1. Catalogs
  2. Intarcon
  3. Intarsplit axial

Intarsplit axial

Intarsplit axial

Intarsplit axial

Product catalog summary
Overview
Split refrigeration systems are designed for small and medium-sized cold rooms, suitable for both refrigerated and frozen products. These systems consist of a low noise condensing unit for outdoor installation and a slim-type or cubic-type evaporating unit. They are known for their triple acoustic insulation, making them among the quietest on the market. The tropicalised design allows them to operate under extreme ambient conditions, withstanding temperatures up to 50ºC.
Technical Specifications
  • Power Supply: 230V-I-50Hz or 400V-III-50Hz.
  • Refrigerant: R-134A or R-404A, with a load below 10 kg.
  • Compressor: Hermetic reciprocating compressor with noise insulation in 3-phase models.
  • Control: Multifunction electronic control with a digital remote keyboard and digital condensing temperature control.
  • Design: Tropicalised for high ambient temperatures, thermostatic expansion valve, and centrifugal version for ducted outlet of condenser hot air.
Features
  • Factory-tested systems with no need for on-site testing.
  • Refrigerant preload for 15 m piping.
  • Electrical heater defrosting and stainless steel drain tray.
  • Flare-type cooling connections with service valves.
  • Magnetothermal protection for motors.
Installation Guidelines
  • Maximum vertical distance between units: 15 meters if the condensing unit is higher than the evaporating unit, otherwise 6 meters.
  • Minimum inclination of draining pipe for negative temperature series: 20%.
Optional Features
  • R-407A refrigerant.
  • Crankcase heater for outdoor installations.
  • Proportional control of condensing temperature for low ambient temperature operation.
Series and Models
  • Series MSH / BSH / ASH / MSF / BSF / ASF: Various models available with different cooling capacities and configurations, including axial and centrifugal versions.
Dimensions and Capacities
  • Detailed dimensions and capacities are provided for both evaporators and condensers across different series.
  • Cooling capacities are specified for various cold room temperatures and ambient conditions.
See more

Catalog excerpts

Intarsplit axial-1

Commercial split systems 77 Refrigerant load below 10 kg. 77 R-134A or R-404A refrigerant. 77 Systems tested at factory with no need for test on site. Split refrigeration systems for small and medium size cold rooms for preservation of refrigerated and frozen products. Featuring a slim-type or a cubic-type evaporating unit and multifunction electronic control with digital remote keyboard and digital condensing temperature control. intarsplit Split systems consisting of a condensing unit in vertical or horizontal construction, with axial or centrifugal motorfans, and a slim-type or cubic-type evaporating unit. 77 Tropicalised design for ambient temperature up to 45 ºC. 77 Thermostatic expansion valve. 77 Centrifugal version for a ducted outlet of condenser hot air. Split systems consisting of a low noise condensing unit for outdoor installation and a slim-type or cubic-type evaporating unit. Thanks to their triple acoustic insulation Sigilus units are among the most silent units in the market, and thanks to their tropicalised design they are really suitable to operate under extreme ambient conditions. 77 Tropicalised design for high ambient temperature up to 50ºC. 77 Low noise condensing units with low speed fans. 77 Thermostatic expansion valve.

 Open the catalog to page 1
Intarsplit axial-2

innovative refrigeration solutions intarsplit 77 Systems tested at factory with no need for test on site. 77 Tropicalised design for ambient temperature up to 45 ºC. 77 Thermostatic expansion valve. 77 Refrigerant preloaded. Technical features Split systems for small and medium size cold rooms at positive and negative temperature, compossed by a condensing unit in horizontal construction and a slim-type or cubic-type evaporating unit. Control pad intarsplit units feature an advanced XWING electronic control as standard. • 230V-I-50Hz or 400V-III-50Hz power supply. • Reduced R-134A or R-404A refrigerant...

 Open the catalog to page 2
Intarsplit axial-3

axial and centrifugal split systems series MSH / BSH Positive temperature Axial Series / Model Cooling capacity / Cold room volume, according to cold room temp. (1) Axial version Power supply Nominal Max. Evap. Cond. absorbed absorb. air flow air flow power Intensity (m3/h) (m3/h) (kW) (A) Centrifugal version Sound pressure level dB(A) (2) Centrifugal Series / Model Sound pressure level dB(A) (2) Centrifugal Series / Model Negative temperature Axial Series / Model Cooling capacity / Cold room volume, according to cold room temp. (1) Axial version Power supply Nominal Max. Evap. Cond. absorbed...

 Open the catalog to page 3
Intarsplit axial-4

innovative refrigeration solutions series MSH / BSH Positive temperature Axial version Axial Series / Model Cooling capacity / Cold room volume, according to cold room temp. (1) Power supply Centrifugal version Sound pressure level dB(A) (2) Centrifugal Series / Model Nominal Max. absorbed absorb. power Intensity (kW) (A) Sound pressure level dB(A) (2) Centrifugal Series / Model Negative temperature Axial version Axial Series / Model Cooling capacity / Cold room volume, according to cold room temp. (1) Power supply Nominal Max. absorbed absorb. power Intensity (kW) (A) Centrifugal version • R-407A...

 Open the catalog to page 4
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.