Duct Burners (DB Series)

Duct Burners (DB Series)

Duct Burners (DB Series)

Product catalog summary
Overview: The Lanemark Midco HMA2A series air heating burners are designed for high efficiency and low emissions in air replacement or make-up air heating applications. They are suitable for various industrial uses such as paint spray booths, drying ovens, HVAC systems, and more.
Key Features:
  • High heat output per unit length.
  • Low emissions suitable for both manned and unmanned operations.
  • Wide range of acceptable process air velocities.
  • High turndown ratio of up to 30:1.
  • Short flame length and common burner head for natural gas and propane.
Specifications:
  • Maximum heat input: 220 kW per 305 mm section (750,000 Btu/h per ft).
  • Air velocity range: 7.5 – 18 m/s (1500 – 3500 ft/min).
  • Required air pressure: 0.5 – 3.0 mbar (50 – 300 Pa).
  • Efficiency: 100% (LHV) or 92% (HHV).
  • Burner head gas pressure for natural gas: 8.8 mb – 19.5 mb; for propane: 3.3 mb – 7.5 mb.
Design and Configuration: Burners can be configured in straight sections or various shapes like "H" or "I" using compact elbows and tees. Gas manifolds are available in cast iron and aluminum to reduce weight.
DB Air Heating Burner Systems: These systems comply with European Standard EN746 Part 2 and are available in packaged or semi-packaged formats. They include a modulating gas valve train and control box with standard components like a burner controller and ignition transformer.
Standard Equipment Options:
  • Fuels: Natural Gas, Propane.
  • Control Voltage: 230V, 110V.
  • Flame Sensing: UV Scanner, Flame Rod.
  • Heat Output Control: Modulating, High/low/Off.
Model Specifications: The document lists various models (DB01 to DB10) with their respective maximum heat input ranges and gas valve train connections.
See more

Catalog excerpts

Duct Burners (DB Series)-1

Lanemark Midco HMA2A series air heating burners are designed to provide a high efficiency, high turndown, low emission solution for air replacement or “make-up” air heating applications. • Paint spray booth air heating - spray and bake cycles • Paint drying and curing ovens • HVAC air replacement schemes for factories, warehouses, distribution centres... • Crop dryers • Print media dryers Lanemark Midco HMA2A series burners operate directly within the heated air flow and can be located either upstream or downstream of the main air supply fans. • High heat output per unit length • Low emissions - suitable for manned/unmanned operations • Wide acceptable process air velocity range • High turndown (up to 30:1) • Short flame length • Common burner head for natural gas and propane Lanemark’s DbCalc© software is available to determine burner ratings and to design suitable duct profile plate arrangements at firing rates of up to 220 kW per 305 mm (750,000 Btu/h per ft) burner length. Burners can be configured either as straight sections or in various “shapes” such as “H” or “I” designs by the use of compact elbows and tees, to fit within required duct dimensions. Gas manifolds are available in both cast iron and aluminium which significantly reduces the weights of larger burner assemblies.

 Open the catalog to page 1
Duct Burners (DB Series)-2

DB AIR HEATING BURNER SYSTEMS MODEL Higher heat inputs are available on request *** Gas Connection based on 146 kW per 305 mm (500,000 Btu/h per ft) burner sectbn * Heat Input Range @ 146 - 205 kW per 305 mm burner section length length @ 20 mb gas supply pressure (Please refer to Lanemark for gas valve train ** Heat Input Range @ 500,000 - 700,000 Btu/h per ft burner section length conmcrion szes for firing rates > 146 kWper 305 mm (5°°,000 Btu/h per ft) Lanemark DB Duct Burner Systems comply with the relevant sections of European Standard : EN746 Part 2 Lanemark DB Duct Burner Systems...

 Open the catalog to page 2