H.Stars High Temperature Heat Pump - 1

H.Stars Group H.Stars High Temperature Heat Pump H.Stars (Guangzhou) Refrigerating Equipment Group Ltd.

Open the catalog to page 1
H.Stars High Temperature Heat Pump - 2

Company Profile H.Stars High Temperature Heat Pump H.Stars (Guangzhou) Refrigerating Equipment Group Co., Ltd., established in 1992 , is a foreigninvested enterprise, headquarter located in Economic and Technological Development Zone of Guangzhou, as an important member of H.Stars (HK) Group, has specialized in manufacturing of refrigerating air conditioning and industrial heating and cooling equipment. It has various special equipment design, techniques and manufacturing capabilities . H.Stars Group main products include refrigerating equipment, air conditioning equipment, industrial...

Open the catalog to page 2
H.Stars High Temperature Heat Pump - 3

High Temperature Heat Pump H.Stars High Temperature Heat Pump Air-source High Temperature Heat Pump ·Adopt air as heat source ·Water temperature outlet 55℃ ~90℃ ·Ambient temperature: -30℃ ~55℃ ·90℃ COP 2.3 ·Suitable for high temperature heating industry ·Optional VSD variable frequency inverter to improve energy efficiency ·Optional cold recovery system 5℃ ~30℃ frozen water Water Source High Temperature Heat Pump ·Use water source to produce 55℃ ~90℃ hot water ·Suitable for waste heat recovery and utilization、 ·Not limited by the ambient temperature, the inlet High temperature cycle...

Open the catalog to page 3
H.Stars High Temperature Heat Pump - 4

Variable working condition curve H.Stars High Temperature Heat Pump Ambient Temp. Air source heating correction factor Ambient Temp. Air source power correction factor Customized Design, Unique Equipment H.Stars Group / Superior HVAC Products Manufactured by H.Stars

Open the catalog to page 4
H.Stars High Temperature Heat Pump - 5

Variable working condition curve H.Stars High Temperature Heat Pump Water source outlet orrection coefficient for heating capacity of 80°C effluent water source Water source outlet Correction factor for power of outlet water source at 80°C H.Stars Group / Superior HVAC Products Manufactured by H.Stars Customized Design, Unique Equipment

Open the catalog to page 5
H.Stars High Temperature Heat Pump - 6

Variable working condition curve H.Stars High Temperature Heat Pump Water source outlet Correction coefficient for heating capacity of 90°C outlet water source Water source outlet Correction coefficient of 90°C outlet water source power Customized Design, Unique Equipment H.Stars Group / Superior HVAC Products Manufactured by H.Stars

Open the catalog to page 6
H.Stars High Temperature Heat Pump - 7

Standard model parameter table H.Stars High Temperature Heat Pump Technical parameters of air source high temperature heat pump Refrigerant:R134a Water Side MAX Pressure MPa Condenser water pressure drop kPa Energy control % Cooling wate flow m3/h Condenser inlet and outlet pipe diameter in Nominal heating capacity Note: 1. Nominal working conditions: air dry/wet bulb temperature 20℃ /15℃ , hot water inlet/outlet temperature 83℃ /88℃ ; fouling coefficient 0.018 ㎡ ·℃ /kW; 2. Ambient temperature range: 5℃ ~43℃ , please contact the manufacturer when the ambient temperature is lower than 5℃ ;...

Open the catalog to page 7
H.Stars High Temperature Heat Pump - 8

Standard model parameter table H.Stars High Temperature Heat Pump Technical parameters of air source high temperature heat pump Power Supply:3φ-380V-50Hz Condenser inlet and outlet pipe diameter in Cooling wate flow m3/h Water Side MAX Pressure MPa Condenser water pressure drop kPa Energy control % Nominal heating capacity Note: 1. Nominal working conditions: air dry/wet bulb temperature 20℃ /15℃ , hot water inlet/outlet temperature 83℃ /88℃ ; fouling coefficient 0.018 ㎡ ·℃ /kW; 2. Ambient temperature range: 5℃ ~43℃ , please contact the manufacturer when the ambient temperature is lower...

Open the catalog to page 8
H.Stars High Temperature Heat Pump - 9

Standard model parameter table H.Stars High Temperature Heat Pump Technical parameters of water source high temperature heat pump (80 ℃ ) Refrigerant:R134a Water Side MAX Pressure MPa Water pressure drop kPa Water Side MAX Pressure MPa Water pressure drop kPa Energy control % Nominal heating capacity Note: 1. Nominal heating capacity standard: heat source water inlet and outlet temperature 35°C/30°C, hot water inlet and outlet temperature 75°C/80°C; fouling coefficient 0.018 ㎡ ·°C/kW; 2. The minimum outlet temperature of heat source water is 15℃ ; 3. The maximum outlet temperature of hot...

Open the catalog to page 9
H.Stars High Temperature Heat Pump - 10

Standard model parameter table H.Stars High Temperature Heat Pump Technical parameters of water source high temperature heat pump (80 ℃ ) Refrigerant:R1234ze Water Side MAX Pressure MPa Water pressure drop kPa Water Side MAX Pressure MPa Water pressure drop kPa Energy control % Nominal heating capacity Note: 1. Nominal heating capacity standard: heat source water inlet and outlet temperature 35°C/30°C, hot water inlet and outlet temperature 75°C/80°C; fouling coefficient 0.018 ㎡ ·°C/kW; 2. The minimum outlet temperature of heat source water is 15℃ ; 3. The maximum outlet temperature of hot...

Open the catalog to page 10
H.Stars High Temperature Heat Pump - 11

Standard model parameter table H.Stars High Temperature Heat Pump Technical parameters of water source high temperature heat pump (90 ℃ ) Power Supply:3φ-380V-50Hz Water Side MAX Pressure MPa Water pressure drop kPa Water Side MAX Pressure MPa Water pressure drop kPa Nominal heating capacity Energy control % Note: 1. Nominal heating capacity standard: heat source water inlet and outlet temperature 12°C/7°C, hot water inlet and outlet temperature 83°C/88°C; fouling coefficient 0.018 ㎡ ·°C/kW; 2. The minimum outlet temperature of heat source water is 5℃ ; 3. The maximum outlet temperature of...

Open the catalog to page 11
H.Stars High Temperature Heat Pump - 12

Standard model parameter table H.Stars High Temperature Heat Pump Technical parameters of water source high temperature heat pump (90 ℃ ) Power Supply:3φ-380V-50Hz Water pressure drop kPa Water Side MAX Pressure MPa Water pressure drop kPa Water Side MAX Pressure MPa Condenser Refrigerant charge kg Nominal heating capacity Energy control % Note: 1. Nominal heating capacity standard: heat source water inlet and outlet temperature 12°C/7°C, hot water inlet and outlet temperature 83°C/88°C; fouling coefficient 0.018 ㎡ ·°C/kW; 2. The minimum outlet temperature of heat source water is 5℃ ; 3....

Open the catalog to page 12