1. Catalogs
  2. Kent Stainless
  3. KVCRP Pop Up Drain - Double Contained / Dual Skin

KVCRP Pop Up Drain - Double Contained / Dual Skin

KVCRP Pop Up Drain - Double Contained / Dual Skin

Product catalog summary
Product Overview
The Kent KVCRP Pop Up Drain is a dual skin, double contained pneumatic floor gully designed for various industrial applications. It features a double flange/gasket connection for enhanced containment and safety.

Activation Options
  • Control Room
  • Sprinkler System
  • Air Connection
  • Wall Mounted Rotary Switch

Pneumatic Valve Options
  • Single Acting Sprung Out Cylinder: Requires air supply to close; opens automatically if air supply fails, ideal for fire suppression systems.
  • Single Acting Sprung In Cylinder: Requires air supply to open; remains sealed if air supply fails, suitable for clean production areas.
  • Double Acting Cylinder: Requires air supply to both open and close, used for cleaning cycles.

Industries
  • BioPharma
  • Pharmaceutical
  • Laboratories

Specifications
Product CodeHeightTop DiameterBody DiameterOutletFlow Rate (US GPM)
KVCRPDC400/4”/6” RD20.4in (519mm)15.7in (400mm)14.56in (370mm)4” Sch 10126.8 GPM (8.0 l/s)
KVCRPDC400/6”/8” RD20.4in (519mm)15.7in (400mm)14.56in (370mm)6” Sch 10317 GPM (20 l/s)
KHCRPDC400/4”/6” RD20.4in (519mm)15.7in (400mm)14.56in (370mm)4” Sch 1097.1 GPM (6.0 l/s)
KHCRPDC400/6”/8” RD20.4in (519mm)15.7in (400mm)14.56in (370mm)6” Sch 10221.9 GPM (14.0 l/s)

Outlet Options
  • Bottom Outlet with P Bend Trap
  • Side Outlet with Running Trap
  • Double Contained Outlets for Stainless Steel or Polypropylene Pipe
See more

Catalog excerpts

KVCRP Pop Up Drain - Double Contained / Dual Skin-1

Kent KVCRP Pop Up Drain - Double Contained / Dual Skin Kent KVCRP Pop Up Drain - Double Contained / Dual Skin Kent Kent KVCRP Pop Up Drain - Double Contained / Dual Skin This is a Dual Skin, Twin Walled or Double Contained version of our KVCRP Pneumatic Floor Gully. The pneumatic connection is accessed from inside the drain body. A flange supplied by Kent is mechanically connected to the inward air pipe. A second flange is connected to the internal air pipe and these come together to form a double flange/gasket connection. There are 3 options for the pneumatic valve choice: Single Acting Sprung Out Cylinder Air supply required to close the drain and exhausted to allow the cover to open using an internal spring. This system is generally used when the drains are connected to the fire suppression system. In the event of the air supply system failing the covers will open. Single Acting Sprung In Cylinder Air supply required to open the drain and exhausted to allow the cover to close using an internal spring. This system is generally used in clean production areas. In the event of the air supply system failing the covers will remain sealed. Double Acting Cylinder Air supply is required to both open and close the drain, this system is generally used when drains are to be opened for cleaning / wash down cycles. Constant air supply required to keep the cover sealed. INDUSTRIES - BioPharma - Pharmaceutical - Laboratories t it Opening Options Sprung Out - Sprung In - Double Action 1.57” (40mm) clear opening under cover Product Code Bottom Outlet With P Bend Trap

 Open the catalog to page 1
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.