Catalog excerpts
iRTUe Versatile and modular I/O extensions transforming any master unit into an Highlights • IEC 61850 GOOSE communication with a processing time under 3ms • Flexible configuration of two I/O cards per unit with digital & analog inputs and relays • Sate-of-the-art technology for advanced automation functionalities like load shedding • Serial (EXP422) or double Ethernet port (copper or fiber) to connect to iRTUs/iGWs or any other third party master unit • Modbus TCP via Ethernet or Modbus RTU via serial to communicate with older substation IEDs iRTUe units communicate with Modbus TCP/RTU and IEC 61850 GOOSE, allowing to extend and distribute the acquisition and command capabilities of any master device. We offer flexible I/O board configurations to fulfill any application requirement, making the iRTUe the perfect choice to both set-up and retrofit electrical communication networks. Contemporary substation automation calls for advanced I/O modules to provide modern services such as interlocking or load shedding. These functionalities rely on state-of-the-art characteristics, which cannot be realised with serial communication media and old protocols. For this reason, the iRTUe handles IEC 61850 GOOSE messaging (with a processing time under 3ms) for newer projects but also Modbus with events buffer and timestamping for older substations/ master units. They connect via double Ethernet (RJ45, ST or SC) or serial (EXP422) port and are synchronized with IEEE 1588 (PTP) to ensure optimal time accuracy. This allows the iRTUe to communicate with any other equipment in the network: for instance RTUs, gateways, other iRTUe modules and third-party IEDs on the substation proce
Open the catalog to page 1GOOSE communication works with enhanced retransmission mechanisms on a publisher/subscriber basis, allowing P2P communication between iRTUe and IEDs with a processing time under 3ms (performance class P2). Since these systems are based on software configurations rather than hardwired signal paths, they are more costeffective, easily extendable and on demand reconfigurable, making them highly adaptive to changing substation configurations and network topologies. IEC 61850 GOOSE also features strong VLAN and priority tagging functionalities via IEEE 802.1Q to send messages efficiently across...
Open the catalog to page 2iRTUe Configurations The iRTUe can be ordered in 8 different configurations • iRTUe#D1D1: 48 Digital Inputs • iRTUe#D1R1: 24 Digital Inputs + 8 Relay Outputs • iRTUe#D1A1: 24 Digital Inputs + 8 Analog Inputs • iRTUe#R1A1: 24 Digital Inputs + 8 Analog Inputs • RTU#Q1 • 3 voltage inputs at 110Vac through four pin 5.08mm terminal block connectors • 3 current inputs for 1A current transformers, via 6 pin 5.08mm terminal block connectors • iRTU#Q2 • 3 combined inputs using an RJ45 connector, for passive smart sensors based on IEC 60044-7/8 Other configurations upon request Substation Gateway...
Open the catalog to page 3General Characteristics Communication Features Serial (1) RS-422 port to connect to iRTU&iGW devices with ModbusRTU Ethernet (2) 10/100BaseTX ports, RJ45 or FX100 fiber optics with ST or SC connectors Time Synchronization IEEE 1588 (PTP-Precise Time Protocol) client Power supply W : wide range, 32 - 250Vdc / 80 - 250Vac MTBF 177,000h (one hundred seventy seven thousand hours) Environmental Operating temperature : -25ºC to +70ºC Protocols IEC 61850 GOOSE messaging or Modbus TCP/RTU IEC 61850 Logical Nodes GGIO predefined (future firmware upgrades will allow any SCL file) Time response under...
Open the catalog to page 4All IGrid T&D catalogs and technical brochures
-
iGW
4 Pages
-
iGW-VM
4 Pages
-
iGWlite
4 Pages
-
iControl SCADA
4 Pages
-
iRTU
4 Pages