Overview: The document provides technical specifications for single-phase and three-phase motor-controlled AC/DC power sources, specifically the EPOS CV 821, EPOS CV 831, and EPOS CV 753 models. These power sources are designed for reliable load applications with manual or automatic voltage settings via ACTAS software.
Specifications:
  • Voltage and Current: The power sources offer a range of voltage outputs (15-270 VAC, 15-300 VDC for single-phase; 15-300 VACPN, 15-520 VACPP, 15-300 VDC for three-phase) with a step value of 1 V and accuracy of ±1%.
  • Load Capacity: Rated currents vary by model, with the EPOS CV 821 supporting up to 30 A AC/DC, the CV 831 up to 40 AAC/30 ADC, and the CV 753 up to 25 AAC/32 ADC.
  • Transformer and Frequency: The transformers have capacities of 8.1 kVA, 11.5 kVA, and 22.5 kVA, supporting DC, 50, or 60 Hz frequencies.
  • Protection and Regulation: Features include electronic fuses for overcurrent protection and motor-controlled regulation without separate phase control.
Performance:
  • Settling Time: Varies by model and mode, with DC settling times ranging from 3 ms/V to 42 ms/V and AC settling times from 7 ms/V to 8 ms/V.
  • Measurement Accuracy: Voltage accuracy is <0.2%, and current accuracy is <0.1%.
  • Sampling Rate: Ranges from 500 Hz to 10 kHz.
Physical and Environmental:
  • Power Supply: The systems require 230 VAC ±10% for single-phase and 3 x 400 VAC ±10% for three-phase models.
  • Housing and Dimensions: The units are housed in 19" racks with varying sizes and weights, from 39 kg to 130 kg.
  • Operating Conditions: Operating temperature is 0-50°C, with storage temperatures of -20 to 60°C and relative humidity of 5-90% non-condensing.
Compliance: The equipment complies with EN 61010-1: 2011 and EN 61326-1: 2013 standards for safety and EMC requirements.
Appendix: Detailed performance data for operating current, voltage drop, settling time, and maximum switch-on current for each model under various conditions.
See more

Catalog excerpts

 EPOS CV 821-831-753 Specifications -1

Single-phase and three-phase motor-controlled AC/DC power sources for reliable supply to the load applications. The output voltage is set either manually or automatically using the ACTAS software with the aid of variable voltage transformers controlled by servomotors. Output values and operating statuses are clearly displayed on status displays. The power source is short-circuit proof and protected against overload conditions. System concept EPOS CV 821 EPOS CV 831 EPOS CV 753 single-phase single-phase three-phase Source Voltage 1 x 15...270 VAC 1 x 15...270 VAC 3 x 15...300 VACpn Rated current 1 x 30 A AC/DC 1 x 40 AAC 3 x 25 AAC Type of load 30 A 40 A 8 A for max. 9 minutes across the entire across the entire stroke 25 A for max. 1 minute stroke range range across the entire stroke The operating conditions are detailed in the appendix! Rectification Two-pulse Six-pulse bridge circuit 3) bridge circuit 2) Isolation No galvanic isolation Integrated isolating Protection Electronic fuses for measuring and evaluating overcurrent, short-circuit and Regulation Motor-controlled No separate control of the individual phases, control phase Uxpn can be selected Settling time Range Accuracy Sampling rate 11 Depending on the mains connection 2) Without smoothing capacitor 3) With smoothing capacitor Technical specifications subject to change without prior notice | ©12/2019 KoCoS Messtechnik AG www.kocos.com Doc. 7614005 Rev. 2.00

 Open the catalog to page 1
 EPOS CV 821-831-753 Specifications -2

Complete system Power supply 230 VAC ±10%, 3 x 400 VAC ±10%, Discrete connections for supplying power to the control electronics and the power module separately Connections Industrial plug connectors Housing 19" housing 19" housing 19" housing Mounting depth Depth + 100 mm Depth + 50 mm 430 mm for connection plug for connection plug Display elements High-resolution 3.5" screen Jog dial 6 status LEDs Screen status indication Illuminated ring on the jog dial Environment Operating temperature: 0...50°C Storage temperature: -20...60°C Relative humidity: 5...90%, non-condensing Protection: Installed...

 Open the catalog to page 2
 EPOS CV 821-831-753 Specifications -3

Operating current, voltage drop, settling time ohmic load U/Irpl : Ripple Technical specifications subject to change without prior notice | ©12/2019 KoCoS Messtechnik AG www.kocos.com Doc. 7614005 Rev. 2.00

 Open the catalog to page 3
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.