Pressure transmitter COMPACT ECOnomic HYDROGEN
4Pages

{{requestButtons}}

Catalog excerpts

Pressure transmitter COMPACT ECOnomic HYDROGEN - 1

MEASUREMENT TECHNOLOGY Pressure transmitter COMPACT ECOnomic HYDROGENType series CA1600 Application area ■ Chemical and petrochemical industry ■ Machinery construction ■ Automotive technology ■ Hydrogen production and storage Technical data Features ■ Digital pressure transmitter for hydrogen applications ■ Case and wetted parts of stainless steel, degree of protection IP 65 ■ Measuring ranges - 0...4 bar up to 0...700 bar - -1.3 bar up to -1.15 bar ■ Output signal 4.20 mA , in 2-wire technology ■ Accuracy < 0.5 % ■ Easy zero point correction using a magnet ■ Media temperature -20.120 °C ■ Thin film sensor ■ EAC declaration (upon request) Options ■ Approvals/Certificates - Explosion protection for gases - Certificate of measuring equipment for Russian Federation ■ Output signal (invers) 20.4 mA ■ Various process connections ■ Further electrical connections ■ Accuracy < 0.3% Application The pressure transmitter COMPACT ECOnomic HYDROGEN is suitable for measuring the relative and absolute pressure of hydrogen and media containing hydrogen. Constructional design / case Process connection Design: Compact case with outstanding protection against moisture Stainless steel mat.-no. 1.4301 (304) ■ G 1/2 B per EN 837-1 ■ G 1/4 B per EN 837-1 ■ G 1/4 A per DIN EN ISO 1179-2 (DIN 3852-11) model E ■ SITEC (M16x1,5, 60°, female thread) Pressure com- Ventilation via electrical connection pensation: Electrical con- Right-angle plug per Material wetted parts Process con- St. steel mat.-no. 1.4404/1.4435 (316L) nection: Diaphragm: St. steel mat.-no. 1.4404/1.4435 (316L) Internal gas- NBR (for process connection G1/2B and ket: SITEC (M16x5) only)

Open the catalog to page 1
Pressure transmitter COMPACT ECOnomic HYDROGEN - 2

Measuring system Sensor: Thin film sensor Signal: Damping: Measuring rate: Current range: Resolution: Load, Rb: 4...20 mA (20...4 mA), 2-wire technology 30 ms 250 Hz 3.7.23 mA 0.04 % of nominal range Rb < (Uv-10V)/0,02A [Ohm] Uv = supply voltage Supply voltage Standard version: Functional 10.30 V DC Nominal range * different measuring ranges upon request Accuracy General Limit point set- per DIN 16086 * at a maximal ambient temperature of 40 ° C Calibration vertical mounting position position: Extended temperature ranges upon request Accuracy: < 0.5 % of adjusted measuring...

Open the catalog to page 2
Pressure transmitter COMPACT ECOnomic HYDROGEN - 3

Zero point correction The zero point can be set easily with a magnet within ± 10% of the nominal range. To correct the zero point, hold a permanent magnet – a pin board magnet, for example – at the position marked on the pressure transmitter (i.e. the letter in a circle) for 1/2 to 2 1/2 minutes after the power has been switched on. To correct the zero point, atmospheric pressure has to be applied. Offsets for previously set values for initial and ultimate pressures will be corrected automatically by the device. A magnetic field applied outside of this time period has no effect on the...

Open the catalog to page 3
Pressure transmitter COMPACT ECOnomic HYDROGEN - 4

LABOM Mess- und Regeltechnik GmbH Im Gewerbepark 13 27798 Hude Germany Phone: +49 (0) 4408 804-0 Fax: +49 (0) 4408 804-100 e-mail: info@labom.com www.labom.com

Open the catalog to page 4