WPA-14-S-N

WPA-14-S-N

WPA-14-S-N

Product catalog summary
Purpose
The WPA-14-S-N fan is designed for air supply or extraction ventilation in rooms and workplaces, particularly recommended for use with local exhaust systems. It is suitable for stationary installation in ventilation or technical rooms. The fan should not be used for conveying aggressive media or substances that pose an explosion hazard. It complies with the ErP 2009/125/EC Directive.
Structure
The fan features a steel spiral housing and a motor with a radial impeller directly installed on the motor shaft (direct drive). The impeller blades are designed to resemble an aircraft wing profile, minimizing acoustic pressure levels. The outlet is compatible with round-section flexible connectors, and the inlet can be fitted with a connection ferrule. Both the inlet and outlet have protective grills for safety. The fan motor is mounted on a vibro-absorbing frame to prevent vibration transmission. Safety switches for power cut-off during servicing and installation are available upon request.
Dimensions
The fan model WPA-14-S-3-N has specific dimensions: A - 1000 mm, B - 1200 mm, C - 100 mm, W - 1100 mm, Z - 760 mm, D - 400 mm, E - 400 mm, F - 430 mm, n - 8 pcs, G - 10 mm, M - 640 mm, P - 840 mm, K - 400 mm, J - 455 mm, L - 915 mm.
Technical Data
The fan operates at 3000 synchronous rotations per minute with a supply voltage of 3x400 V and a motor rate of 15 kW. It has an ingress protection rating of IP54. The acoustic pressure level is 100 dB(A) at 1 meter and 91 dB(A) at 5 meters. The maximum volume flow is 23,100 m³/h, with a maximum vacuum of 4000 Pa. The fan weighs 182 kg.
Operational Conditions
The maximum temperature of the conveyed air is +60°C, and the maximum temperature within the work area is +40°C. The maximum dustiness of the conveyed air should not exceed 0.3 g/m³.
See more

Catalog excerpts

WPA-14-S-N-1

radial fans Purpose WPA-14-S-N is designed for air-supply- or extraction ventilation of rooms and workplaces, is recommended especially for use with system of local exhausts. The fan can be installed stationary in a ventilation rooms or other technical rooms. Do not use the fan for conveying the media of aggressive properties or substances causing explosion hazard. The construction meets the requirements of the ErP 2009/125/EC Directive. The fan consists of a steel spiral housing and a motor. Its radial impeller is directly installed on the motor shaft (direct drive). The cross-section of the impeller blades reminds the profile of an aircraft wing, providing low acoustic pressure level of the fan. Outlet connection is adapted for attachment of round-section flexible connectors, whereas the inlet can be equipped with a connection ferrule. For safety reasons, the inlet and outlet are equipped with protective grill. On demand of Customer, the fan can be delivered with another location of the outlet ferrule. The fan motor is screwed to the base which is placed on a vibroabsorbing frame, to avoid vibration transmission to the floor. On demand of Customer, we deliver safety switches to cut off the power supply during the servicing and installing activities (see catalogue card ELECTRICAL ACCESSORIES).

 Open the catalog to page 1
WPA-14-S-N-2

Technical data Type 1. Maximum temperature of the conveyed air is +60°C. Maximum temperature within the work area +40°C. 2. Maximum dustiness of the conveyed air should not exceed 0,3 g/m3.

 Open the catalog to page 2

All KLIMAWENT catalogs and technical brochures

  1. PODRYW-N

    1  Page

  2. WW-302-KL

    1  Page

  3. WOK-W

    2  Pages

  4. WOK-N

    2  Pages

  5. WPA-P-N

    2  Pages

  6. fast-p

    2  Pages

  7. WPA-S-N

    2  Pages

  8. WPA-E-N

    2  Pages

  9. AIRCARE

    2  Pages

  10. catalogue 2016

    256  Pages

  11. Catalogue 2015

    221  Pages

  12. SMOKING BOX

    2  Pages

  13. Roof Fans

    13  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.