1. Catalogs
  2. KoCoS Messtechnik AG
  3. ARTES 600 Specifications

ARTES 600 Specifications

 ARTES 600 Specifications

ARTES 600 Specifications

Product catalog summary
Applications
The document describes a highly precise, portable measuring system designed for functional tests on various types of protection equipment. It features four voltage outputs and six current outputs, enabling three-phase tests on static, digital, and self-powered relays, as well as differential protection relays. The device can be operated via a PC with ARTES testing software or through a built-in control panel with a 5" touch screen.
Sources
All signals can be independently set for phase, amplitude, and frequency. The system includes internal feedback for monitoring output values, issuing warnings if discrepancies occur. Outputs are protected against overload and short-circuits.
General Specifications
The frequency range is DC to 3 kHz, with transient signals up to 4 kHz. Frequency resolution is 0.001 Hz with an error of less than 0.01%. Phase angle ranges from 0 to 360° with a resolution of 0.001° and an error of less than 0.05°.
Voltage and Current Outputs
Voltage outputs include 4-phase, 3-phase, and 1-phase configurations with high accuracy and low total harmonic distortion (THD). Current outputs are available in 6-phase, 3-phase, and 1-phase configurations, also with high accuracy and low THD.
Low-Level Signal Outputs
These outputs are designed for testing protection devices with low-level signal inputs, offering high accuracy and independent setting capabilities.
DC Output
The DC output range is 12 to 260 VDC with a maximum power of 50 W and includes overload and short-circuit protection.
Analog Inputs
There are two analog inputs with a measuring range of 0 to ±20 mA, featuring galvanic isolation and high accuracy.
Multi-Function Inputs
These inputs can measure analog and binary signals, with configurable trigger thresholds and ranges. They are galvanically isolated and support various voltage ranges.
Binary Outputs
The system includes relay and transistor outputs with specified switching capacities and frequencies, all galvanically isolated.
Complete System
The device includes all necessary connections on the front panel, with integrated power supply, Ethernet, and USB interfaces. It can be operated in an upright position.
Operation
The system can be operated via PC with ARTES software or standalone using the touch screen and function keys.
Connections/Interfaces
Includes measurement connections, low-level signal outputs, generator socket, USB, Ethernet, and internal GPS receiver.
Supply Voltage
Rated voltage is 100 to 265 VAC or 120 to 265 VDC, with a wattage of 2500 W.
Construction
The device is housed in a portable 19" housing with IP20 protection, weighing 15.9 kg.
Environment
Operating temperature is 0 to 50°C, with storage temperature from -20 to 60°C. It complies with IEC standards for vibration and shock.
Generic Standards
Safety and EMC standards include EN 61010-1, EN 61326-1, EN 61000-6-4, and EN 61000-6-2.
See more

Catalog excerpts

 ARTES 600 Specifications -1

Applications Highly precise, portable measuring system for functional tests on various types of protection equipment. Four voltage outputs and six current outputs which can provide particularly high output power allow three-phase tests on static, digital and self-powered relays as well as differential protection relays. Analog measurement inputs also make it possible to test and calibrate transducers. The device can be operated and controlled either with a PC and the ARTES testing software or alternatively by means of the built-in control panel equipped with a high-resolution, resistive 5" touch screen, function keys and a jog wheel. Sources All signals can be set separately and independently of one another as regards phase, amplitude and frequency. The output values of the current and voltage amplifiers are monitored by means of internal feedback measurements. If the output values do not agree with the setpoint values, a warning is issued to this effect. All outputs also have overload and short-circuit protection. Frequency range Transient signals Frequency resolution Frequency accuracy Phase angle Phase resolution Phase accuracy Voltage outputs Current outputs Resolution 1 mA Low-level signal outputs Special low-level outputs with very high accuracy make it possible to test protection devices with low-level signal inputs. All signals can be set separately and independently of one another as regards phase, amplitude and frequency. All outputs also have overload and short-circuit protection. Number Output range Max. output current Frequency range Transient signals Frequency resolution Frequency accuracy Phase angle Phase resolution Phase accuracy For symmetrical output quantities Technical specifications subject to change without prior notice | ©06/2025 KoCoS Messtechnik AG www.kocos.com Doc. 7610201 Rev. 1.50

 Open the catalog to page 1
 ARTES 600 Specifications -2

Output range Output power Accuracy Protection Overload and short-circuit protection Analog inputs Number Measuring range Accuracy Protection Galvanic isolation via digital high-speed isolators Multi-functioninputs Multi-function inputs for the measurement of analog and binary signals. The trigger threshold and the trigger range can be freely configured for evaluation purposes. The inputs are also configurable for the measurement of potential-free contacts. Measuring ranges 2/10/300/600 VAC/DC Frequency range DC..6 kHz Trigger threshold/range 0.300 VDC, freely configurable, or potential-free contact...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.