1. Catalogs
  2. JEAN MÜLLER
  3. PLClassic in SASIL

PLClassic in SASIL

PLClassic in SASIL
1 / 22 PagesView full catalog

PLClassic in SASIL

Product catalog summary
System Description
The Powerlizer Classic is an energy management system that integrates metering and communication technology within SASIL low voltage switchboards. It features sensors integrated into switch-fuses, minimal installation effort due to bus technology, and Ethernet communication at the low voltage level. The system provides a web-based information system and utilizes the PLPro software for enhanced functionality.
Key Advantages
  • Integration of sensors in switch-fuses for efficient energy distribution.
  • Reliable data recording and analysis for improved service reliability and cost-oriented energy distribution.
  • Complete transparency in energy balance considerations through managed distribution and allocation of energy costs.
System Information
The PLMaster can manage up to 60 sensors connected via the JM data bus, which is based on the RS-485 interface. It serves as the central data recorder, performing functions such as data recording, sensor configuration, long-term data storage, and Ethernet communication.
Communication
The PLMaster supports network-level communication, enabling online visualization, email reporting, SMS notifications, and network communication with PC-based control systems. The PLPro software offers centralized visualization, data analysis, and cost management.
Configuration
Configuration of the PLMaster system is done using the PLConfig software, compatible with Windows 2000/XP. The PLClassic and PLVario systems are incompatible at the field bus level but can share data at the network level.
Product Definition and Application
The PLMaster is the central unit in the energy management system, featuring Ethernet and RS-485 communication. It is used for energy data recording and communication in low voltage distribution panels, complementing SASIL switchgear technology.
Operation and Handling
The PLMaster features a front LCD display for user interaction, with LEDs indicating operational status. A keyboard allows for data entry and configuration, and a serial RS-232 interface enables configuration via PLConfig software.
Connections
The PLMaster includes an Ethernet interface, digital I/O interface, and various connectors for the JM data bus, facilitating comprehensive system integration.
Technical Specifications and Components
Terminals: The document outlines various terminals for data buses and power supply, including Ethernet interface, digital I/O interface, and multiway connectors. Specific terminals are designated for JM Data bus A-D, power supply DC24V, and ground connections.
PLMaster Technical Data: The PLMaster system supports asynchronous/half-duplex communication via RS-485, with a maximum of 60 components. It operates within a temperature range of -10 to +55°C and features an LCD display with IP40 protection.
Measuring Module EE05: Integrated into SASIL switch-fuses, this module measures current, voltage, and power, and communicates with the PLMaster system via RS-485. It includes fuse monitoring and requires a DC 24V power supply.
Fuse Monitoring ES00: This device monitors fuse status in SASIL switch-fuses, powered by the monitored network without additional supply. It signals fuse operation through LEDs and relay activation.
PLSensor: Designed for DIN rail mounting, it measures current and voltage in three-phase systems and communicates with the PLMaster system. It requires a DC 24V power supply and processes status information from circuit breakers.
Key Features and Applications
The systems are designed for integration with SASIL technology, focusing on energy data acquisition in low voltage distribution panels. The devices support serial communication and are equipped with various interfaces for data transmission. Monitoring and operational status are indicated through LEDs, providing clear visual feedback on system performance.
Standards and Compliance
The systems comply with EMC standards EN61000-6-2, ensuring electromagnetic compatibility. The devices are designed for specific environmental conditions, with defined temperature ranges and protection classes.
Product Definition
The PLSensor is designed for DIN mounting rail installation and is used for surface mounting. It features an electronic current and voltage sensor and communicates with the PLMaster system via a serial RS-485 (JM Data bus) interface.
Application
The PLSensor is used in conjunction with the PLMaster and SASIL technology for energy data recording in low voltage distribution panels. It is compatible with circuit-breakers and fuse combination units.
Product Description
The PLSensor measures all relevant electrical quantities of three-phase systems using current transformers and voltage taps. It transmits these measurements to the PLMaster via a serial data bus. The sensor requires a DC 24V power supply and can process signals from circuit-breakers, such as position indicators and release signals.
Measured Quantities
The PLSensor measures phase voltage, phase current, power factor, active power, reactive power, apparent power, and both active and reactive energy in a four-quadrant metering system.
Status Information
The sensor provides fuse monitoring, switch position indication, and fault signals from circuit-breakers.
Operation
Operation and display are managed through colored LEDs and a push-button. The sensor is configured by selecting an address in the PLMaster and activating the configuration mode via the push-button. The status LEDs indicate different operational modes, such as correct operation, device error, and configuration mode.
Connections
The PLSensor has various terminals for voltage taps, current transformers, circuit breaker signals, and the JM Data bus. It includes connections for power supply, ground, and auxiliary switches.
Technical Data
The PLSensor operates within a voltage range of 400V to 690V and requires a DC 24V power supply. It supports asynchronous data transmission via RS-485 with a baud rate of 153.6 kBaud. The device is designed for a temperature range of -10 to +55°C and has a protection class of IP20.
See more

Catalog excerpts

PLClassic in SASIL-1

52 Powerlizer Classic in SASIL

 Open the catalog to page 1
PLClassic in SASIL-2

53 Powerlizer Classic within SASIL

 Open the catalog to page 2
PLClassic in SASIL-3

54 55 60 64 68 70 99 114 55 60 64 68 70 99 114 Seite page Inhalt Contents Systembeschreibung Zubehör Zeichnungen Description Accessories Drawings PLMaster Messmodul EE05 Sicherungsüberwachung ES00 PLSensor PLMaster Measuring module EE05 Fuse monitoring ES00 PLSensor PLClassic

 Open the catalog to page 3
PLClassic in SASIL-4

PowerlizerVario PowerlizerVario PowerlizerVario in SASIL PowerlizerVario within SASIL PowerlizerClassic in SASIL PowerlizerClassic within SASIL Schalttafeleinbaugeräte Panel meter Software Software Anhang Appendix 55 Konzeptvorteile POWERLIZER CLASSIC • Integration der Sensoren in der Schaltleiste • Minimaler Installationsaufwand durch Bustechnik • Ethernetkommunikation direkt in der NS-Ebene • Web-basierendes Informationssystem • Leistungsfähige Softwareebene PLPro Das Energiemanagement-System POWERLIZER Classic integriert Mess- und Kommunikationstechnik in die SASIL-Niederspannungsschaltanlage....

 Open the catalog to page 4
PLClassic in SASIL-5

56 Systeminfo Bis zu 60 Sensoren werden über den JM-Datenbus innerhalb der Niederspannungsverteilung mit einem PLMaster verbunden. Die Sensoren können wahlweise vom Typ EE05 (in SASIL-Schaltleisten integriert) oder PLSensor (Hutschienen-Gerät) sein. Der PLSensor wird bevorzugt zur Datenerfassung der Leistungsschalter eingesetzt. Der JM-Datenbus ist als RS-485-Schnittstelle ausgeführt und zur effizienten Datenübertragung in vier galvanisch getrennte Busstränge unterteilt. Jeder Busstrang wird am letzten Teilnehmer (Sensor) mit einem Widerstand von 120Ù abgeschlossen. Der PLMaster übernimmt als...

 Open the catalog to page 5
PLClassic in SASIL-6

PowerlizerVario PowerlizerVario PowerlizerVario in SASIL PowerlizerVario within SASIL PowerlizerClassic in SASIL PowerlizerClassic within SASIL Schalttafeleinbaugeräte Panel meter Software Software Anhang Appendix 57 Kommunikation Die standardisierte Kommunikationsebene des PLMaster ist die Netzwerkebene. Eine Vielzahl an Funktionen und Diensten kann somit direkt ohne Erweiterung der Infrastruktur genutzt werden. • Online-Visualisierung durch Web-Server (http): Visualisiert als WEB-basierendes Informationssystem den Anlagenzustand, wie Messwerte, Zählerwerte, Betriebs- und Störmeldungen online...

 Open the catalog to page 6
PLClassic in SASIL-7

58 Konfiguration Mit der Software PLConfig kann die Konfiguration des PLMaster-Systems sowohl seriell über die Serviceschnittstelle (RS-232) als auch über die Speicherkarte ausgeführt werden. Die Software ist unter den Windows Betriebssystemen WIN2000/XP lauffähig. PLConfig wird ohne Mehrpreis zusammen mit dem PLMaster zur Verfügung gestellt. Kompatibilität der Systeme PLClassic zu PLVario Auf der Feldbusebene sind die Komponenten des PLClassic Systems (JM-Datenbus) nicht kompatibel mit den Komponenten des PLVario Systems (CANBus). Auf der Netzwerkebene können die Daten von PLMaster und PLVario-NET...

 Open the catalog to page 7
PLClassic in SASIL-8

PowerlizerVario PowerlizerVario PowerlizerVario in SASIL PowerlizerVario within SASIL PowerlizerClassic in SASIL PowerlizerClassic within SASIL Schalttafeleinbaugeräte Panel meter Software Software Anhang Appendix 59 Verdrahtungsplan wiring diagram PLClassic

 Open the catalog to page 8
PLClassic in SASIL-9

60 PLMaster Produktdefinition • Zentrale Verwaltungseinheit im Energiemanagementsystem und Webserver • Schubeinsatztechnik, analog der SASILSchaltgeräte • Ethernetkommunikation TCP/IP • Serielle Kommunikation zu den Messsensoren nach RS-485 (JM-Datenbus) Einsatzbereich • Energiedatenerfassung und Datenkommunikation in der Niederspannungsverteilung • Im Umfeld der SASIL Schaltgerätetechnologie • In Verbindung mit PLSensor oder EE05 Messmodulen Produktbeschreibung Der PLMaster integriert mit seiner Ethernet-Schnittstelle moderne Kommunikationstechnik in die Niederspannungsschaltanlage. Als zentraler...

 Open the catalog to page 9
PLClassic in SASIL-10

PowerlizerVario PowerlizerVario PowerlizerVario in SASIL PowerlizerVario within SASIL PowerlizerClassic in SASIL PowerlizerClassic within SASIL Schalttafeleinbaugeräte Panel meter Software Software Anhang Appendix 61 PLMaster Handhabung Die Anzeige (Bedienerdialog) wird frontseitig durch ein hinterleuchtetes LCD-Display 1 ermöglicht. Zur Langzeitarchivierung der Daten kann eine CompactFlash® Speicherkarte der Firma SanDisk® verwendet werden. Diese wird in den Steckplatz 2 über einen PCMCIA-Adapter gesteckt. Leuchtdioden zeigen die verschiedenen Betriebsmodi an. Status-LED 3 für Funktion der Speicherkarte:...

 Open the catalog to page 10
PLClassic in SASIL-11

62 PLMaster Anschlüsse 1 Ethernetschnittstelle (RJ-45) 2 digitale I/O Schnittstelle (SUB-25D) 3 Steckerbuchsenleiste Klemme 1: JM-Datenbus A-D GND Klemme 2: nicht belegt Klemme 3: JM-Datenbus A DATA A Klemme 4: JM-Datenbus A DATA B Klemme 5: JM-Datenbus A Schirmung Klemme 6: JM-Datenbus B DATA A Klemme 7: JM-Datenbus B DATA B Klemme 8: JM-Datenbus B Schirmung Klemme 9: JM-Datenbus C DATA A Klemme 10: JM-Datenbus C DATA B Klemme 11: JM-Datenbus C Schirmung Klemme 12: JM-Datenbus D DATA A Klemme 13: JM-Datenbus D DATA B Klemme 14: JM-Datenbus D Schirmung Klemme 15: Versorgungsspannung DC24V Klemme...

 Open the catalog to page 11
PLClassic in SASIL-12

PowerlizerVario PowerlizerVario PowerlizerVario in SASIL PowerlizerVario within SASIL PowerlizerClassic in SASIL PowerlizerClassic within SASIL Schalttafeleinbaugeräte Panel meter Software Software Anhang Appendix 63 PLMaster Typ / Type Artikel-Nr. / Article No. Bestelldaten /Ordering information PLMaster/ ETHERNET / PLMaster/ ETHERNET Weitere Ausführungen auf Anfrage / Additional options available on request E9405012 Typ PLMaster / Type PLMaster Technische Daten / Technical data DC24 15 RS-485 asynchron/halbduplex / asynchronous / simplex 153,6 max. 60 Komponenten / 60 components maximum RS-232...

 Open the catalog to page 12
PLClassic in SASIL-13

NEUe_Rheienfolge.indd tr.row {} td.cell {} div.block {} div.paragraph {} .font0 { font:7.00pt "Arial", sans-serif; } .font1 { font:8.00pt "Arial", sans-serif; } .font2 { font:28.00pt "Arial", sans-serif; } .font3 { font:26.00pt "Georgia", serif; } Messmodul EEof Measuring module EE05 Produktdefinition In SASIL integriertes Messmodul 畕 Strom- und Spannungsmessung, Leistungs-berechnung Serielle Kommunikation zum PLMaster-System nach RS-485 (JM-Datenbus) Օ Digitale Erfassung Sicherungsuberwachung und Schaltstellungsanzeige Einsatzbereich Energiedatenerfassung in der Niederspannungs-verteilung...

 Open the catalog to page 13
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.