Model Summary
The RHT-MOD series are relative humidity transmitters designed for building automation systems in the HVAC/R industry. They measure relative humidity (rH) and temperature (T) and feature a large touchscreen display for easy configuration. Models include options with or without a relay and are available for wall or duct mounting.

Applications
These devices are used to monitor humidity and temperature in various environments such as offices, public spaces, hospitals, meeting rooms, classrooms, and other commercial applications.

Specifications
  • Measurement Ranges: Temperature: 0...50 °C; Relative Humidity: 0–100%
  • Accuracy: Temperature: <0.5 ºC; Relative Humidity: ±2...3% at 0...50 °C and 10–90% rH
  • Media Compatibility: Dry air or non-aggressive gases
  • Measuring Units: °C and % rH
  • Measuring Element: Temperature: Pt1000; Relative Humidity: Thermoset polymer capacitive sensing element
  • Environment: Operating Temperature: 0...50 °C; Storage Temperature: -20...70 °C; Humidity: 0 to 95% rH, non-condensing
  • Physical Dimensions: 99 x 90 x 32 mm; Weight: 150 g; Material: ABS; Protection Standard: IP20
  • Display: Touchscreen, Size: 77.4 x 52.4 mm
  • Electrical Connections: Power Supply: 24 VAC or VDC, ±10%; Current Consumption: max 90 mA (at 24 V) + 10 mA for each voltage output or 20 mA for each current output
  • Relay Output: SPDT Relay, 250 VAC / 30 VDC / 6 A
  • Communication: Protocol: MODBUS over Serial Line; Transmission Mode: RTU; Interface: RS485
  • Conformance: Meets CE marking requirements, EMC Directive 2014/30/EU, RoHS Directive 2002/95/EC, LVD Directive 2014/35/EU, WEEE Directive 2012/19/EU

Company Certification
The company is certified by DNV GL for ISO 9001, ISO 14001, and RoHS 2 2011/65/EU.
See more

Catalog excerpts

RHT-MOD Humidity transmitter for room with Modbus-1

USER-FRIENDLY MEASURING DEVICES humidity transmitters rht-mod series Wall mount humidity transmitters for building automation systems that use Modbus serial communication protocol RHT-MOD relative humidity transmitters are engineered for building automation systems in the HVAC/R industry. The RHT-MOD measures relative humidity (rH), and temperature (T). RHT-MOD devices are available with large touchscreen display making configuration of the device quick and easy. RHT-MOD series devices include: • Separate field configurable Modbus output for each measurement parameter (rH and T) • One analog output for selected measurement: voltage (0/2-10 V) and current (4-20 mA) • Optional relay output RHT-MOD series devices are commonly used to monitor: • humidity and temperature levels in offices, public spaces, hospitals, meeting rooms and classrooms • humidity and temperature in various commercial applications • humidity and temperature in HVAC/R environment Copyright HK Instruments 2017 www.hkinstruments.fi Datasheet Version 6.0 2017

 Open the catalog to page 1
RHT-MOD Humidity transmitter for room with Modbus-2

Performance Measurement ranges: Temperature: 0...50 °C Relative humidity: 0-100 % Accuracy: Temperature: <0.5 °C Relative humidity: ±2...3 % at 0...50 °C and 10-90 % rH Total error band includes accuracy, hysteresis and temperature effect over 5...50 °C and10-90% rH. Technical Specifications Media compatibility: Dry air or non-aggressive gases Measuring units: °C and % rH Measuring element: Temperature: Pt1000 Relative humidity: Thermoset polymer capacitive sensing element Environment: Operating temperature: 0...50 °C Storage temperature: -20...70 °C Humidity: 0 to 95 % rH, non condensing Physical Dimensions: Case:...

 Open the catalog to page 2

All HK INSTRUMENTS catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.