SmartBlock

SmartBlock

SmartBlock

Product catalog summary
Overview: The document provides detailed information about the SmartBlock I/O modules by Horner Automation, designed to expand the I/O capacity of OCS All-In-One Controllers using CsCAN communications. It highlights the ease of configuration and network expansion capabilities.
Specifications:
  • Bus Protocol: CsCAN
  • Bus Connector: Dual 5-pin Removable Terminal
  • Maximum Distance: 1500 meters
  • Maximum Number of Nodes: 253
  • Power Range: 10-30 VDC
  • Operating Temperature: 0°C to +60°C
  • Storage Temperature: -10°C to +60°C
  • Relative Humidity: 5% to 95%, non-condensing
  • Module ID Configuration: Dual Rotary Switches
Features:
  • Isolated and highly accurate analog modules with 16-bit resolution.
  • RTD & THM Analog models offer 0.5°C accuracy with 0.1°C resolution.
  • Wide variety of analog, digital, and mixed input/output options.
  • Easy-to-read, separate I/O connectors with LED indicator lights.
  • DIN-rail mountable in fully enclosed plastic housing.
Product Range: The document lists various SmartBlock models, including isolated mixed digital/analog I/O modules, RTD input modules, thermocouple input modules, and analog input/output modules. It also includes part numbers for standard and open frame models.
Applications: SmartBlock is suitable for applications requiring precise, accurate data, noise immunity, and data integrity.
See more

Catalog excerpts

SmartBlock-1

SmartBlock Easy & cost-effective way to add advanced I/O SmartBlock expands the I/O capacity of OCS All-In-One Controllers. Using CsCAN communications, SmartBlock I/O provides easy configuration and network expanison. Wide variety of analog, digital and mixed input/output options Easy-to-read, seperate I/O connectors LED indicator lights for each I/O point, power and network status Include a 5-pin double CsCAN plug and Removable Field Wiring Terminals DIN-rail mountable, in fully enclosed plastic housing Easy to Configure & Expand SmartBlock is designed to complement the extremely popular SmartStix Digital I/O family. These two I/O families can be used to expand the I/O capacity of just about any OCS by merely a few points - or potentially few thousand. Additionally, SmartBlock is easily configured using the Horner Cscape software and can be quickly implemented into an existing or new OCS controller. Isolated & Highly Accurate Analog The SmartBlock modules can be fully isolated and are highly accurate with 16-bit resolutions on most models. RTD & THM Analog models offer a .5°C accuracy margin with a 0.1°C resolution making SmartBlock a perfect match for applications that need precise, accurate data, noise immunity, and data integrity. CsCAN supports up to 253 nodes with a maximum network distance of 1500 meters. 59 South State Ave., Indianapolis, IN 46201 | (p) 317.916.4274 (tf) 877.665.5666 (f) 317.639.4279 | www.hornerautomation.com Please visit our website for a complete listing and to learn more about certified Horner Automation products.

 Open the catalog to page 1
SmartBlock-2

HORNERAUTOMATION GROUP SmartBlock General Specifications Item SmartBlock Model Numbers Part Number SmartBlock Standard Isolated Mixed Digital/Analog I/O Module (12/6/4) Isolated RTD Input Module, 4 channel Isolated RTD Input Module, 8 channel Isolated Thermocouple Input Module, 4 channel Isolated Thermocouple Input Module, 8 channel 4 Analog Inputs, 2 Analog Outputs (0-10V, 0 -5V, 0-20mA, 4-20mA) 8 DC inputs and 8 relay outputs 8 DC inputs and 8 -.5 amp DC outputs Isolated Mixed Digital/Analog I/O Module (12/12/2/2) AC Power Monitor (3-phase) AC Power Monitor (3-Phase) using Rogowski coil inputs...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.