Components for Power Factor Correction Application - 1

PQC Power Quality Components Components for Power Factor Correction Application

Open the catalog to page 1
Components for Power Factor Correction Application - 2

1. Filter Reactors Page

Open the catalog to page 2
Components for Power Factor Correction Application - 3

Filter reactors DIN VDE 0550/0532 for general applications Application Harmonics generated by non-linear loads such as variable speed drives or other static power conversion equipment have grown rapidly in recent years. Harmonic currents and the voltage distortion, created by these currents have devastating effects on power supply and distribution systems and its connected loads. This can result in failure of power factor correction capacitors due to overloading, system resonance, overheating of cables and transformers as well as misoperation of PLC’s, computer and other sensitive...

Open the catalog to page 3
Components for Power Factor Correction Application - 4

filter reactors DIN VDE 0550/0532 for general applications Technical Specification Rated voltage See selection list Loss See selection list Rated output See selection list Max. allowable operating current See selection list Max. allowable harmonic voltage See selection list Linear range L(1,2 2 I) > 0,95 LN Adjustment accuracy -2% ... +3% from LN Insulation level UN < 1100 V; 3/- kV (Line-to-line voltage) Temperature limits +35°C annual average Insulation class T40/H - Filter reactors with Al-winding Insulation class T40/F - Filter reactors with Cu-winding Cooling method Natural cooling...

Open the catalog to page 4
Components for Power Factor Correction Application - 5

FILTER REACToRS Selection table: Filter reactors for mains 400 V, 50 Hz Power Reactor L (mH) Winding Weight losses max. oper. current Capacitor kvar 3x ... AL/Cu kg 50 Hz r. m. s. 50 Hz 250 Hz 350 Hz type

Open the catalog to page 5
Components for Power Factor Correction Application - 6

FILTER REACToRS Selection table: Filter Reactors for mains 525V, 50Hz Power Reactor L (mH) Winding Weight losses (Watt) max. oper. current Capacitor kvar 3x ... AL/Cu kg 50 Hz r. m. s. 50 Hz 250 Hz 350 Hz type

Open the catalog to page 6
Components for Power Factor Correction Application - 7

FILTER REACTORS Dimensions Filter reactor with aluminum windings (Al)

Open the catalog to page 7
Components for Power Factor Correction Application - 8

Power Factor Controller BLR-CX Edition2 Reactive power compensation panels are used to reduce load in the electrical grid and to save costs. This is the reason, that there are special requirements for the control units of these compensation panels, the reactive power regulator. The most important task for the reactive power regulator is to control the reliable termination of reactive power. This is reducing the costs for electrical energy. Cables, transformers, switch components and power distribution are unloaded by reduce reactive power. Another task of the reactive power regulator is...

Open the catalog to page 8
Components for Power Factor Correction Application - 9

Power Factor Controller BLR-CM-R Microprocessor controlled power factor controller with 1-phase measurement system and display of measurement values ■ Full-automatic c/k-value setting, self adapting, connection of different capacitor step sizes possible ■ Automatic detection and usage of the optimum capacitor step ■ Manual mode possible ■ Multiple connection types possible through adjustable phase compensation angle ■ Capable for 4-quadrant operation ■ Individually configurable discharging time allows quicker switching time ■ 1-phase measurement system also suitable for non sinusoidal...

Open the catalog to page 9
Components for Power Factor Correction Application - 10

Power Factor Controller BLR-CM 3-phase Microprocessor controlled power factor controller with 3-phase measurement system and display of measurement values ■ Full-automatic c/k-value setting, self adapting, connection of different capacitor step sizes possible ■ Capacitor capacity is stored as a 3-phase value. Thereby 1-phase capacitors can be used. ■ Autoatic detection and usage of the optimum capacirot step for 3-phase power factor control. ■ Manual mode possible ■ Mutiple connection types possible throught adjustable phase compensation angle ■ Capable for 4-quadrant operation ■...

Open the catalog to page 10
Components for Power Factor Correction Application - 11

Power Factor Controller BLR-CM-T/RT for dynamic Power Factor Control Microprocessor controlled power factor controller with 1-phase measurement system and display of measurement values ■ Uses additional to the normal regulation algorithm an second “fast” algorithm ■ For every static output the step type can be chosen between “normal” or “fast” ■ Fast Steps ■ Response time <1 ms after one period measuring ■ To get an optimal compensation result in systems with rapid load changes the controller switches all needed steps by one switch cycle ■ The nomal step size is free adjustable for every...

Open the catalog to page 11
Components for Power Factor Correction Application - 12

Power Analyzer EMM-5 Multi-function power analyzer for acquisition and analysis of all parameters in 3-phase grids ■ 3-phase measurement with 3- or 4-wire connection ■ Operation and parameter input with 4 keys ■ User guidance with plain text menu ■ Measurement data displayed on loarge LCD display with backlight ■ Harmonics measurement up to the 63. harmonic for voltage and current ■ Connected to voltage transformers also suitable for higher voltages ■ Integration in networks possible via interface RS485 Modbus RTU (optional) ■ Flexible alarm system enables supervision of up to 32...

Open the catalog to page 12
Components for Power Factor Correction Application - 13

Voltage Control Relay VxR Multi-function device for voltage supervision of 3-phase systems ■ User guidance with plain text menu ■ Measurement data displayed on loarge LCD display with backlight ■ Harmonics measurement up to the 63. harmonic for voltage ■ Connected to voltage transformers also suitable for higher voltages ■ Integration in networks possible via interface RS485 Modbus RTU (optional) ■ Flexible alarm system enables supervision of up to 32 measurement values ■ Supply voltage 230 V, 45-65 Hz, other voltages on request ■ Voltage measuring 50-530 V, 45-65 Hz ■ Connection with...

Open the catalog to page 13
Components for Power Factor Correction Application - 14

Static Contactor BEL-TS Thyristor switch for rapid switching of capacitors in LV-grid ■ Switching without inrush current, smooth disconnecting ■ Rapid switching ■ Can be used in chocked capacitor banks and unchocked as well ■ Depending on the type for max. voltage 525 V or 690 V ■ Recovery time 20 ms ■ Voltage level trigger signal 8-30 V DC ■ Protection class IP00

Open the catalog to page 14
Components for Power Factor Correction Application - 15

Fuses with blade contacts Fuses with blade contacts Nožové pojistky PHN fuse-links with blade contacts and utilization category gG are suitable for applications with rated voltage 690 V a.c. They feature high breaking capacity, high current limiting capacity, low power losses and low values of overvoltage during fuse-link action. PHN fuse-links with blade contacts and utilization category gG are Fuse-links a.c. They feature suitable for applications with rated voltage 690 Vwith blade contacts PHN high breaking capacity, high current limiting capacity, low power In Size Type [A] losses and...

Open the catalog to page 15