1. Catalogs
  2. Iskra d.d.
  3. Power line carrier equipment ET9
video corpo

Power line carrier equipment ET9

Power line carrier equipment ET9

Power line carrier equipment ET9

Product catalog summary
Overview: The document outlines the technical specifications and features of the ET9 Power Line Carrier (PLC) equipment, which is used in telecommunication systems over high-voltage transmission lines. It emphasizes the integration of modern technologies into traditional PLC systems, allowing for the transmission of speech, data, and teleprotection signals within a single channel.
Specifications:
  • Carrier Rack Options: Two configurations are available: ET9-60W and ET9-120W, supporting up to 6 channels with output power of 60W and 120W respectively.
  • Frequency Range: Operates between 20 kHz and 1000 kHz, programmable without hardware changes.
  • Data Transmission: Utilizes FSK modulation with speeds from 50 Bd to 1200 Bd, supporting asynchronous transmission.
  • Interfaces: Includes universal AF interfaces, telephone interfaces (FXO, FXS, 4W E&M), and RS-232/Ethernet ports for management.
  • Power Supply: Compatible with AC (82V - 264V) and DC (40V - 264V) power sources.
Features:
  • Integrated Modems: Supports integrated FSK modems for data transmission.
  • Teleprotection: Compatible with integrated or external DZ9 teleprotection equipment.
  • Management: Managed via Pegasus SE GUI software, supporting SNMP traps for remote control and monitoring.
  • Synchronization: Capable of synchronization with external GPS signals (PPS, IRIG-B, SNTP).
  • Standards Compliance: Complies with IEC 60495 and RoHS standards.
Applications: The ET9 equipment is suitable for point-to-point communication between substations and as part of private communication systems in power utilities. It supports the transmission of voice channels, teleprotection signaling, and binary states, making it a versatile solution for modern telecommunication needs in power utilities.
Pegasus GUI Software: The document also provides technical specifications and configuration details for the Pegasus GUI-based PC software used for supervision and configuration over RS232 or LAN interfaces.
Specifications:
  • Power Supply: Supports DC (40 V - 264 V) and AC (82 V - 264 V).
  • Dimensions and Weight: Two configurations are provided:
    • 482.6 mm x 534 mm x 332 mm, weighing 23 kg.
    • 482.6 mm x 354 mm x 332 mm, weighing 14 kg.
  • Max Power Consumption: 280 W and 470 W for different configurations.
Equipment Configuration:
  • ET9-60W and ET9-120W configurations are available, with respective sizes of 19'' / 7U + 1U and 19'' / 11U + 1U.
  • LED indicators are present on the ET9 front panel for status monitoring.
  • Relay alarm outputs are included for alerting purposes.
Standards and Compliance:
  • Complies with IEC 60495:1993, IEC 60950-1 (LVD), and RoHS standards.
Ambient Conditions:
  • Storage: Temperature range of -40 °C to +70 °C with humidity below 100%.
  • Operation: Temperature range of -5 °C to +45 °C with humidity below 95%.
Remote Control and Monitoring:
  • SNMP traps are available for remote control of ET9 equipment.
  • Full access to remote ET9 equipment is provided over an embedded operational channel (EOC).
See more

Catalog excerpts

Power line carrier equipment ET9-1

TEHNICAL DATA TECHNICAL DATA AF PART UNIVERSAL AF INTERFACE USEFUL BANDWIDTH TRANSIT FILTERS PROGRAMMABLE BAND PASS FIR FILTERS CONNECTION TYPE INPUT / OUTPUT LEVEL ADJUSTMENT CARRIER RACK OPTIONS ET9 INPUT / OUTPUT IMPEDANCE 4-w, SYMMETRICAL, GALVANIC ISOLATED CARRIER RACK FOR ET9 PLC EQUIPMENT UP TO 6 CHANNELS, OUTPUT POWER (PEP) UP TO 60 W CARRIER RACK FOR ET9 PLC EQUIPMENT UP TO 6 CHANNELS, OUTPUT POWER (PEP) UP TO 120 W UNIVERSAL TELEPHONE INTERFACE FXS 2-w SUBSCRIBER INTERFACE - RING FREQUENCY NUMBER OF REQ.-UNITS - INPUT / OUTPUT LEVEL ADJUSTMENT BUILDING BLOCKS FOR ET9 - POWER PART POWER PART POWER SUPPLY UNIT - INPUT / OUTPUT LEVEL ADJUSTMENT SUB RACK FOR POWER AMPLIFIER AND TRANSMIT LINE FILTERS - RING DETECTOR POWER AMPLIFIER 4-w PAX INTERFACE WITH E&M SIGNALING TRANSMIT LINE FILTER RECIVE LINE FILTER - INPUT / OUTPUT LEVEL ADJUSTMENT LINE MATCHING UNIT SUMMING TRANSFORMER UNIT SPEECH LOW-PASS FILTER CUT-OFF FREQUENCY DATA TRANSMISSION BUILDING BLOCKS FOR ET9 - PROCESSING PART MODEM FSK NUMBER OF REQ.-UNITS PROCESSING PART POWER SUPPLY CENTRALIZED MANAGEMENT AND SUPERVISION UNIT MODULATION UNIT AF ACCESS UNIT WITH UNIVERSAL TELEPHONE INTERFACE - TWO 4-w UNIVERSAL AF INTERFACES - ONE 2-w OR 4-w TELEPHONE INTERFACE AF ACCESS UNIT WITH INTEGRATED MODEMS - TRANSMISSION MODE - TRANSMISSION SPEED PEGASUS - GUI BASED PC SOFTWARE FOR SUPERVISION AND CONFIGURATION OVER RS232 OR LAN INTERFACE SNMP TRAPS FOR ET9 EQUIPMENT REMOTE CONTROL LED INDICATORS ON ET9 FRONT PANEL RELAY ALARM OUTPUTS FULL ACCESS TO REMOTE ET9 EQUIPMENT OVER EMBEDDED OPERATIONAL CHANNEL (EOC) STANDARDS STATE RELAY UNIT TELEPROTECTION APPLICATION - TLI/LFI LINE UNIT WITH ANALOGUE LINE INTERFACE - CSR COMMAND AND SIGNALING RELAY UNIT (2 COMMANDS) POWER LINE CARRIER EQUIPMENT ET9 - STORAGE (TEMPERATURE/HUMIDITY) - OPERATION (TEMPERATURE/HUMIDITY) - TWO 4-w UNIVERSAL AF ACCESS INTERFACE * ET9 REQUIRES AT LEAST ONE AF ACCESS UNIT TYPE NF9, TG9 OR AFA POWER SUPPLY POWER SUPPLY MAX. POWER CONSUMPTION - EQUIPMENT CONFIGURATION ET9-60W GENERAL TECHNICAL DATA PLC COMMUNICATION LINKS ORGANIZED OVER HIGH-VOLTAGE TRANSMISSION LINES REMAINS TRADITIONAL SOLUTION IN POWER UTILITIES MECHANICAL CONSTRUCTION NOMINAL CHANNEL BANDWIDTH NORMAL / INVERSE Tx / Rx FREQUENCY BAND POSITION IN RF BAND ADJACENT / NON-ADJACENT CHANNEL ALLOCATION IN RF RANGE PROGRAMMABLE IN ALL RF RANGE , STEP 1 kHz RECEIVER SENSITIVITY NOMINAL OUTPUT IMPEDANCE AMBIENT CONDITIONS EQUIPMENT CONFIGURATION DIMENSIONS (WxHxD) www.iskra.eu • Published by Iskra, d. d. • Version 3.0, December 2017 PLC LINKS ARE POINT TO POINT COMMUNICATIONS USED FOR SIGNALS TRANSMISSION BETWEEN SUBSTATIONS AS WELL AS A PART OF PRIVATE COMMUNICATION SYSTEM OF POWER UTILITIES NEW TECHNOLOGIES AND SOLUTIONS IN OTHER COMMUNICATION SYSTEMS ARE NOW A DAYS USED ALSO IN PLC SYSTEMS. DIGITAL SIGNAL PROCESSING ENABLES TRANSMISSION OF SPEECH, DATA AND TELEPROTECTION SIGNALS INSIDE THE SAME PLC

 Open the catalog to page 1
Power line carrier equipment ET9-2

POWER LINE CARRIER EQUIPMENT ET9 POWER LINE CARRIER EQUIPMENT ET9 TRANSMISSION OF VOICE CHANNELS (FXO, FXS, 4W E&M) TRANSMISSION OF UP TO 6 PLC CHANNELS EXTENDED CARRIER FREQUENCY RANGE FROM 20 kHz UP TO 1000 kHz – PROGRAMMABLE WITHOUT EXCHANGING HARDWARE AUTOMATIC RF CHANNEL EQUALIZATION (AEQ) TRANSMISSION OF TELEPROTECTION SIGNALING – INTEGRATED OR EXTERNAL DZ9 TELEPROTECTION EQUIPMENT OR EXTERNAL EQUIPMENT OF OTHER VENDORS UNIVERSAL TELEPHONE INTERFACES (FXO, FXS, 4w E&M) TRANSMISSION OF BINARY STATES TRANSMISSION OF DATA USING FSK (50 – 1200 Bd) TELECOMMUNICATION RESOURCE FOR DIFFERENT TELECOMMUNICATION...

 Open the catalog to page 2
Power line carrier equipment ET9-3

POWER LINE CARRIER EQUIPMENT ET9 POWER LINE CARRIER EQUIPMENT ET9 TRANSMISSION OF VOICE CHANNELS (FXO, FXS, 4W E&M) TRANSMISSION OF UP TO 6 PLC CHANNELS EXTENDED CARRIER FREQUENCY RANGE FROM 20 kHz UP TO 1000 kHz – PROGRAMMABLE WITHOUT EXCHANGING HARDWARE AUTOMATIC RF CHANNEL EQUALIZATION (AEQ) TRANSMISSION OF TELEPROTECTION SIGNALING – INTEGRATED OR EXTERNAL DZ9 TELEPROTECTION EQUIPMENT OR EXTERNAL EQUIPMENT OF OTHER VENDORS UNIVERSAL TELEPHONE INTERFACES (FXO, FXS, 4w E&M) TRANSMISSION OF BINARY STATES TRANSMISSION OF DATA USING FSK (50 – 1200 Bd) TELECOMMUNICATION RESOURCE FOR DIFFERENT TELECOMMUNICATION...

 Open the catalog to page 3
Power line carrier equipment ET9-4

TEHNICAL DATA TECHNICAL DATA AF PART UNIVERSAL AF INTERFACE USEFUL BANDWIDTH TRANSIT FILTERS PROGRAMMABLE BAND PASS FIR FILTERS CONNECTION TYPE INPUT / OUTPUT LEVEL ADJUSTMENT CARRIER RACK OPTIONS ET9 INPUT / OUTPUT IMPEDANCE 4-w, SYMMETRICAL, GALVANIC ISOLATED CARRIER RACK FOR ET9 PLC EQUIPMENT UP TO 6 CHANNELS, OUTPUT POWER (PEP) UP TO 60 W CARRIER RACK FOR ET9 PLC EQUIPMENT UP TO 6 CHANNELS, OUTPUT POWER (PEP) UP TO 120 W UNIVERSAL TELEPHONE INTERFACE FXS 2-w SUBSCRIBER INTERFACE - RING FREQUENCY NUMBER OF REQ.-UNITS - INPUT / OUTPUT LEVEL ADJUSTMENT BUILDING BLOCKS FOR ET9 - POWER PART POWER...

 Open the catalog to page 4
Power line carrier equipment ET9-5

TEHNICAL DATA TECHNICAL DATA AF PART UNIVERSAL AF INTERFACE USEFUL BANDWIDTH TRANSIT FILTERS PROGRAMMABLE BAND PASS FIR FILTERS CONNECTION TYPE INPUT / OUTPUT LEVEL ADJUSTMENT CARRIER RACK OPTIONS ET9 INPUT / OUTPUT IMPEDANCE 4-w, SYMMETRICAL, GALVANIC ISOLATED CARRIER RACK FOR ET9 PLC EQUIPMENT UP TO 6 CHANNELS, OUTPUT POWER (PEP) UP TO 60 W CARRIER RACK FOR ET9 PLC EQUIPMENT UP TO 6 CHANNELS, OUTPUT POWER (PEP) UP TO 120 W UNIVERSAL TELEPHONE INTERFACE FXS 2-w SUBSCRIBER INTERFACE - RING FREQUENCY NUMBER OF REQ.-UNITS - INPUT / OUTPUT LEVEL ADJUSTMENT BUILDING BLOCKS FOR ET9 - POWER PART POWER...

 Open the catalog to page 5

All Iskra d.d. catalogs and technical brochures

  1. DZ9 Catalogue

    2  Pages

  2. eMis

    27  Pages

  3. Bistable switch

    26  Pages

  4. ECU

    2  Pages

  5. NEO 3000

    37  Pages

  6. FPC 200

    4  Pages

  7. NFIF

    4  Pages

  8. NFIB

    4  Pages

  9. FI, NFI

    2  Pages

  10. Product line

    20  Pages

  11. MCE940 SCADA

    4  Pages

  12. Energy Sector

    52  Pages

  13. Energy meters

    44  Pages

  14. Low voltage pfc

    30  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.