1. Catalogs
  2. HK INSTRUMENTS
  3. DPTL Differential pressure transmitter for liquids

DPTL Differential pressure transmitter for liquids

DPTL Differential pressure transmitter for liquids

DPTL Differential pressure transmitter for liquids

Product catalog summary
Model Summary
The document provides a summary of differential pressure transmitters for liquids, specifically the DPTL series. These transmitters are designed for use in air-conditioning, heating, and water systems, and can handle mildly corrosive substances. The models vary by measurement range and output type, either voltage or current.

Specifications
Performance: The transmitters have an accuracy of ±1% full scale, with a maximum static pressure of 21 bar. Overpressure limits are 6 bar for ranges 1 and 2.5 bar, and 16 bar for ranges 4 and 6 bar. The response time is 10 ms.
Technical Specifications: The devices measure in bar and operate in ambient temperatures from -10 to 50 °C, with medium temperatures from -10 to 80 °C. They are constructed with ceramic and stainless steel materials, and use EPDM for sealing. The electrical connector follows DIN 43650 standards.
Electrical: For current output models, the supply voltage is 15-24 VDC with a current consumption of max 20 mA, outputting 4-20 mA. Voltage output models require 15-24 VDC or 24 VAC, with power consumption of 0.37 W (VDC) or 0.9 W (VAC), outputting 0-10 V.

Conformance
The products comply with CE marking requirements, including EMC Directive 2014/30/EU, RoHS Directive 2011/65/EU, and WEEE Directive 2012/19/EU. The company is certified by DNV GL for ISO 9001 and ISO 14001 standards.

Model Generation
Models are generated by combining the product series (DPTL), measuring range (e.g., 0...2.5 bar), and output type (V for voltage, C for current). For example, DPTL-2,5-V indicates a voltage output model with a 0...2.5 bar range.
See more

Catalog excerpts

DPTL Differential pressure transmitter for liquids-1

USER-FRIENDLY MEASURING DEVICES pressure The DPTL is made for differential pressure detection in liquids for air-conditioning, heating and water systems. The equipment can withstand mildly corrosive substances and liquids. model summary Description Copyright HK Instruments 2017 www.hkinstruments.fi Datasheet Version 4.0 2017

 Open the catalog to page 1
DPTL Differential pressure transmitter for liquids-2

Performance Accuracy (typ. %/FS): ±1 % Static pressure maximum: 21 bar Overpressure maximum: Ranges 1 & 2.5 bar: 6 bar Ranges 4 & 6 bar: 16 bar Response time: 10 ms Technical Specifications Measuring units: bar Environment: Ambient temperature: -10...50 °C Temperature of medium: -10...80 °C Storage temperature and moisture: -20...50 °C, max 85 % rH Physical Material contacting the medium: Ceramic/Stainless steel A203/1 4305 Sealing material: EPDM Electrical connector: Angle plug according to DIN 43650 Construction A Pressure connectors: Inside thread G1/4” Installation position: Unrestricted Enclosure: Bottom...

 Open the catalog to page 2

All HK INSTRUMENTS catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.