complete set of HYAPF active power filter(abbreviated as active filter)
4Pages

{{requestButtons}}

Catalog excerpts

complete set of HYAPF active power filter(abbreviated as active filter) - 1

HENGYI ELECTRIC GROUP Complete set of HYAPF ac�ve power filter (abbreviated as ac�ve filter) 1 Brief introduc�on and schema�c diagram of filtering effect Wall mounted module HYAPF ac�ve filter can detect the loaded current in a real �me through the external current transformer, extrac�ng the harmonic components of the loaded current calculated by the internal DSP, and then deliver to the internal IGBT through PWM signal. The control inverter will produce current with the same size and opposite direc�on as the loaded harmonic and inject it into the power grid for compensa�ng harmonic current, thus to filter the func�ons. Harmonic compensa�on: APF can filter two to fi�y �mes of harmonic at the same �me. Reac�ve power compensa�on: Capaci�ve and induc�ve (from -1 to 1) step-less compensa�on Three phase unbalance compensa�on: Three phase ac�ve power unbalance compensa�on, Three phase reac�ve power unbalance compensa�on and phase compensa�on. The switching �mes of semiconductors can be over 10000 �mes per second, with quick response and instant management. The designed life�me can be over than 100 thousand hours (more than ten years). Schema�c diagram of filtering effect of HYAPF ac�ve power filter Current Transformer S2 quick response and instant management Analysis of current sampling signal Semiconductor emission power Drawer module(LCD op�onal) The powerinstantly launched by the semiconductors with the same size and opposite direc�on will be balanced out with the harmonic in the power grid, instantly elimina�ng the harmonic and protec�ng the normal working of the electrical system. 2 Model and meanings HY APF -400V -50A /4L (Drawer module) No: Drawer module, A: Set cabinet type, B:Wall mounted type (op�onal for three types) 4L:Three phase four wire 3L: three phase three wire Capacity: 50A ( 35A, 50A, 75A and 100A to be op�onal) Voltage grade: 400V Ac�ve filter Corporate code 3 Normal working condi�on and installa�on condi�on 3.1 Environmental temperature: -10℃ ~ +40℃ 3.2 Rela�ve humidity: :5%~ 95% without condensa�on. 3.3 Al�tude: ≤1500m, between 1500 ~ 4000m, according to GB/T3859.2, the power will be lowered by 1% when adding 100

Open the catalog to page 1
complete set of HYAPF active power filter(abbreviated as active filter) - 2

4.1 Rated input line voltage: 400V(-20% ~ +20%) 4.2 Power grid frequency: 50Hz (range: 45Hz ~ 55Hz) 4.3 Power grid structure: three phase three wire, three phase four wire (400V) 4.5 Circuit topology: Tri-level 5.1 Single module capacity: 400V (35A, 50A, 75A and 100A to be optional) 5.3 Target power factor: 1 5.4 Intelligent air cooling: with good ventilation condition 6.1 Communication interface: RS485, CAN interface 6.2 Communication protocol: electrical total protocol, Modbus protocol 6.3 Module displaying interface: LCD multifunctional touch color screen 6.4 With PC terminal software:...

Open the catalog to page 2
complete set of HYAPF active power filter(abbreviated as active filter) - 3

HENGYI ELECTRIC GROUP 8 Selec�on table for ac�ve power filter set cabinet series Product Model HY-APF-400V- Outline size (width*depth*height) 9 Wifi module (mobile APP remote control) or GPRS module (controlled by PC terminal) 9.1 It can addi�onally be op�onal for Wifi module (mobile APP remote control) or GPRS module (controlled by PC terminal). Install GPRS PC terminal

Open the catalog to page 3
complete set of HYAPF active power filter(abbreviated as active filter) - 4

Wiring diagram 11 Examples for applicable industries Medical industry Water treatment industry Tex�le industry Shipping industry electric railway power distribu�on system Data center Commercial building 12 Order �ps 12.1 Users need to provide some features of the applicable site or to be customized a�er measuring data.

Open the catalog to page 4

All Hengyi Electrical Co. catalogs and technical brochures

  1. HYSVG Sta