MECHANICAL Overall dimensions Fixation ROBUSTNESS Operating Temperature Humidity Protection level CEM level Mechanical performance POWER SUPPLY Voltage - power Input/ Earth Insulation Alarm Output CENTRAL UNIT Microprocessor Memory Clock Operating Safety Diagnosis by leds COMMUNICATION Ethernet Asynchronous Diagnosis by leds Maintenance link Height x length = 108 x 84 mm ; Width = 25 mm x number of the modules on demand Bolted on plate or grid (embedded) or on asymmetrical DIN rack -40°C at +70°C (storage until 85°C) 5 to 95% without condensation. the LT can be tropicalized...

 Open the catalog to page 3
LT Energy-4

Diagnosis LOGIC INPUTS Type Modularity Norm Protection Display LOGIC OUTPUTS Type Nominal current Modularity per block Protection Output/earth insulation Display RELAY OUTPUTS Type Modularity per block Protection Output/earth insulation Display ANALOG INPUTS Range Resolution Number of inputs per block Maximum error at full scale Channel/earth insulation ANALOG OUTPUTS Range Resolution Maximum error at full scale Insulation between output and earth REDUNDANT RELAY OUTPUTS Configuration and modularity Voltage Digital intputs current Switching power / voltage / current LOGIC INPUTS Tested status...

 Open the catalog to page 4

Archived catalogs

  1. BRIO

    4  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.