1. Catalogs
  2. heol design
  3. T202 - PTP client time station, with PoE

T202 - PTP client time station, with PoE

T202 - PTP client time station, with PoE

T202 - PTP client time station, with PoE

Product catalog summary
Overview: The HEOL-T202 is a PTP client time station designed for synchronizing automated systems and timestamping events in industrial environments. It supports IEEE 1588-2008 standards and offers features like pulse generation, IRIG output, and event input.
Specifications: The T202 module can synchronize with a PTP master clock with 1µs accuracy. It supports both multicast and unicast addressing modes and operates with a two-step clock mechanism. The device can maintain accurate time even if the connection to the master clock is lost, thanks to its OCXO option.
Power and Interfaces: The T202 supports Power over Ethernet (PoE) and can operate on various power inputs, including 12/60VDC and 85/250VAC. It features multiple interfaces such as RS232/RS422, Ethernet, and alarm relay outputs.
Environmental Conditions: The device operates in temperatures ranging from 0/50°C to -40/+70°C, depending on the option selected. It is compliant with various environmental and safety standards, including EN55022/55011 and IEC/EN 60950.
Compliance and Standards: The T202 module complies with RoHS standards and has passed several immunity and emission tests, ensuring its reliability in various industrial settings.
Ordering Information: The T202 is available in different configurations, including compact and rack-mounted housings. Options for oscillators, power inputs, and additional features like IRIG output and secondary event input can be specified when ordering.
See more

Catalog excerpts

T202 - PTP client time station, with PoE-1

HEOL DESIGNT202, IEEE 1588 / PTP Client Time Station, with pulse generator, IRIG output, and event input. 1 Bd d'Armor - 22300 LANNION - FRANCE [email protected] 1 HEOL DESIGN © 2015 All Rights Reserved. All specifications subject to change without notice.

 Open the catalog to page 1
T202 - PTP client time station, with PoE-2

DATA SHEET HEOL-T202 : PERFORMANCE and EASY INTEGRATION The T202 module is a PTP client station, able to synchronize automated systems and timestamp events in an industrial environment. As the T202 doesn’t integrate GPS antenna, you can install it anywhere in your system (it is just necessary to connect it to your LAN, so it can synchronize to an external PTP server – T200 GPS PTP master clock for example). Using the Precision Time Protocol (IEEE1588), the T102 can be synchronized with 1µs accuracy to PTP master clock. The PTP V2 implementation of the HEOL-T202 is fully compliant to the IEEE...

 Open the catalog to page 2
T202 - PTP client time station, with PoE-3

DATA SHEET Historic data can be backed-up to an EEPROM (over 8000 status records). The Power On Ethernet enables installation of the HEOL-T202x without the need for additional cables to provide power. It also offers redundancy of the AC/DC in case of failure of one of them. The T202 is available in 2 different metal housings, either compact or 19’’ rack mounted form factor. This rack unit displays on a LCD module the status and timing information. OCXO or TCXO Clock Event inputs External Events TOP/pps IRIG Sync outputs PTP + NTP (synchro and events) HTTP (config) SNMP (alarms and events) SMTP...

 Open the catalog to page 3
T202 - PTP client time station, with PoE-4

1 Bd d'Armor - 22300 LANNION - FRANCE [email protected] 4 HEOL DESIGN © 2015 All Rights Reserved. All specifications subject to change without notice.

 Open the catalog to page 4
T202 - PTP client time station, with PoE-5

■ According to ^ ^ directive, the HEOL-T202 module has passed the following tests : > EN55022/55011 class B : conducted and radiated emissions. > EN61000-4-2: Immunity to electrostatic discharges. > EN61000-4-3: Immunity tests on electromagnetic fields radiated at radioelectrical frequencies, with 10V/m electromagnetic field. > EN61000-4-4: Immunity to rapid transients. > EN61000-4-6: Immunity tests on conducted interference, induced by radioelectrical fields. > EN61000-4-8: Immunity to Power frequency magnetic field (30 A/m) > EN61000-4-11: Voltage dips, short interruptions and voltage variations...

 Open the catalog to page 5
T202 - PTP client time station, with PoE-6

ORDERING PART NUMBER DC/POE: DC+Power Ethernet AC : 110 to 250V (Rack only) • I/O option I/O connector mounted — • Oscillator option - OCXOSR : standard (0 / +50°C) OCXOMR : medium (-20 / +65°C) OCXOHR : high (-40 / +70°C) If other options are needed, just add the part number of these options at the end of the T202 part number : -422 for RS422 serial port instead of RS232 -EVENT2 for secondary Event input -PPSREL for PPS/TOP output on fast static relay -RTC for fast start without GPS satellites 1 Bd d'Armor - 22300 LANNION - FRANCE [email protected] 6 © 2015 All Rights Reserved. All specifications...

 Open the catalog to page 6
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.