Gen5 Riva Polyphase Meter The Gen™5 Riva Polyphase Meter. equipped with power microprocessors as well as an embedded Linux operating system, combines robust polyphase electric smart metering functionality with innovative distributed intelligence (DI) edge computing capability on Itron’s Gen5 industrial IoT (IIoT) network. This unique feature enables a new approach to AMI for your commercial & industrial customers, enabling AMI, consumer engagement, grid operations, smart city applications and more – from every single meter. In addition to providing full electric smart meter functionality for commercial & industrial (C&I) customers, each Gen5 Riva Polyphase Meter is embedded with robust DI capability that processes and analyzes data in real time at the edge to provide insights to control and manage the grid more accurately. Improve grid efficiency, reliability and safety while transforming customer service and adapting to an evolving energy landscape. Harness a unified, intelligently connected network platform with DI to unlock new applications in smart energy, water and communities. Leverage DI for advanced applications Itron’s DI platform utilizes an app store model, similar to a smartphone. This ensures rapid, continuous innovation, choice and new value across a broad ecosystem of apps from multiple vendors. This model offers significant ROI improvements along with the ability to easily add additional smart utility and city use cases as business needs ev
Open the catalog to page 1FEATURES AND BENEFITS Flexible Two-Way Communications Tamper Detection » Bi-directional Distributed Intelligence applications » Detect and report exceptions for events such as magnetic fraud attacks » Execute all supported meter reading, configuration update and firmware download functionality » Customize targeted meter firmware updates » Support on-demand readings from the meter Upgradable Firmware » Customize firmware upgrades with the ability to automatically roll-back if activation fails » Create multiple firmware images including primary and pending Bi-Directional Metering » Store received...
Open the catalog to page 2Meets applicable standards: » ANSI C12.1 - 2008 (American National Standard for Electricity Meters - Code for Electricity Metering) » ANSI C12.20 - 2010 (American National Standard for Electricity Meters - 0.2 and 0.5 Accuracy Classes) » ANSI/IEEE C62.45 - 2002 (Guide to Surge Testing on Low-Voltage AC Power Circuits) » ANSI MH 10.8 - 2005 Specification for Bar Code » ANSI ASQZ 1.4 - 2008 Sampling Procedures and Tables for Inspection by Attributes » IEC 61000-4-2 2008 » IEC 61000-4-4 2012 » IEEE C37.90.1 - 2004 SWC Surge Testing » IEEE C62.45 Recommended Practice on Surge Testing for Equipment...
Open the catalog to page 3Power Requirements Voltage rating: 120v-480v Frequency: 60 Hz (50 Hz) Operating voltage: ± 20% (60Hz); ± 10% (50 Hz) Operating range: ± 3 Hz Battery voltage: 3.6 V nominal Battery operating range: 3.4 V-3.8 V Operating Environment Temperature: -40° to +85°C Humidity: 0% to 95% relative humidity Transient/Surge Suppression ANSI C12.20 0.2 accuracy class Demand calculation: Block or Rolling Energy calculation: Bi-directional (Wh, VAh, VARh and VARh Q1-Q4)) Time Reference When Off Network Line sync: Power line frequency Crystal sync: 5.8 PPM @ 25°C; 110 PPM over full temperature range Eight-digit...
Open the catalog to page 44 Pages
4 Pages
3 Pages
4 Pages
4 Pages
2 Pages
4 Pages
4 Pages
4 Pages
4 Pages
3 Pages
4 Pages