Device Specifications:
  • Model: ITR700-002
  • Power Supply: 230V~ 50/60Hz
  • Current: 30 mA
  • Radio Frequency: 868.3MHz
  • Transmission Power: < 10dB
  • Transmission Range: ~100m in free field, ~30m indoors
  • Cable Length: < 10m
  • KNX Media: KNX RF 1.R
  • Temperature Accuracy: ±0.3 ºC between -10 ºC & +70 ºC
  • Protection Type: IP 20, Class II
  • Temperature Range: Operation (-5°C to 45°C), Storage (-15°C to 55°C)
  • Flammability: Non-flammable
  • Color: Light Grey
  • Dimensions: 46x46x11 mm (HxWxD)
  • Certification: KNX Certified
  • Configuration: Configuration with ETS
Device Description:

The Interra ITR700-002 is a 4-input wireless KNX RF S-Mode universal interface. It supports analog or binary input and can control heating and cooling across four zones. It is suitable for installations without KNX bus cables, requiring a ITR750-002 KNX RF S-Mode media coupler for communication with the KNX Bus. The device detects input status changes and sends telegrams as configured in ETS. It also measures temperature and manages temperature alarms.

Layouts and Wirings:
  • The interface has 4 inputs, each configurable via ETS.
  • Supports various functions: Switch, Dimmer, Multiple Switch, Sequential Switch, Blind/Shutter Control, Scenes Management, Fixed/Forced value sending, Counter functionality.
  • Includes up to 4 independent thermostats for zone-specific heating/cooling control.
  • Features a programming button for setup.
  • Programming and commissioning require ETS5 or later.
Installation and Safety Notes:
  • Optimize radio signal range by selecting appropriate installation locations, avoiding interference sources like metallic surfaces and microwaves.
  • Maintain a minimum 2m separation between transmitter and receiver.
  • Suitable for indoor installations in dry rooms only.
  • Follow wiring diagrams for installation.
  • Supply the interface with 230V, use the programming key to load the physical address and application software.
See more

Catalog excerpts

ITR700-002 - KNX RF 4 CHANNEL UNIVERSAL INTERFACE-1

Interra ITR700-002 is a 4-input wireless KNX RF S-Mode universal The programming and commissioning must be done with ETS5 or later interface. The 4 channel which can be individually parameterized can be used as analog or binary input. It incorporates up to 4 independent UNIVERSAL INTERFACE Carry out the wiring according to wiring diagrams described in “layouts and Thermostats for the control of Heating and / or Cooling of 4 different zones. ITR700-002 is a perfect solution for using in conventional wirings” section. Fig. 1 : Connection to switch / pushbutton. Fig. 2 : Connection to temperature probe. media coupler. Interra ITR700-002 KNX RF 4 channel universal Fig. 3 : Connection to movement detector. interface detects the status changes at its inputs and send telegrams -> Supply the interface with 230V. The red LED goes on. according to ETS configuration. In addition, it also allows the measure- -> Press the Programming key (1). The green LED goes on. installations without placing KNX bus cables. Communication with the KNX Bus must be carried out using a ITR750-002 KNX RF S-Mode ment of the temperature and the management of temperature alarms. Device Power Supply Radio Frequency Transmission Power Transmission Range In free field: ~100m Indoors: ~ 30m -> Load the physical address and the application software into the actuator FUNCTIONS & CHARACTERISTICS • The Universal Interface incorporates 4 inputs, each of which can be parameterized individually through the ETS • Switch, Dimmer, Multiple Switch, Sequential Switch, Blind/Shutter Control, Scenes Management, Sending of a Fixed/Forced value, Counter functionality. • It also incorporates up to 4 independent Thermostats for the control of Heating and / or Cooling of 4 different zones. Cable Length • It has a programming button (1) to carry out its programming. • Programming and commissioning by ETS5 or later. Temperature Accuracy Temperature Range The range of the radio signal depends on various external states. The range can be optimized by the choice of installation location avoiding placing it close to any possible sources of interference, e.g. metallic surfaces, microwave ovens. Non-flammable Product Light Grey Avoid to install it close to radio electrical devices, microwaves,… Leave a minimum separation of 2m between the transmitter and SAFETY NOTES May be used for indoor installations in d

 Open the catalog to page 1

All Interra catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.