1. Catalogs
  2. Honeywell Thermal Solutions
  3. Butterfly valves BVG, BVA, BVH

Butterfly valves BVG, BVA, BVH

Butterfly valves BVG, BVA, BVH

Butterfly valves BVG, BVA, BVH

Product catalog summary
Overview: This document is a product brochure for Kromschroeder's butterfly valves, specifically models BVG, BVGF, BVA, BVAF, BVH, BVHS, and BVHM. These valves are designed for controlling gas, air, hot air, and flue gas with high accuracy and low leakage.
Specifications:
  • Gas Types: BVG and BVGF are suitable for natural gas, town gas, LPG, and other non-aggressive gases. BVGF can also handle biologically produced methane. BVA and BVAF are designed for air.
  • Materials: Housing is made of AlSi, valve disc of aluminum, and drive shaft of stainless steel for BVG, BVGF, BVA, and BVAF. BVH, BVHM, and BVHS use GGG for housing and stainless steel for valve disc and drive shaft.
  • Temperature Range: Medium temperature ranges from -20 to +60°C for BVG, BVGF, BVA, and BVAF, and up to +450°C for BVH, BVHM, and BVHS.
  • Pressure: Maximum inlet pressure is 500 mbar for BVG and BVGF, and 150 mbar for BVH, BVHM, and BVHS.
Applications:
  • BVG and BVA: Used for adjusting gas and air volumes in combustion processes, with options for manual adjustment to set flow rates.
  • BVGF and BVAF: Provide clearance-free operation and quick adjustment to setpoints.
  • BVH: Suitable for precise flow rate adjustments and low leakage in high-temperature applications.
  • BVHS: Features a safety closing function to prevent uncontrolled air entry during power failures.
  • BVHM: Designed for intermittent operation with a high number of cycles, featuring low leakage rates.
Technical Features:
  • Butterfly valves can be mounted directly onto actuators IC 20 or IC 40.
  • Available in nominal diameters from DN 40 to 150, with options for reduced diameters.
  • Certified and approved for various standards, including EC type-testing and FM approval.
Contact Information: For further details, contact Elster GmbH in Germany via phone or email, or visit their website.
See more

Catalog excerpts

Butterfly valves BVG, BVA, BVH-1

Butterfly valves BVG, BVGF, BVA, BVAF, BVH, BVHS, BVHM Product brochure · GB 3 Edition 01.12 • • • • • • • • • • • For gas, air, hot air and flue gas Low leakage rate and pressure loss High control accuracy BVG and BVA with reduced nominal diameters Butterfly valve can be mounted directly onto the actuator IC 20 or IC 40 Suitable for intermittent operation BVGF, BVAF work clearance-free Low-maintenance operation BVG: EC type-tested and certified BVHM: FM approved BVG: certified pursuant to GOST-TR www.kromschroeder.com

 Open the catalog to page 1
Butterfly valves BVG, BVA, BVH-2

2 · BVG, BVGF, BVA, BVAF, BVH, BVHS, BVHM · Edition 01.12 BVG for gas, BVA for air. These butterfly valves can be fitted with an adapter set with square shaft, free shaft end or manual adjustment, for instance. BVG, BVA Application The butterfly valves are designed to adjust volumes of gas, cold and hot air and flue gas on various appliances and flue gas lines. They are designed for control ratios up to 1:10, and with the mounted actuator IC 20 or IC 40 they are suitable for regulating flow rates for modulating or stage-controlled combustion processes. BVG, BVA Using the adapter set with manual...

 Open the catalog to page 2
Butterfly valves BVG, BVA, BVH-3

BVG, BVGF, BVA, BVAF, BVH, BVHS, BVHM · Edition 01.12 · 3 Example of applications IC 20 + BVG VAG M BVG, BVGF, lambda correction If the burner is to be operated with excess gas or air for reasons of the process operation, the butterfly valve BVG, BVGF can be used to correct the lambda value. The butterfly valve with manual adjustment is used to adjust the high-fire rate. IC 20 + BVA BVA M BVA, BVAF, adjusting the burner capacity In pneumatic systems, the butterfly valve with mounted actuator IC 20..E determines the air volume for the required burner capacity. VAG The butterfly valve with manual...

 Open the catalog to page 3
Butterfly valves BVG, BVA, BVH-4

4 • BVG, BVGF, BVA, BVAF, BVH, BVHS, BVHAA • Edition 01.12 Technical data BVG, BVGF: natural gas, town gas, LPG and other non-aggressive fuel gases. BVGF: biologically produced methane (max. must not contain condensate. Housing material: AISi, valve disc: aluminium, drive shaft: stainless steel, seals: HNBR. reduction by 2 nominal sizes is possible. Inlet pressure pu: max. 500 mbar (7.25 psi). Pressure differential between inlet pres- sure Pu and outlet pressure p^: max. 150 valve disc: stainless steel, drive shaft: stainless steel. Inlet pressure pu: max. 150 mbar (2.16 psi). Pressure differential...

 Open the catalog to page 4
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.