H.Stars Screw Type Chiller Heat Pump Unit
29Pages

{{requestButtons}}

Catalog excerpts

H.Stars Screw Type Chiller Heat Pump Unit - 1

H.Stars Screw Type Chiller/ Heat Pump Unit H.Stars (Guangzhou) Refrigerating Equipment Group Ltd.

Open the catalog to page 1
H.Stars Screw Type Chiller Heat Pump Unit - 2

Design Features and Performance H.Stars Screw Type Chiller/Heat Pump Unit H.Stars 40STD Screw Type Chiller unit has 4 series: Screw Type Water-cooled Chiller, Screw type Water Source Heat Pump Unit, Screw Type Air-cooled Chiller, Screw Type Air Source Heat Pump. Operation Reliable With the self-produce major components and independent intellectual property rights, the system is perfectly matched to enable COP up to 6.0. Optional H.Stars patented heat recovery unit , 30% to 100% of heat capacity can be recovered while chiller applicable for air-conditioning system. The highest temperature of...

Open the catalog to page 2
H.Stars Screw Type Chiller Heat Pump Unit - 3

Chiller Structure H.Stars Screw Type Chiller/Heat Pump Unit Water-cooled Chiller Standard Configuration Compressor Semi-hermetic twin screw compressors Self-produced high efficiency evaporator Self-produced high efficiency condenser Microcomputer controller Throttling device Thermostatic/electronic expansion valve Starting mode Delta Starter Power Supply Insulation Material Anti-corrosive waterproof mesh insulation Reinforced Shrink-wrap Covering ,industrialgrade High strength matte paint Water Pipe Connection Water-cooled screw type chiller adopts high efficient twin screw compressors...

Open the catalog to page 3
H.Stars Screw Type Chiller Heat Pump Unit - 4

Chiller Structure(continued) H.Stars Screw Type Chiller/Heat Pump Unit Air-cooled Chiller Standard Configuration Compressor Specialized air cooled compressor Self-produced high efficiency evaporator Self-produced high efficiency fin coil condenser Microcomputer controller Throttling device Thermostatic/electronic expansion valve Starting mode Delta Starter Power Supply Insulation Material Anti-corrosive waterproof mesh insulation Reinforced Shrink-wrap Covering ,industrialgrade High strength matte paint Water Pipe Connection Air-cooled screw type chiller adopt specialized air cooled...

Open the catalog to page 4
H.Stars Screw Type Chiller Heat Pump Unit - 5

Main components H.Stars Screw Type Chiller/Heat Pump Unit Screw Type Compressor Compressor adopt cast iron shell and forged steel rotor. It ensures a small space between two screws but without surface contact.The rotor support ensure accurate positioning while the rotor at various pressure ratios, reduce wear, prevent leakage, and extend life time. The compressor is designed with full wear resistance bearing, reduce energy consumption and improve reliability. Compressor motor adopts silicon steel core, motor cooling by-pass, refrigerant diversion design, which ensures the motor works at...

Open the catalog to page 5
H.Stars Screw Type Chiller Heat Pump Unit - 6

HMI (Human Machine Interface) Control Center H.Stars Screw Type Chiller/Heat Pump Unit Product features and functions Control center Adopts advanced and highly integrated controll system to greatly improve the anti-interference ability of the system The HMI directly displays the fault content, and cooperates with the simple operation interface to feedback various maintenance information to users with real-time display of three-phase voltage and current data. Integrated control system with protection real-time monitor and alarm combined together to fully protect the operation safety of the...

Open the catalog to page 6
H.Stars Screw Type Chiller Heat Pump Unit - 7

Standard Unit Performance Parameter Table H.Stars Screw Type Chiller/Heat Pump Unit HMI Display 10 inch / 8 inch true color touch screen to display more delicate and clear . Support USB flash disk to upgrade the system. Easy to operate and visually display dynamic operation information Multi language switches freely. True color display of control center greatly improves efficiency to monitor the chiller, record chiller data with security protection and convenient operation. Interface structure diagram Factory Setting 厂家设置 Program 程序自检 self-checking Maintenance 维修设置 setting Setting 设置界面...

Open the catalog to page 7
H.Stars Screw Type Chiller Heat Pump Unit - 8

Optional Parts H.Stars Screw Type Chiller/Heat Pump Unit Heat Recovery The condensing heat of the chiller (usually discharged into the atmosphere by the cooling tower) is recovered and used effectively. For example, a hotel needs to provide both heat (for hot water) and air conditing during the summer. With the heat recovery, the heat absorbed during cooling can be transferred to the building where hot water is needed by heat recovery. In the cooling season, hot water above 50 °C can be provided free by adopting the heat recovery unit. Heat recovery of up to cooling capacity 30% to 100%....

Open the catalog to page 8
H.Stars Screw Type Chiller Heat Pump Unit - 9

Optional (continued) H.Stars Screw Type Chiller/Heat Pump Unit Heat Exchanger Tube Condenser Heat Exchange Tube Condenser heat exchange tube specification Heat exchange tube material Copper Tube Copper tube Aluminum brass tube Nickel coppe tube Stainless tube Stainless Tube Tube thickness option 2 (mm) Tube thickness option 3 (mm) Tube thickness option 4 (mm) Suitable for water quality Standard noncorrosive neutral water Alkaline water Acid water Evaporator heat exchange tube specification Heat exchange tube material Copper Tube Nickel coppe tube Nickel Copper Tube Tube thickness option 1...

Open the catalog to page 9
H.Stars Screw Type Chiller Heat Pump Unit - 10

H.Stars Screw Type Chiller/Heat Pump Unit VFD (Variable Frequency Driver) technology VFD is to change the power supply frequency, thus adjusting the load, to reduce power consumption, reduce losses, and extend the life of the equipment. The core of VFD technology is the Variable-frequency Driver. Automatic adjustment of motor operating speed rate by conversion of power supply frequency to make the fixed grid of 50 Hz change to the frequency of of 30-130 Hz. At the same time, the power supply voltage adapts to the range of 142-270V, which solves the problem that the electrical equipment...

Open the catalog to page 10
H.Stars Screw Type Chiller Heat Pump Unit - 11

Standard Unit Parameter List / 50Hz H.Stars Screw Type Chiller/Heat Pump Unit Screw Type Water-cooled Chiller Technical Parameters Water Side Max. Pressure Mpa Water pressure drop KPa Inlet pipe diameter in Water Side Max. Pressure Mpa Water pressure drop KPa Inlet pipe diameter in Capacity control % Nominal cooling capacity Compressor Input Power KW Note: 1. Nominal cooling capacity reference: evaporator inlet and outlet water temperature 12℃ /7℃ , condenser inlet and outlet water temperature 30℃ / 35℃ ; fouling factor 0.018m².℃ / KW; 2. Chilled water temperature range: 5-20℃ 3. Cooling...

Open the catalog to page 11

All H.Stars (Guangzhou) Refrigerating Equipment Group Ltd. catalogs and technical brochures