1. Catalogs
  2. KoCoS Messtechnik AG
  3. ACTAS L260 | L360 Specifications

ACTAS L260 | L360 Specifications

ACTAS L260 | L360 Specifications

ACTAS L260 | L360 Specifications

Product catalog summary
System Concept: The document describes high-precision test systems designed for function tests on various switchgear devices, including circuit breakers and disconnectors. These systems are adaptable for development, laboratory, and production environments, featuring flexible connections and automatic control capabilities for voltage and current sources.
Control Outputs: The systems utilize electronic switching outputs (IGBT) for controlling closing and opening coils, with a voltage capacity of 300 VAC/DC and a peak current of 100 A. The time resolution is 0.1 ms with an accuracy of ±0.02 ms.
Analog Outputs: These outputs are used to set desired values and voltage waveforms, with an output range of 0...10 VDC and a load impedance greater than 10 kΩ.
Measurement Inputs: The system supports a maximum recording duration of 13.33 minutes at 500 Hz and 8 seconds at 50 kHz, with a time accuracy of ±0.005 ms. It features 16-bit A/D conversion and a measurement accuracy of 0.05% of range.
Binary Inputs: These inputs have a time resolution of 0.02 ms and a sampling rate of 50 kHz, with an activation range of 24…300 VDC.
Complete System: The system operates with a standard Windows PC using ACTAS 2.60 software for control and data evaluation. It includes a wide-range power supply and various PC interfaces.
Environmental Specifications: The operating temperature range is -10 to 50°C, with storage temperatures from -30 to 70°C. The system is protected to IP20 standards and conforms to CE standards EN 61010-1: 2011 and EN 61326-1: 2013.
Product Specifications: The document compares two models, ACTAS L260 and ACTAS L360, detailing differences in control outputs, measurement inputs, and additional equipment connections. The ACTAS L360 offers more extensive capabilities than the L260.
See more

Catalog excerpts

ACTAS L260 | L360 Specifications -1

System concept High-precision test systems for function tests on various types of switchgear device, including circuit breakers, disconnectors or earthing switches, regardless of the type of drive unit. The inputs and outputs are connected flexibly via industrial plug connectors, making the test systems particularly suitable for use in development and laboratory environments as well as in production environments. Digital and analog control outputs enable voltage or current sources to be controlled automatically, allowing fully automatic tests. In combination with PROMET, three-pole dynamic resistance measurements can be carried out on up to four interrupter units per pole. Control outputs Electronic switching outputs (IGBT) for single or three-phase control of the closing and opening coils. All operating sequences can be configured and output in increments of 1 ms. IGBTs for controlling the Voltage 300 VAC/DC re|ease coils Current 100 A peak Intrinsically safe via short-circuit Time resolution 0.1 ms and overload protection Binary output Relay output 30 VDC / 2 A (max. 220 VDC) (resistive load) Analog outputs for Analog outputs to set the desired values and the voltage waveform and to controlling external release connected sources. voltage sources Output range 0...10 VDC /1 mA Load impedance Power supply to external Reference voltage for 10 VDC sensors analog sensors Supply voltage for 5 VDC or 10 VDC, can be selected via jumper incremental sensors General Recording duration Time resolution Time accuracy A/D-conversion Accuracy Analog inputs Oversampling Sampling rates Activation range Measuring range close/open coil current Coil voltage Measuring range motor Motor voltage Sensor inputs 200 kHz per measurement channel (physical) 500 Hz...50 kHz, adjustable in steps Main contacts <5 ft Resistive contacts (PIR) >5 ft...12 kft combined with main contact inputs Binary inputs Time resolution Sampling rate Auxiliary contacts Incremental inputs for Limit frequency digital travel transducers device isolated against earth all measurement inputs isolated against earth Activation range 24...300 VDC, adjustable External supply, activation range configurable 200 kHz Technical specifications subject to change without prior notice | ©12/2019 KoCoS Messtechnik AG www.kocos.com Doc. 7612002 Rev. 1.12

 Open the catalog to page 1
ACTAS L260 | L360 Specifications -2

Complete Operation, system control, data storage and evaluation are carried out using a standard, external Windows PC system with the ACTAS 2.60 software. User interface ACTAS system software for the parameterization, execution and evaluation of switchgear tests under Windows 7/8.1/10 Power supply Wide-range power supply unit, nominal range 100...250 VDC and 90...250 VAC; 47...63 Hz working range: +6% / -10% of the nominal range Measurement connections Via safety plug connectors located on the back panel PC interfaces 1 x RJ45 Ethernet 1 x serial RS422 KoCoS interfaces 4 x control of external...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.