Rogowski coil Current sensors_ARCT-M-ID series - 1

ARCT-XXX-M-ID SERIES ARCT-M-ID series is a Rogowski coil split-core current transformer for the electronic measurement of AC waveform current with galvanic separation between the primary current and the secondary output voltage. ARCT-M-ID series is an ideal CTid built-in Rogowski coil split-core current transformer for JAGUAR IoT meters, and its ratio error and phase displacement are fully tested with IEC 61869-2 standards accuracy Class 1.0 and IEEE/ANSI C57.13 Class 1.2. Features ■ Quick & simple install with plug & play type ■ Safe 120 mV secondary output (60Hz) ■ Current range: 10-5000+Amps ■ Accuracy standard: IEEE/ANSI C57.13 Class 1.2 Link How to Use 1. Specifications ■ Coil length : 11.81 inches(30 cm) - 118.11 inches(300 cm) ■ Window size : 3.15 inches(80 mm) - 11.81 inches(300 mm) ■ Cord diameter : 0.31 inches(8 ± 0.2 mm) ■ Weight : 150 - 500 g ■ Output level (RMS) : 100 mV / kA @ 50 Hz, 120 mV / kA @ 60 Hz ■ Positioning error : One loop — < 0.8% of reading Two loop —*• < 0.25% of reading

Open the catalog to page 1
Rogowski coil Current sensors_ARCT-M-ID series - 2

ARCT-XXX-M-ID SERIES ■ Frequency : 40 Hz - 5 kHz ■ Overvoltage category : CAT lll1000 Vrms(Non-service Entrance), CAT IV 600 Vrms(Non-Service Entrance) ■ Pollution degree : 2, Controlled Environment ■ Insulation test voltage : 7400 Vrms / 1 min ■ Connection cable : 2 x AWG24 [option AWG18] shielded, standard length 1.5m (option 2m -15 m) ■ Protection degree : IP67(Option) ■ Altitude : up to 2000 m over sea-level ■ Operating temperature : -30 °C +80 °C(-22 °F ~+176 °F) ■ Storage temperature : -40 °C +90 °C(-104 °F ~+194 °F) ■ Relative humidity tolerance : 0 - 95% ■ Installation and use :...

Open the catalog to page 2
Rogowski coil Current sensors_ARCT-M-ID series - 3

ARCT-XXX-M-ID SERIES LED light flashes when commanded through the interface. 4. Typical Accuracy ■ In the following graphs, a positive phase angle error indicates that the output of the Rogowski coil CT with an integrator leads the primary current. ■ Graphs show typical performance at 25°C, 50/60Hz ■ Performance Graphs - The standard CT meets IEEE C57.13 class 0.6 standard & IEC 61869-2 class 0.5S standard www.hqsensing.com Specifications are subject to change without notice

Open the catalog to page 3
Rogowski coil Current sensors_ARCT-M-ID series - 4

ARCT-XXX-M-ID SERIES ARCT-115-M-ID Series Rated current: 1000A/120mV(60Hz) Current error (%) Only meets IEC 61869-2 Class 1.0 at rated currents greater than 1000 A. ARCT-180-M-ID Series two-loop [Rated current: 2000A/120mV(60Hz)] Only meets IEC 61869-2 Class 0.5S at rated currents greater than 2000 A.

Open the catalog to page 4
Rogowski coil Current sensors_ARCT-M-ID series - 5

ARCT-XXX-M-ID SERIES ARCT-300-M-ID Series two-loop [Rated current: 3000A/120mV(60Hz)] Current error (%) Only meets IEC 61869-2 Class 0.5S at rated currents greater than 3000 A. Safety The J&D CTs are UL/EN 61010-1, CE, RoHS compliant and certified, are also conformed up to Pollution degree 2, 1000Vac CAT III, 600V CAT IV rated devices. Please be sure that Failure to follow these instructions can result in serious injury and/or cause damage. The Rogowski coil current transducer shall be used in electric/electronic equipment in accordance with the operating instructions of all related systems...