1. Catalogs
  2. Intarcon
  3. MSH / BSH series

MSH / BSH series

MSH / BSH series

MSH / BSH series

Product catalog summary
Overview: The document provides detailed technical specifications and features of the MSH/BSH series commercial split refrigeration units, designed for small and medium-sized cold rooms. These units are suitable for preserving refrigerated and frozen products and are available in various configurations to accommodate different installation needs.
Main Features:
  • Available in slim-type or cubic-type evaporating units.
  • Equipped with multifunction electronic control and digital remote keyboard.
  • Designed to operate in high ambient temperatures up to 45ºC.
  • Includes a thermostatic expansion valve and fast-freezing function.
  • Centrifugal versions available for ducted outlet of condenser’s hot air.
Technical Specifications:
  • Uses R404A refrigerant with hermetic reciprocating compressors.
  • Includes high and low-pressure switches, liquid receiver, and refrigerant preload for 15m piping.
  • Electric heater defrosting and stainless steel drain tray.
  • Flare-type cooling connections with service valves and 10 meters of electrical wiring included.
Installation Guidelines:
  • Maximum vertical distance between units is 15 meters if the condensing unit is higher than the evaporating unit, otherwise 6 meters.
  • Drain pipe requires a 20% minimum inclination in negative temperature series.
  • Optional crankcase heater recommended for outdoor installations.
Control and Operation:
  • Advanced XWING electronic control with multifunction digital keyboard.
  • Temperature control with recording of maximum and minimum values.
  • Fast-freezing function and night operation mode.
Power Supply and Wiring:
  • Standard power supply options: 230V - I - 50Hz and 400V - III - 50Hz.
  • Includes various wiring configurations for probes, valves, fans, defrosting, and optional components like door switch and cold room lamp.
Series Variants:
  • SH-NF Series: Axial condensing unit with slim-type evaporating unit.
  • SH-CF Series: Centrifugal condensing unit with slim-type evaporating unit.
  • SH-QF Series: Axial condensing unit with cubic-type evaporating unit.
  • SH-CQF Series: Centrifugal condensing unit with cubic-type evaporating unit.
Optional Features:
  • Change to 400 V-III-50 Hz power supply.
  • Crankcase heater and proportional control of condensation temperature.
  • Electronic fans in the evaporating unit.
Performance Data: The document includes detailed tables with performance data for various models, specifying cooling capacities, power consumption, air flow rates, and sound pressure levels at different temperatures.
Technical Document Summary
1. Dimensions
The document provides dimensions for various condensing and evaporating units. Key measurements are given in millimeters for different series and models, including the 3000 and 4000 series, as well as specific models like MSH-CQF-4068 and BSH-CQF-4136. The dimensions include parameters such as A, B, C, D, E, F, G, and H, with specific fan sizes noted.
2. Series/Model Specifications
The document outlines specifications for different series and models, focusing on compressor types, cooling capacities at various temperatures, nominal power consumption, maximum absorbed current, and airflow rates for both evaporating and condensing units. It also includes details on available static pressure, weight, and sound pressure levels (SPL) in dB(A).
3. Positive Temperature Range
Models such as MSH-CQF-3034 to MSH-CQF-4068 are detailed with their cooling capacities at temperatures ranging from -5 ºC to 10 ºC. The document provides information on power supply, power consumption, airflow, and other technical parameters.
4. Negative Temperature Range
Models like BSH-CQF-3074 to BSH-CQF-4136 are specified for cooling capacities at temperatures from -25 ºC to -15 ºC. Similar technical details are provided, including power supply, power consumption, and airflow rates.
5. Electrical Connection
The document includes a section on electrical connections, although specific details are not provided in the text excerpt.
See more

Catalog excerpts

MSH / BSH series-1

commercial split units technology in refrigeration MSH / BSH series Commercial split units Split refrigeration units for small and medium size cold rooms for preservation of refrigerated and frozen products. Featuring a slim-type or a cubic-type evaporating unit and multifunction electronic control with digital remote keyboard and digital condensing temperature control. intarsplit Split units consisting of a condensing unit in vertical or horizontal construction, with axial or centrifugal fans, and a slim-type or cubic-type evaporating unit. Tropicalised design for high ambient temperature up to 45ºC. Thermostatic expansion valve. Fast-freezing function. Centrifugal versions for a ducted outlet of condenser’s hot air. 9 15

 Open the catalog to page 1
MSH / BSH series-2

commercial split units technology in refrigeration intarsplit Tropicalised design for high ambient temperature up to 45ºC. Thermostatic expansion valve. Fast-freezing function. Description Features Split units for small and medium size cold rooms at positive and negative temperature, compossed by a condensing unit in horizontal or vertical construction and a slim-type or cubic-type evaporating unit. Electronic control intarsplit units feature an advanced XWING electronic control as standard. • R404A refrigerant. • Hermetic reciprocoating compressor (with noise insulation in 3-phases models)....

 Open the catalog to page 2
MSH / BSH series-6

centrifugal split units technology in refrigeration MSH-CQF / BSH-CQF series Split units, featuring a centrifugal condensing unit and a cubic-type evaporating unit, designed for preservation of generic products in medium size cold rooms at positive and negative temperature. Centrifugal version SH-CQF series The centrifugal condensing units are designed to be installed indoors with a duct to extract the condenser’s hot air. Technical features 50Hz, R404A Compressor Series / Model Cooling capacity (kW) / rated room size at 35 ºC ambient temperature -5 ºC m Nominal power consump. (kW) Max absorb....

 Open the catalog to page 6
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.