1. Catalogs
  2. Helmholz GmbH & Co. KG
  3. TB20-C, bus coupler PROFINET IO

TB20-C, bus coupler PROFINET IO

TB20-C, bus coupler PROFINET IO

TB20-C, bus coupler PROFINET IO

Product catalog summary
Overview
The TB20-C is a PROFINET IO bus coupler designed to connect a PROFINET bus to TB20 peripheral modules. It supports hot-swapping, allowing modules to be replaced during operation, and can accommodate up to 63 modules. The device includes a 24 V DC power supply and an integrated power supply unit for peripheral modules.
Specifications
  • Power Supply: 24 V DC, 18...28 V DC, with a current draw of 75 mA without modules and a power supply for modules at 5 V DC, max 2.5 A.
  • Dimensions: 73 x 35 x 110 mm, Weight: Approx. 115 g.
  • PROFINET Interface: 2 ports, Ethernet physical layer, 100 Mbps full duplex transmission rate, 340 bytes I/O image size.
  • USB Interface: 1 Mini-USB port, Full-speed USB 1.1 device, with 1.5 kV isolation voltage.
  • Environmental Conditions: Operating temperature 0 °C to +60 °C, storage temperature -20 °C to +80 °C, relative humidity 95% without condensation, protection rating IP 20.
Features
  • Integrated 2-port switch, Conformance Class C, Media Redundancy Protocol (MRP), automatic addressing, topology detection, and diagnostic alarms.
  • Supports a minimum cycle time of 250 µsec and an IRT bridge delay of less than 3 µsec.
  • Includes a concealed "factory reset" switch for restoring factory settings.
  • Integration using GSDML file and equipped with 7 LEDs, one of which is bi-color.
Certifications
  • CE, UL certified, compliant with RoHS and REACH standards.
  • Noise immunity and interference emission standards: DIN EN 61000-6-2 and DIN EN 61000-6-4.
  • Vibration and shock resistance: DIN EN 60068-2-6:2008 and DIN EN 60068-2-27:2010.
Applications
The TB20-C is suitable for industrial environments requiring reliable and flexible I/O systems with the ability to perform diagnostics, parameter configuration, and firmware updates via the "TB20 ToolBox".
See more

Catalog excerpts

TB20-C, bus coupler PROFINET IO-1

TB20-C, bus coupler PROFINET IO PROFINET IO Modules can be replaced during operation (hot-swapping) 24 V DC power supply Integrated power supply unit for powering peripheral modules (2.5 A) Supplies the system’s I/O voltage (24 VDC) USB device port for online diagnostics, configuring parameters, setup, and firmware updates with "TB20 ToolBox" TB20 ToolBox simulation for commissioning the I/O system without a higher-level controller in order to test the system's operation (I/O check) Concealed "factory reset" switch for restoring the module to its factory settings I/O device as per PROFINET IO (IEC 61158-6-10) Integrated 2-port switch Full-duplex transmission rate of 100 Mbps 340 byte I/O data Up to 63 peripheral modules Conformance Class C Media Redundancy Protocol (MRP) Automatic addressing / hot-swapping (LLDP, DCP) Topology detection I&M data Diagnostic alarms, process alarms, pull/plug alarms Integration using GSDML file 7 LEDs, one of them bi-color The PROFINET bus coupler is designed to connect a PROFINET bus to TB20 peripheral modules. It can accommodate up to 63 modules of any kind connected in series with the bus coupler. The bus coupler supports hot-swapping for replacing modules during operation. In addition, it will recognize all connected peripheral modules and assign each module the corresponding inputs/outputs from the process image table. A functioning TB20 configuration will always require a bus coupler and at least one peripheral module. Technical specifications General information Order number Article name Bus coupler PROFINET IO, 24 V power supply connector, bus cover element, base module Dimensions (DxWxH) PROFINET interface Number Physical layer Transmission rate 100 Mbps full duplex Helmholz GmbH & Co. KG | Hannberger Weg 2 | 91091 Großenseebach | Germany Phone +49 9135 7380-0 | Fax +49 9135 7380-110 | [email protected] | www.helmholz.de Änderungen und Irrtümer vorbehalten. 04-20

 Open the catalog to page 1
TB20-C, bus coupler PROFINET IO-2

Powered by TCPDF (www.tcpdf.org) integrated switch Conformance Class C, Media Redundancy Protocol (MRP), automatic addressing / topology detection (LLDP, DCP), PTCP, statistics counter Alarm functions Diagnostic alarms, process alarms, pull/plug alarms Minimum cycle time Isolation voltage Electrical isolation Number of modules that can be connected in series Voltage supply Current draw Current draw without modules (internal) Power supply for modules Power dissipation Installation position Ambient conditions Ambient temperature Transport and storage temperature Protection rating Pollution degree...

 Open the catalog to page 2
*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.