video corpo

V5832A/5833A,C

V5832A/5833A,C

V5832A/5833A,C

Product catalog summary
General Overview: The V5832A/5833A,C small linear valves are designed for modulating and on/off control of hot and chilled water in fan coil units and small reheaters/recoolers. They are compatible with small electric linear valve actuators and thermoelectric actuators.
Features:
  • Compact size for limited space installations.
  • Long stroke for high-quality performance.
  • Soft seat for low leakage and high rangeability.
  • Various fittings for different connections.
  • Manual operation adjustment cap.
  • Flat surfaces for installation tools.
  • Changeable valve inserts without draining using tool WV108M.
Specifications:
  • Models: Two-way V5832A, Three-way V5833A, Three-way with bypass V5833C.
  • Nominal pressure rating: PN16.
  • Material: Brass body, stainless steel stem, brass plug.
  • Suitable medium: Water with up to 50% glycol.
  • Controlled water temperature: 2 to 120°C.
Flow Capacities and Pressure Ratings:
  • Two-way valves have a rangeability of 100:1.
  • Three-way valves have equal percentage flow characteristics for port A-AB and linear for bypass port B-AB.
  • Close-off pressure ratings vary by model and actuator type.
Operation: The valves feature a built-in return spring for opening or closing force, depending on the model. They can be manually operated during installation phases without a controller or actuator.
Mounting: Ensure correct flow direction and avoid mounting with the stem pointing downward. The valve should be installed stress-free with a tightening torque of 25 to 30 Nm.
Accessories: Connection sets are required for installation, with options for soldering and external thread connections.
Spare Parts: Valve inserts are available as spare parts and can be changed without draining the system using tool WV108M.
See more

Catalog excerpts

V5832A/5833A,C-1

V5832A/5833A,C SMALL LINEAR VALVES PN16 FOR MODULATING AND ON/OFF-CONTROL SPECIFICATION DATA FEATURES • Small size allows installation where space is limited. • Long stroke results in a high-quality characteristic. • Soft seat provides low leakage rate and high rangeability. • Reduced kVS values in the bypass to facilitate hydronic balancing. • Range of fittings available for different connections (soldered, threaded). • Adjustment cap for manual operation. • Flat surfaces on body to fit installation tools. • Flat sealing connections in standard sizes. • Valve inserts changeable without draining by using insert replacement tool WV108M. • 40 mm distance between ports A/AB and the bypass (V5833C, only). SPECIFICATIONS Models Two-way V5832A Three-way V5833A Three-way with bypass V5833C Operation Two-way stem up to open, port A to B; Three-way stem up see tables on page 2 and 3 <0.02% of kvs Brass DN15 (1/2“), DN20 (3/4“) to close, port A to AB Nominal pressure rating PN16 These small linear valves are used in combination with small electric linear valve actuators and thermoelectric actuators for Capacity index (kVS) the control of hot and/or chilled water for fan coil units and L , t small reheaters/recoolers in electric/electronic temperature Leakage rare c°ntr°l systems. Valve body Material Size Trim Stem Stainless steel Plug Brass Suitable medium Water, with max. 50% glycol Controlled water temperature 2...120 °C ® U.S. Registered Trademark Copyright © 2018 Honeywell Inc. • All rights rese

 Open the catalog to page 1
V5832A/5833A,C-2

V5832A/V5833A,C SMALL LINEAR VALVES PN16 - SPECIFICATION DATA Modulating valves Rangeability Two-way valves100:1 Three-way valves Flow characteristic Stroke On/Off valves Stroke Dimensions 100:1 for controlled port Equal percentage port A-AB, linear for bypass port B-AB 6.5 mm 2.5 mm see Fig. 4 on page 5 FLOW CAPACITIES AND CLOSE OFF PRESSURE RATINGSTWO-WAY VALVES Valve *Up to 1000kPa system pressure. **For ON/OFF control, stroke 2.5mm. *For ON/OFF control, stroke 2.5mm.

 Open the catalog to page 2
V5832A/5833A,C-3

V5832A/V5833A, C SMALL LINEAR VALVES PN16 - SPECIFICATION DATA *For ON/OFF control, stroke 2.5mm. OPERATION A built-in return spring in the two-way valve produces an opening force. In the three-way valve and the three-way valve with bypass, the spring produces a closing force on the A to AB ports. The valves are supplied with a screwed-on adjustment cap for manual operation and for protection of the stem. This allows the stem to be set up for filling or initial heating / cooling during the building construction phase without the use of a controller or actuator. The small electric valve actuators...

 Open the catalog to page 3
V5832A/5833A,C-4

V5832A/V5833A,C SMALL LINEAR VALVES PN16 - SPECIFICATION DATA MOUNTING When installing the valve, care must be taken that the flow direction is correct (see section "Typical Operation"). The valve must not be mounted with the stem pointing downward. The adjustment cap must be removed from the valve only when the actuator is fitted. The valve should be installed as stress-free as possible with a tightening torque of 25 to 30 Nm. The valve is supplied complete with mounting instructions. The water quality must meet VDI 2035 requirements. Valves V5832A need two connection sets, valves V5833A three...

 Open the catalog to page 4
V5832A/5833A,C-5

V5832A/V5833A,C SMALL LINEAR VALVES PN16 - SPECIFICATION DATA Allow 130mm for the actuator and clearance for removal Three-way valve with bypass *Modulating valves, only (in the case of ON/OFF valves, the stroke amounts to 2.5 mm and the closure distance to 14 mm).

 Open the catalog to page 5
V5832A/5833A,C-6

V5832A/V5833A,C SMALL LINEAR VALVE PN16 - SPECIFICATION DATA Valve inserts are provided as spare parts for the V5832A and V5833A,C small linear valves. When the tool WV108M is used, the valve inserts can be changed without draining the system. The following valve inserts are interchangeable • Two-way valves: kVS 0.16, 0.25, 0.40, and 0.63 Manufactured for and on behalf of the Environmental & Energy Solutions Division of Honeywell Technologies Sari, Rolle, Z.A. La Piece 16, Switzerland by its Authorized Representative: Home and Building Technologies Honeywell GmbH Boblinger Strasse 17 71101 Schonaich,...

 Open the catalog to page 6

All Honeywell Environmental & Combustion Controls EMEA catalogs and technical brochures

  1. V5832B/V5833A

    4  Pages

  2. VSxF-2/-3/-4

    7  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.