1. Catalogs
  2. HW Ventilation
  3. Q sickle profile fixed pitched axial fans

Q sickle profile fixed pitched axial fans

Q sickle profile fixed pitched axial fans

Q sickle profile fixed pitched axial fans

Product catalog summary
Product Overview
Q impellers are designed with fixed pitch sickle profile blades and a light aluminum alloy hub, suitable for high-speed and low-noise applications. They are available in configurations with 6, 8, 10, or 14 blades, supporting both clockwise and anticlockwise rotations. The blades can be set at angles from 20° to 50°, allowing for either sucking or blowing air flow.

Applications
Q impellers are versatile and can be used in compressors, ventilators, radiators, generators, lift trucks, agricultural sprayers, farm ventilation, earth-moving machines, air conditioners, refrigeration units, and cooling towers.

Blade Materials
The impellers are available in various materials to accommodate different operational temperatures and environments:
  • PPG: Polypropylene Glass Reinforced, Orange, -20°C to +85°C
  • PAG: Polyamide Glass Reinforced, White, -40°C to +120°C
  • RYT: Ryton, Brown, -50°C to +200°C
  • PAA: Antistatic Polyamide, Black, -40°C to +120°C
  • PAX: Antistatic, Self-extinguishing PA, Black, -40°C to +120°C
  • PAM: Antistatic, Self-extinguishing, Magnetically shielded PA, Black, -40°C to +120°C
Custom colors are available upon request, and ATEX materials are suitable for hazardous environments.

Specifications and Dimensions
Q impellers are available in diameters ranging from 230 mm to 750 mm. The hub diameter and configurations vary based on the number of blades:
  • 6 blades: Hub Ø 96 mm, Min Ø 230 mm, Max Ø 602 mm
  • 8 blades: Hub Ø 134 mm, Min Ø 270 mm, Max Ø 640 mm
  • 10 blades: Hub Ø 172 mm, Min Ø 310 mm, Max Ø 680 mm
  • 14 blades: Hub Ø 242 mm, Min Ø 500 mm, Max Ø 750 mm
Dimensions vary by angle, with height (H) and width (I) increasing as the angle increases from 20° to 50°.

Performance and Energy Efficiency
Q impellers have been tested in an AMCA 210/07 wind tunnel and comply with the EU Directive 2015 on Energy Efficiency for axial fans. They are ErP2015 ready, ensuring high energy efficiency standards.

Contact Information
HW VENTILATION S.r.l., Viale dei Kennedy 81/83, 20027 Rescaldina (MI) – ITALY. Phone: +39 0331 1558 815, Fax: +39 0331 1225 767, Email: [email protected], Website: www.hwventilation.it
See more

Catalog excerpts

Q sickle profile fixed pitched axial fans-1

Fixed pitch sickle profile axial impellers, diameters from 230 mm to 750 mm PRODUCT FEATURES Q impellers are manufactured assembling fixed pitch sickle profile blades with a light aluminum alloy hub. The impellers are thought to be employed in applications that require the highest rotation speeds and low noise levels. The impellers are available in configurations with 6/8/10/14 blades both for clockwise and anticlockwise rotation. Q blades are available with right or left fixed setting angles ranging from 20° to 50°. Q impellers can produce a sucking or blowing air flow. • Farms ventilation • Earth moving machines • Refrigeration units • Lift trucks • Cooling Towers • Agricultural sprayers SERUTAEF TCUDORP BLADE MATERIALS Q are available in plastics, and ATEX materials to suit a variety of applications which require different temperatures and rotation speeds. DESCRIPTION Polypropylene Glass Reinforced (PP 30% glass) Polyamide Glass Reinforced (PA6) Ryton Antistatic Polyamide Antistatic, Self extinguishing PA Antistatic, Self extinguishing, Magnetically shielded PA Orange White Brown Black Black Black *Custom colors available upon request **ATEX materials for hazardous environments ***Contact technical dpt. for customized advise

 Open the catalog to page 1
Q sickle profile fixed pitched axial fans-2

SPECIFICATIONS AND DIMENSIONS SNOISNEMID DNA SNOITACIFICEPS Q impellers are configurable with 6/8/10/14 blades. Blades are available with right or left fixed setting angles ranging from 20° to 50°. ENERGY EFFICIENCY Our fans have been tested in AMCA 210/07 wind tunnel and comply with the requirements of EU Directive 2015 on Energy Efficiency for axial fans. For further info contact our technical department. PERFORMANCE DIAGRAMS HW VENTILATION S.r.l. Viale dei Kennedy 81/83 20027 Rescaldina (MI) – ITALY

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.