Model Summary:
The DPT-FLOW series includes models DPT-FLOW-1000, DPT-FLOW-2000, DPT-FLOW-5000, and DPT-FLOW-7000, each with different measurement ranges from 0-1000 Pa to 0-7000 Pa. These models are designed for measuring air flow in ducts and on centrifugal fans, available with or without display and autozero functions.
Applications:
The DPT-Flow series is used in HVAC/R systems for air flow monitoring across centrifugal fans and blowers, in-duct air flow monitoring, and VAV applications. They are multifunctional transmitters for building automation, measuring volume flow, velocity, and static and differential pressure.
Specifications:
  • Accuracy: Models 1000 and 2000 have an accuracy of 1% + ±2 Pa for pressures < 125 Pa and 1% + ±1 Pa for pressures > 125 Pa. Models 5000 and 7000 have an accuracy of 1.5% + ±2 Pa for pressures < 125 Pa and 1.5% + ±1 Pa for pressures > 125 Pa.
  • Thermal Effects: Temperature compensated across full capability.
  • Overpressure: Proof pressure is 25 kPa, and burst pressure is 30 kPa.
  • Response Time: Selectable from 1.0 to 20 seconds via menu.
  • Media Compatibility: Suitable for dry air or non-aggressive gases.
  • Operating Environment: Temperature range from -10 to 50 °C, with autozero calibration from -5 to 50 °C. Humidity range is 0 to 95% rH, non-condensing.
Physical and Electrical Specifications:
  • Dimensions: 90.0 x 95.0 x 36.0 mm, weight 150 g.
  • Materials: Case made of ABS, lid of PC, duct connectors of ABS, and tubing of PVC.
  • Protection Standard: IP54.
  • Display: 2-line display with 12 characters per line.
  • Electrical Connections: 4-screw terminal block, with voltage and current output options.
Conformance:
The devices meet CE marking requirements, including EMC Directive 2014/30/EU, RoHS Directive 2011/65/EU, and WEEE Directive 2012/19/EU.
AZ-Calibration:
The AZ-calibration function provides automatic zeroing, eliminating output signal drift and the need for manual calibration. It is maintenance-free and ensures long-term accuracy.
See more

Catalog excerpts

DPT-Flow Flow transmitter for HVAC systems-1

USER-FRIENDLY MEASURING DEVICES air flow and velocity transmitters dpt-flow Multifunctional air flow transmitters for building automation systems The DPT-Flow series air flow transmitters are engineered for building automation in the HVAC/R industry. The most technologically advanced transmitters on the market, measuring volume flow, velocity, and static and differential pressure. The DPT-Flow series devices can be connected directly to the pressure measurement points in a centrifugal fan, providing accurate flow measurement of the fan. The smart user interface enables easy selection of settings according to the selected fan or in-duct measurement probe. DPT-Flow series devices include: • Two field selectable functions: o Measure and monitor in-duct volume flow, velocity or differential pressure o Measure and monitor air flow across centrifugal fans • Multiple field selectable measurement units: o Volume flow: m3/s, m3/h, cfm, l/s o Velocity: m/s, ft/min o Pressure: Pa, inWC, mmWC, kPa, mbar, psi • Unique proportional output options: o Volume flow or velocity: voltage (0-10 V) or current (4-20 mA) o Pressure: voltage (0-10 V) or current (4-20 mA) DPT-Flow series device options offer: • AZ (autozero) function for automatic zero point calibration, eliminating the need for periodic manual autozeroing to ensure long term accuracy similar products • AVT series air velocity transmitters • DPT-R8 series 8-range differential pressure transmitters • DPT-MOD series differential pressure transmitters with Modbus configuration DPT-Flow series devices are commonly used in HVAC/R systems for: • air flow monitoring across centrifugal fans and blowers • in-duct air flow monitoring • VAV applications model summary Copyright HK Instruments 2017 www.hkinstruments.fi Datasheet Version 6.0 2017

 Open the catalog to page 1
DPT-Flow Flow transmitter for HVAC systems-2

Performance Accuracy (from applied pressure): Models 1000 and 2000: Pressure < 125 Pa = 1 % + ±2 Pa Pressure > 125 Pa = 1 % + ±1 Pa Models 5000 and 7000: Pressure < 125 Pa = 1.5 % + ±2 Pa Pressure > 125 Pa = 1.5 % + ±1 Pa (Accuracy specifications include: general accuracy, temperature drift, linearity, hysteresis, long term stability, and repetition error) Thermal effects: Temperature compensated across the full spectrum of capability Overpressure: Proof pressure: 25 kPa Burst pressure:30 kPa Zero point calibration: Automatic autozero or manual pushbutton Response time: 1.0-20 s, selectable via...

 Open the catalog to page 2

All HK INSTRUMENTS catalogs and technical brochures

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.