Catalog excerpts
protocol conversion. Highlights • From meter data concentration to protocol conversion – full range of protocols (DNP3.0, IEC 61850 (MMS & GOOSE), DLMS, Modbus, IEC 60870-5-101/102/103/104 etc.) to communicate with all devices and control centers involved in any kind of substation or generation plant IEC 61850 compliant • Adaptable and modular communication units suitable for all energy environments • Internal switch with RSTP/ PRP/ HSR redundancy • Up to 4 Ethernet ports, 4 serial ports, and optional, internal 4G, 3G and GPRS modems Overview This gateway was designed to provide particularly strong protocol conversion, network redundancy and SCADA automation (incl. IEC 61850) functionalities. It is thus the perfect choice to set up, automize or retrofit generation plants, substations and other control networks requiring data conversion between several protocols, as for instance Modbus to Ethernet or IEC 61850 to DNP3. The data collection from meters, protection relays, and other IEDs can be performed using any protocol, inlcuding IEC 60870-5, IEC 61850 (MMS/GOOSE), DNP3, DLMS, Modbus or Procome, whilst managing a microseconds timestamp resolution via NTP or PTP. Further, the iGW can also process and transfer the data to one or multiple control centers or SCADA master stations using upstream protocols such as IEC 104, IEC 101, TASE2.0/ ICCP (IEC 60870-6), IEC 61850-90-2, DNP3, and Modbus RTU/TCP. An architecture based on iGWs is open, efficient and scalable, as it allows to integrate coming generations of devices (IEDs, sensors, routers etc.) and adapt to any kind of network changes, saving you lots of time and
Open the catalog to page 1Communication Ports Communication Protocols The iGW comes with 2 independent 10/100 BaseTX Ethernet ports (two different MAC addresses, RJ45 connector) and an internal Ethernet switch with (2) 10/100BaseTX, (2) fiber optic FX100 sensors with ST, SC o SFP connectors, and RSTP/PRP/ HSR redundancy. The iGW was designed to use a high number of protocols and communicate with several control centers at once. Additionally, the iGW carries 4 software configurable serial ports: 1 full RS-232/RS-485/RS-422 + 2 basic RS-232/RS485/RS-422 and 1 RS-422/RS-485 port (EXP422) to connect iRTUe models....
Open the catalog to page 2iGW B0 Series (4) Software configurable serial ports with LEDs: (1) Full RS-232/ RS-422/ RS-485 serial port (2) Basic RS-232/ RS-422/ RS-485 serial ports (1) RS-422/ RS-485 serial port (EXP-422 port) (2) 10/100BaseTX Ethernet ports (RJ45 connector) (1) USB port to connect peripheral devices (1) MGMT port (MiniUSB connector) for local maintenance iGW S Series The S Series carries the B0 ports and an embedded Ethernet switch (connected to one of the two independent Ethernet ports), which provides: SO - (3) 10/100BaseTX RJ connectors (2) FX100 ports with HSR/PRP redundancy and SC, ST or SFP...
Open the catalog to page 3Protocol Stack General Characteristics Master/Slave Modbus TCP/UDP and JBUS (master) Master/Slave ModbusRTU Master DLMS Master Spabus, Mlink, Procome Environmental Operating temperature: -25ºC to +70ºC IEC 60068-2-1, IEC 60068-2-2, IEC 60068-2-3, IEC 60068-2-14, IEC 60068-2-30, IEC 60068-2-38 SNMP Agent/Manager Vibration & shock test IEC 60068-2-6, IEC 60068-2-7 Physical External dimensions: 173 x 78.4 x 137 mm (HxWxD) IP30 enclosure with DIN Rail mounting Power supply W : wide range, 32 - 250Vdc / 80 - 250Vac (2.5kVrms isolation) 24 : 19.5-60Vdc (2.5kVrms isolation) MTBF 177,000h (one...
Open the catalog to page 4All IGrid T&D catalogs and technical brochures
-
iGW-VM
4 Pages
-
iRTUe
4 Pages
-
iGWlite
4 Pages
-
iControl SCADA
4 Pages
-
iRTU
4 Pages