Product catalog summary
Abstract
The document describes a low-power passive voltage and current sensor designed for indoor applications, particularly for power/distribution transformers and separable connectors type A. The voltage sensor operates on a capacitive or resistive divider principle, while the current sensor uses a Rogowski coil. These sensors comply with the IEC 61869-11 standard and do not require an external power supply. They are easy to install and maintain accuracy throughout their lifetime, offering RJ45 type connections with various cable lengths.
Voltage Sensor Principle
The voltage sensor operates based on the IEC 61869-11 standard, using either a resistive or capacitive divider to transform high voltage input (Uin) to a normed output voltage (Uout). The transformation relationship is tailored to specific needs, ensuring linearity in response according to IEC 61689-11:2017 standards. Graphs illustrate amplitude and phase errors, advising the use of appropriate sensors for higher voltage limits.
Installation Procedures
For power/distribution transformers, the installation involves removing and cleaning the bushing interface, applying lubricant, and securing the sensor with installation accessories. A torque wrench is required for tightening. Ground cables must be connected, and the sensor signal is read using an RJ45 cable with a measuring instrument impedance of ≥20kΩ. For separable connectors, the procedure involves similar steps of cleaning, lubricating, and reinstalling the bushing.
Technical Characteristics
The sensors have specific rated parameters, including a primary voltage of 20/√3 kV, insulation levels of 24/50/125 kV, and a transformation ratio of 10000:1. They are tested for accuracy class 1%/3P and withstand various electrical tests, including power-frequency and lightning impulse tests. The sensors are compliant with multiple IEC standards, ensuring reliability and performance.
See more

Catalog excerpts

Interface - Low power passive voltage and current sensor 24kV-250A-1

LOW-POWER PASSIVE VOLTAGE AND CURRENT SENSOR 24kV-250A. INTERFACE A The Voltage sensor is produced on the basis of capacitive or resistive divider, according to the IEC 61869-11 standard. The current sensor consists of the operating principle of a Rogowski coil. This equipment is totally passive, without the need of power supply. Applicable for power/distribution transformers, and separable connectors type A. The sensors offer alternatives for monitoring and protecting network. Indoor application The sensors provide a RJ45 type connection with the corresponding cable (1m, 2m, 5m, 10m). Easy utilization and installation. Accuracy over complete lifetime INDISOL . Rua de Pardilhó 7 . 3860-529 Estarreja . Portugal . T +351 234 844 494 . [email protected] . ww

 Open the catalog to page 1
Interface - Low power passive voltage and current sensor 24kV-250A-2

LOW-POWER PASSIVE VOLTAGE AND CURRENT SENSOR 24kV-250A. INTERFACE A VOLTAGE SENSOR PRINCIPLE The basic principle of sensors, with diferente accuracy and transformation classes, is based on the IEC 61869-11 standard The sensors are based, according to customer preference, on the resistive or capacitive divider. The sensor has two elements that divide the input signal in a normed output value. The transformation relationship between the high voltage (pݑ Ȱݑְݑ ) and output voltage (۰ݑ Ȱݑܰݑ°ݑ ) is developed according to the needs. VOLTAGE SENSOR LINEARITY Amplitude error [%] according to table 6A.4...

 Open the catalog to page 2
Interface - Low power passive voltage and current sensor 24kV-250A-3

LOW-POWER PASSIVE VOLTAGE AND CURRENT SENSOR 24kV-250A. INTERFACE A RATED PARAMETERS Each sensor is identified with rating plate, where it is possible to see the different characteristics of the sensor. Among the characteristics, we can find, for example, the sensor accuracy class, operating temperature, transformation ratio and measurement impedance. To obtain the mentioned accuracy class, it is important to respect the measurement impedance as well as not to exceed the sensor operating voltage. Voltage sensor In the example on the right, we have an example for 24kV (voltage sensor) and 250A...

 Open the catalog to page 3
Interface - Low power passive voltage and current sensor 24kV-250A-4

LOW-POWER PASSIVE VOLTAGE AND CURRENT SENSOR 24kV-250A. INTERFACE A Apply lubricant inside the sensor and then the rubber (3). • Connect the sensor with the bushing interface. Secure the sensor using the installation accessories (4). To install the sensor, a torque wrench, metric 10, is required. • Tighten the 4 accessories with a torque of 25Nm. • After installing, it is important to apply a lubricant to the sensor connection surface (5). • After applying the lubricant, assemble the bushing. • At the end of assembly, it is important to connect the ground cables. On the side of the sensor, we...

 Open the catalog to page 4
Interface - Low power passive voltage and current sensor 24kV-250A-5

LOW-POWER PASSIVE VOLTAGE AND CURRENT SENSOR 24kV-250A. INTERFACE A -Separable conector (Interface A). 24kV – 250A A second possible application for this sensor is the possibility of using it in a Separable conector. Step 1 – Remove the bushing from the connector. Step 2 – After cleaning the sensor and applying the lubricant, install the sensor on the connector. 1 Step 3 – In the end, the bushing is installed again. INDISOL . Rua de Pardilhó 7 . 3860-529 Estarreja . Portugal . T +351 234 844 494 . [email protected] . www.indi

 Open the catalog to page 5
Interface - Low power passive voltage and current sensor 24kV-250A-6

LOW-POWER PASSIVE VOLTAGE AND CURRENT SENSOR 24kV-250A. INTERFACE A TECHNICAL CHARACTERISTICS Current sensor Voltage sensor Rated primary voltage Rated primary current Insulation Level Rated transformation ratio Rated transformation ratio Accuracy class Short time thermal current Rated voltage factor Test type Accuracy class Rated frequency Rated burden Rated burden Lightning impulse test Test type Power-Frequency Withstand Voltage, 1min Partial discharges Note: No power frequency withstand test on secundary terminal is allowed INDISOL . Rua de Pardilhó 7 . 3860-529 Estarreja . Portugal . T +351...

 Open the catalog to page 6